Adjust the output torque (current) of the motor
(2) Selection method of General-purpose magnetic flux vector control
Perform secure wiring.
(Refer to page 14)
Display the extended function parameters.
(Pr. 160) (Refer to page 162)
Set the motor. (Pr. 71)
Motor
Mitsubishi standard
SF-JR
motor
SF-HR
Mitsubishi high
Others
efficiency motor
SF-JRCA 4P
Mitsubishi constant-
SF-HRCA
torque motor
Others (SF-JRC, etc.)
Other standard motor
Other constant-
torque motor
∗1
Refer to page 103 for other settings of Pr. 71.
∗2
Refer to page 105 for offline auto tuning.
Set the motor capacity.
(Pr. 80) (Refer to page 74)
Set the operation command. (Refer to page 165)
Test run
As required
Perform offline auto tuning. (Pr. 96) (Refer to page 105)
Set motor excitation current. (Pr. 82) (Refer to page 105)
Set slip compensation. (Pr. 245, Pr. 246, Pr. 247) (Refer to page 78)
NOTE
Uneven rotation slightly increases as compared to the V/F control. (It is not suitable for machines such as grinding
machine and wrapping machine which requires less uneven rotation at low speed.)
When a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is connected between the inverter and motor, output
torque may decrease.
76
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Set "0" in Pr. 160 to display the extended function parameters.
Pr. 71 Setting ∗1
0 (initial value)
40
3
Offline auto tuning is necessary.
1
50
13
Offline auto tuning is necessary.
3
Offline auto tuning is necessary.
13
Offline auto tuning is necessary.
Set motor capacity (kW) in Pr. 80 Motor capacity.
(V/F control is performed when the setting is "9999" (initial value).
Select the start command and speed command.
(1)Start command
1)Operation panel: Setting by pressing
of the operation panel
2)External command: Setting by forward rotation or reverse rotation
command (terminal STF or STR)
(2)Speed command
1)Operation panel: Setting by turning
of the operation panel
2)External analog command (terminal 2 or 4):
Give a speed command using the analog signal input to terminal 2 (or
terminal 4).
3)Multi-speed command:
The external signals (RH, RM, RL) may also be used to give speed
command.
Remarks
∗2
∗2
∗2
∗2