6
Temperature class: T4. The maximum surface temperature on
the equipment is 135°C (275°F) and the ignition temperature
of the gas or vapour is between 135°C (275°F) and 200°C
(392°F).
The sensor housing protection is IP 65 and the ambient tem-
perature must be between -30°C (-22°F) and +60°C (140°F).
Liability
Following commissioning, the total responsibility lies with the
owner.
Marking
The sensors and the barrier are all marked with blue signs
according to the pictures below.
A5E00822935 Ex-sign Sensor transmitter
s
Östergårdsg. 2-4, Box 5065, 402 22 Göteborg, Sweden
Gas Analyser model CD 6 Transmitter
Art. no. 7MB6122-
Warning: For installation follow system drawing 4100-2082
0044
DEMKO 06 ATEX 139648X
Ambient temperature range: -20°C ≤ Tamb ≤ +60°C
Ingress Protection: IP65 (EN60529:1991/A1:2000)
IECEx ULD 06.0011X Ex ia IIC T4
Supply: none
Made in France
A5E00822939 Ex-sign Sensor receiver
s
Östergårdsg. 2-4, Box 5065, 402 22 Göteborg, Sweden
Gas Analyser model CD 6 Receiver
Art. no. 7MB6122-
Warning: For installation follow system drawing 4100-2082
0044
DEMKO 06 ATEX 139648X
Ambient temperature range: -20°C ≤ Tamb ≤ +60°C
Ingress Protection: IP65 (EN60529:1991/A1:2000)
IECEx ULD 06.0011X Ex ia IIC T4
Ui: 25V
Ci: 40nF
Supply: A5E00814175/001-006
Installation Guidelines
Siemens Laser Analytics AB
II (1)GD T135 °C
EEx ia IIC T4
S/N:
Prod. year:
89
Siemens Laser Analytics AB
II 1 GD T135 °C EEx ia IIC T4
S/N:
Ii: 150mA
Li: 0,22mH
Prod. year:
Made in France
89
ATEX manual for LDS 6
A5E01206710-02

Advertisement

Table of Contents
loading

Table of Contents