Display Functions; User Settings - HP Enterprise R1500 G4 UPS User Manual

Hide thumbs Also See for Enterprise R1500 G4 UPS:
Table of Contents

Advertisement

2. User Interface

2.3 Display functions

Press the
structure. Press the
menu.
Display Function Menu
Main menu
Measurements
Control
Settings
Fault log
Identification

2.4 User settings

The following table displays the options that can be changed by the user.
Local settings
In/Out settings
Continued
Page 9
button to activate the menu options. Use the
button to select an option. Press the
Submenu
Load Segments
Start battery test
Reset fault state
Restore factory settings Returns all settings to original values
Reset power usage
Local settings
Input/output settings
ON/OFF settings
Battery settings
Description
Available settings
[English] [French] [German]
Language
[Spanish] [Italian] [Portuguese]
[Russian]
Menus, status, notices and alarms,
UPS fault, event log data and settings
are in all supported languages.
LCD settings
Allows LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm
[Enabled] [Disabled on battery]
[Always disabled]
Allows you to enable or disable the
audio alarm if an alarm occurs.
Output voltage*
[100V] [120V] [125V]
On INTL models: [200V] [208V] [220V] [230V]
[240V]
*Important: The output voltage of the UPS must be set to the same nominal voltage as the facility
input voltage for optimum UPS performance.
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70V before UPS transfers
to battery.
This can be used if the load can
withstand low voltage supply.
Sensitivity
[High] [Low]
High: For sensitive equipment, the
UPS will easily transfer to battery
when utility conditions deteriorate.
Low: For less sensitive equipment,
the UPS will not transfer to battery
when utility conditions deteriorate.
Load segments -
[No Delay] [1 s] [2 s]...[65354 s]
Auto start delay
The connected equipment is powered
after the specified delay.
and
buttons to scroll through the menu
button to cancel or return to the previous
Display information or Menu function
Load W VA/Load A pf/Output V Hz/Input V Hz/
Battery V min/Efficiency/Power usage
Group 1: ON/OFF
Group 2: ON/OFF
These commands overrule user settings for load segments.
Starts a manual battery test
Clears active faults (UPS restart required)
Clears power usage measurements
Sets general parameters
Sets Input and output parameters
Sets on and off conditions
Sets battery configuration
Displays event log or alarms
UPS Type/Part Number/Serial Number/Firmware release/Com
card address
Default settings
English
User selectable when UPS is
powered the first time.
Enabled
User selectable when UPS is
powered the first time.
Normal mode
High
Group 1: 3 s
Group 2: 6 s
792518-001 Edition 2