Mitsubishi Electric FR-D720-070 Instruction Manual page 95

Table of Contents

Advertisement

Frequency setting by external terminals
(2) Multi-speed setting for 4th speed or more (Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
Frequency from 4th speed to 15th speed can be set according to the combination of the RH, RM, RL and REX signals. Set the
running frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (In the initial value setting, 4th speed to 15th speed are invalid).
For the terminal used for REX signal input, set "8" in any of Pr. 178 to Pr. 182 (input terminal function selection) to assign the
function.
Speed 10
Speed 11
Speed 12
Speed 9
Speed 13
Speed 8
Speed 14
Speed 15
ON ON ON ON
RH
ON ON
ON ON
RM
ON
ON
ON
ON
RL
ON
ON
ON ON ON ON ON ON
REX
*1
∗1
When "9999" is set in Pr. 232 Multi-speed setting (speed 8), operation is
performed at frequency set in Pr. 6 when RH, RM and RL are turned off and
REX is turned on.
REMARKS
The priorities of the frequency commands by the external signals are "Jog operation > multi-speed operation > terminal 4 analog
input > terminal 2 analog input".
(Refer to page 153 for the frequency command by analog input)
Valid in the external operation mode or PU/external combined operation mode (Pr. 79 = "3" or "4").
Multi-speed parameters can also be set in the PU or external operation mode.
Pr. 24 to Pr. 27 and Pr. 232 to Pr. 239 settings have no priority between them.
When Pr. 59 Remote function selection ≠ "0", multi-speed setting is invalid as RH, RM and RL signals are remote setting signals.
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 182 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Parameters referred to
Pr. 15
Jog frequency
Refer to page 91
Pr. 59 Remote function selection
Refer to page 93
Pr. 79 Operation mode selection
Refer to page 165
Pr. 178 to Pr. 182 (input terminal function selection)
90
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Forward rotation
Time
Multi-speed
selection
Multi-speed operation connection example
Refer to page 113
Inverter
STF
REX
10
Frequency setting
RH
2
potentiometer
RM
5
RL
SD