2. On field supplied terminations for side wall exit, ex­
haust piping may extend a maximum of 12 inches
(305MM) for 2" PVC and 20 inches (508MM) for 3"
(76MM) PVC beyond the outside wall.
3. If exhaust piping must be run up a side wall to position
above snow accumulation or other obstructions, pip­
ing must be supported every 24 inches (610MM).
When exhaust piping must be run up an outside wall,
any reduction in exhaust pipe size must be done after
the final elbow.
4. Distance between exhaust pipe terminations on multi­
ple furnaces must meet local codes.
12" (305MM)
ABOVE AVE.
SNOW
ACCUMULATION
1/2" (13MM) FOAM
3" (76MM) OR
2" (51MM) PVC
PROVIDE SUPPORT
FOR EXHAUST LINES
NON-DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
FIGURE 40
EL296UHV NON-DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
SIZE TERMINATION
PIPE PER TABLE 27.
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
NOTE - Do not discharge exhaust gases directly into any chimney or vent stack. If ver­
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus­
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 41
Condensate Piping
This unit is designed for either right‐ or left‐side exit of con­
densate piping in upflow applications. In horizontal applica­
tions, the condensate trap must extend below the unit. An
8" service clearance is required for the condensate trap.
Refer to figure 42 for condensate trap locations. Figures 50
(3/4" drain connection) and 51 (1/2" drain connection)
shows trap assembly using 1/2" PVC or 3/4" PVC.
SIZE TERMINATION
PIPE PER TABLE
27.
INSULATION
UNCONDITIONED
ATTIC SPACE
STRAIGHT-CUT OR
ANGLE-CUT IN DIRECTION
OF ROOF SLOPE
EXHAUST VENT
1/2" (13MM)
WEATHERPROOF
INSULATION
SHOULDER OF FITTINGS
PROVIDE SUPPORT
OF PIPE ON TOP PLATE
EXTERIOR
PORTION OF
CHIMNEY
NOTE - If necessary the condensate trap may be installed
up to 5' away from the furnace. Use PVC pipe to connect
trap to furnace condensate outlet. Piping from furnace
must slope down a minimum of 1/4" per ft. toward trap.
1 - Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length of
PVC pipe required to reach available drain.
2 - For furnaces with a 1/2" drain connection use a 3/8
allen wrench and remove plug (figure 42) from the cold
end header box at the appropriate location on the side
of the unit. Install field-provided 1/2 NPT male fitting
into cold end header box. For furnaces with a 3/4"
drain connection use a large flat head screw driver or a
1/2" drive socket extension and remove plug. Install
provided 3/4 NPT street elbow fitting into cold end
header box. Use Teflon tape or appropriate pipe dope.
3 - Install the cap over the clean out opening at the base
of the trap. Secure with clamp. See figure 50 or 51.
4 - Install drain trap using appropriate PVC fittings, glue
all joints. Glue the provided drain trap as shown in fig­
ures 50 and 51. Route the condensate line to an open
drain. Condensate line must maintain a 1/4" down­
ward slope from the furnace to the drain.
CONDENSATE TRAP AND PLUG LOCATIONS
(Unit shown in upflow position)
Trap
(same on
right side)
1-1/2 in.
NOTE - In upflow applications where side return
air filter is installed on same side as the conden­
sate trap, filter rack must be installed beyond
condensate trap or trap must be re-located to
avoid interference.
5 - Figures 45 and 47 show the furnace and evaporator
coil using a separate drain. If necessary the conden­
sate line from the furnace and evaporator coil can
drain together. See figures, 46, 48 and 49.
Upflow furnace (figure 48) - In upflow furnace applica­
tions the field provided vent must be a minimum 1" to a
maximum 2" length above the condensate drain outlet
connection. Any length above 2" may result in a flood­
ed heat exchanger if the combined primary drain line
were to become restricted.