Display Functions; User Settings - HP 1U User Manual

Table of Contents

Advertisement

2. User Interface

2.3 Display functions

Press the
button to activate the menu options. Use the
the
button to select an option. Press the
Display Function Menu
Main menu
Measurements
Control
Settings
Fault log
Identification

2.4 User settings

The following table displays the options that can be changed by the user.
Local settings
In/Out settings
Continued
Page 9
button to cancel or return to the previous menu.
Submenu
Display information or Menu function
Load W VA/Load A pf/Output V Hz/Input V Hz/
Battery V min/Efficiency/Power usage
Load Segments
Group 1: ON/OFF
Group 2: ON/OFF
These commands overrule user settings for load segments.
Start battery test
Starts a manual battery test
Reset fault state
Clears active faults (UPS restart required)
Restore factory settings
Returns all settings to original values
Reset power usage
Clears power usage measurements
Local settings
Sets general parameters
Input/output settings
Sets Input and output parameters
ON/OFF settings
Sets on and off conditions
Battery settings
Sets battery configuration
Displays event log or alarms
UPS Type/Part Number/Serial Number/Firmware release/Com card
address
Available settings
Description
Language
[English] [French] [German] [Spanish]
[Italian] [Portuguese] [Russian]
Menus, status, notices and alarms, UPS
fault, event log data and settings are in all
supported languages.
LCD settings
Allows LCD screen brightness and contrast
to be adapted to room light conditions.
Audible alarm
[Enabled] [Disabled on battery] [Always
disabled]
Allows you to enable or disable the audio
alarm if an alarm occurs.
Output voltage
[100V] [120V] [125V]
On INTL models: [200V] [208V] [220V]
[230V] [240V]
Input thresholds
[Normal mode] [Extended mode]
Extended mode reduces lower input volt-
age to 70V before UPS transfers to battery.
This can be used if the load can
withstand low voltage supply.
Sensitivity
[High] [Low]
High: For sensitive equipment, the
UPS will easily transfer to battery when
utility conditions deteriorate.
Low: For less sensitive equipment, the UPS
will not transfer to battery when utility
conditions deteriorate.
Load segments - Auto
[No Delay] [1 s] [2 s]...[65354 s]
start delay
The connected equipment is powered
after the specified delay.
and
buttons to scroll through the menu structure. Press
Default settings
English
User selectable when UPS is pow-
ered the first time.
Enabled
User selectable when UPS is
powered the first time.
Normal mode
High
Group 1: 3 s
Group 2: 6 s
792518-001 Edition 1