Mitsubishi Electric FR-D720-070 Instruction Manual page 51

Table of Contents

Advertisement

(3)
Selection of rated sensitivity current of earth (ground) leakage current breaker
When using the earth leakage current breaker with the inverter circuit, select its rated sensitivity current as follows,
independently of the PWM carrier frequency.
Breaker designed for harmonic and
surge suppression
Rated sensitivity current:
I∆n≥10×(Ig1+Ign+Igi+Ig2+Igm)
Standard breaker
Rated sensitivity current:
I∆n≥10×{Ig1+Ign+Igi+3×(Ig2+Igm)}
Example of leakage current
Example of leakage current of
of three-phase induction motor
cable path per 1km during the
during the commercial
commercial power supply operation
power supply operation
when the CV cable is routed in
metal conduit
(200V 60Hz)
(200V 60Hz)
1.0
120
0.7
0.5
100
0.3
8 0
0.2
0.1
6 0
0.07
4 0
0.05
0.03
2 0
0.02
0
2 3.5
8 1422
38
80
150
0.1 0.2
0.75
5.5
30
60
100
0.4
Cable size (mm
)
Motor capacity (kW)
2
<
>
Example
Selection example (in the case of the left figure (400V class
2
× 5m
2
× 60m
5.5mm
5.5mm
ELB
Noise
filter
Inverter
IM
400V
2.2kW
Ig1
Ign
Ig2
Igm
Igi
Rated sensitivity current (mA) (≥ Ig × 10)
NOTE
Install the earth leakage breaker (ELB) on the input side of the inverter.
In the
connection earthed-neutral system, the sensitivity current is blunt against an earth (ground) fault in the
inverter output side. Earthing (Grounding) must conform to the requirements of national and local safety regulations
and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards)
When the breaker is installed on the output side of the inverter, it may be unnecessarily operated by harmonics even
if the effective value is less than the rating.
In this case, do not install the breaker since the eddy current and hysteresis loss will increase, leading to temperature
rise.
General products indicate the following models. ...... BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA, NV-2F earth leakage
relay (except NV-ZHA), NV with AA neutral wire open-phase protection
The other models are designed for harmonic and surge suppression ....NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-
C2, earth leakage alarm breaker (NF-Z), NV-ZHA, NV-H
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
EMC and leakage currents
Ig1, Ig2:
Leakage currents in wire path during commercial
power supply operation
Ign:
Leakage current of inverter input side noise filter
Igm:
Leakage current of motor during commercial power
supply operation
Igi:
Leakage current of inverter unit
Example of leakage current per 1km during
the commercial power supply operation
when the CV cable is routed in metal conduit
(Three-phase three-wire delta
connection 400V60Hz)
120
100
8 0
6 0
4 0
2 0
0
2 3.5
8 1422
38
80
150
2.2
5.5 11
20
5.5
30
60
100
1.5
3.7
7.5
15
Cable size (mm
)
2
For " " connection, the amount of leakage current is appox.1/3 of the above value.
Breaker Designed for
Harmonic and Surge
Suppression
1
× 66 ×
Leakage current Ig1 (mA)
3
Leakage current Ign (mA)
Leakage current Igi (mA)
1
× 66 ×
Leakage current Ig2 (mA)
3
Motor leakage current Igm (mA)
Total leakage current (mA)
Example of leakage current of three-
phase induction motor during the
commercial power supply operation
(Totally-enclosed fan-cooled
type motor 400V60Hz)
2. 0
1. 0
0. 7
0. 5
0. 3
0. 2
0. 1
1.5
3.7
7.5
15
2.2
5.5
11
20
Motor capacity (kW)
connection))
Standard Breaker
5m
= 0.11
1000m
0 (without noise filter)
1
60m
= 1.32
1000m
0.36
2.79
6.15
3
30
100
39

Advertisement

Table of Contents
loading

Table of Contents