Rear Vent Configuration With Vertical Termination - Lopi 564 GSR2 25K CF Installation Manual

Deluxe fireplace
Table of Contents

Advertisement

Finalizing the Installation

Rear Vent Configuration with Vertical Termination

The termination must fall
within the shaded area shown
in the chart. Use the
indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°)
may be used.
Only one horizontal elbow
may be used.
Use 8" (203mm) diameter
vent for the initial horizontal
run and 90° upward elbow.
Then attach the 8" (203mm)
to 6-5/8" (168mm) reducer
(Travis part # 98900165) to
the elbow. Use 6-5/8"
(168mm) diameter vent for
the remaining vent.
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
(for qualified installers only)
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
Exhaust Restrictor # 3
Intake Restrictor # 2
Diffuser Position # 2
10 feet (3m)
5 feet (1.5m)
0 feet
H2
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
5/15/2019 - 1508
Exhaust Restrictor # 5
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 2
Intake Restrictor # 1
Diffuser Position # 2
Attach 6-5/8" reducer to the top of
the first upward turning elbow.
This is considered a
vertical elbow
564 GSR2 25K CF (AUST)
27
40' max (12m)
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet