Requirements For Gas Heat; Condensate Drain Configuration - Trane YHC092E Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent -gas/electric
Table of Contents

Advertisement

Installation
4. Disconnect the 5" pipe nipple and union from the
"Through the Base Gas" kit assembly.
5. Using pipe sealant, attach the 6½" nipple and gas
shutoff assembly to the 90° elbow on the gas supply
line.
6. Using pipe sealant, attach the 5" pipe nipple and union
to the street el attached to the gas valve.
7. Connect 5" pipe nipple and union to 6½" nipple and
gas shutoff assembly.
Figure 36. Typical through the base gas installation

Requirements for Gas Heat

Note: The unit gas train and Optional Through The Base
Gas Shut-Off Valve are rated at 1/2 PSIG maximum.
A pressure reducing regulator is recommended to
prevent this maximum from being exceeded.
These components must be isolated during field
gas piping test that exceed 1/2 PSIG. It is
recommended that the field piping be capped prior
to the unit gas train or Optional Through The Base
Gas Shut-Off Valve if present.
Gas supply line properly sized and connected to the
unit gas train.
All gas piping joints properly sealed.
Gas piping leak checked with a soap solution. If piping
connections to the unit are complete, do not pressurize
piping in excess of 0.50 psig or 14" W.C. to prevent
component failure.
Drip leg Installed in the gas piping near the unit.
Minimum gas supply pressure should be 4.5" W.C.
Maximum gas supply pressure must not exceed 14.0"
W.C.
Manifold pressure for single stage heaters should be
set to 3.3" W.C.
Manifold pressure for two stage heaters should be set
to 3.5" W.C. on HIGH FIRE and 1.8" W.C. on LOW FIRE.
Flue Exhaust clear of any obstruction.
30

Condensate Drain Configuration

An evaporator condensate drain connection is provided
on each unit. Refer to
Figure 16, p. 21
for the appropriate drain location.
The condensate drain pan is factory installed to drain
condensate to the back side of the unit. See
and
Figure 17, p.
22. It can be converted to drain
condensate out the front side of the unit or through the
base.
To Convert Drain Condensate Out the Front of
Unit:
1. Remove evaporator access panel and supply air access
panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit and
rotate 180°.
4. Slide the condensate drain pan back into the unit, align
the drain with the grommeted opening in the rear
support panel and push until the coupling is seated in
the grommet.
5. Replace the front support panel by aligning the panel
with tabs in the raceway. Align the condensate drain
pan support in the grommeted hole as the panel is put
in place.
6. Replace evaporator access panel and supply air access
panels.
To Convert Drain Condensate Through the
Base of Unit:
1. Remove evaporator access panel and supply air access
panels.
2. Remove the support panel that the condensate drain
pan exits through.
3. Slide the condensate drain pan out of the unit.
4. Place on a level surface in the position it was removed
from the unit.
5. Remove the plug knockout in the bottom of the drain
pan to convert it to through the base drainage.
6. Plug the original condensate drain opening with a field
supplied 3/4" NPT plug.
7. Slide the condensate drain pan back into the unit, align
the drain support with the grommeted opening in the
rear support panel and push until the support is seated
in the grommet.
8. Replace the front support panel by aligning the panel
with tabs in the raceway. Align the plugged condensate
drain pan coupling in the grommeted hole as the panel
is put in place.
9. Replace evaporator access panel and supply air access
panels.
and
Figure 17, p. 22
Figure 16, p. 21
RT-SVX21K-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents