To reset the Relay Function to use Standard Alarms, enter the desired Relay Set Up
(P100).
Control
Off
Level
In Bounds
Out of Bounds
General
Rate of Change
Temperature
Loss of Echo (LOE)
Cable Fault
Pump
Fixed Duty Assist
1.
When reading and setting this parameter through Modbus or SmartLinx
communications the parameter values are mapped to different numbers.
See the relevant SmartLinx manual for Modbus information.

Independent Relay Setpoints

Relay ON and OFF Setpoint values set the critical points (based on the Relay Function)
where, in RUN mode:
Relay status indicators are switched ON and OFF
Alarm Indicators (if programmed) are switched ON or OFF
Relays are energized and de-energized
For most Relay Functions, setpoint values represent material levels, entered in Units
(P005) or percent of Span (P007) as referenced to Empty (P006). Temperature alarm
values are entered in degrees Celsius (°C).
Rate alarms are entered in Units / minute or percent of Span per minute. A positive value
is entered for a filling rate alarm; negative for emptying.
7ML19981BD02
Values For P111
1
Type
#
0* Relay set off, no action (preset)
1 Based on level setpoints ON and OFF
When level enters the range between ON and OFF
2
setpoints
When level exits the range between ON and OFF set-
3
points
4 Based on rate setpoints ON and OFF
5 Based on temperature setpoints ON and OFF
6 When echo is lost
7 When the circuit to a transducer is opened
At fixed ON and OFF setpoints and allows multiple
50
pumps to run or for rake control
AiRanger DPL Plus – INSTRUCTION MANUAL
Relay Control
Page 45