Single Port Fs Unit (Long Piping Model); Parts Replacement Method - Toshiba MMY-MAP0806FT8P-TR Service Manual

Table of Contents

Advertisement

15

SINGLE PORT FS UNIT (LONG PIPING MODEL)

PART REPLACEMENT METHOD
WARNING
・Wear a pair of gloves.
Otherwise, you will risk an injury involving a replacement part or some other object.
・Stop the power supply of the air conditioner and turn off switch of the power supply breaker.
1. Electric parts cover
1 Detachment
1) Loosen fixing scews. (φ4 x 8, 2 pcs)
2) Pull the cover downward and then remove the cover.
2 Attachment
1) Hook the electric parts cover on the screw. (2 places)
2) Slide up the electric parts cover and fit it in.
3) Tighten the screws. (φ4 x 8, 2 pcs)
Screws
2. P.C.board
1 Detachment
1) Perform work of procedure 1-1 Detachment. (Electric parts cover)
2) Remove connectors which are connected
from the control P.C.board to the other parts.
CN67 :
Power supply wires
CN710 :
SVS, SVSS, SVDD, SVD
CN720 :
PMV
CN101 :
TCS sensor
CN400 :
Communication wire
CN22 :
Earth wire
3) Unlock the locks of the card edge spacer (4 positions)
and then remove the control P.C.board.
2 Attachment
1) Fix the control P.C.board to the card edge spacers. (4 positions)
2) Connect the connectors disconnected in item 1-2) as before.
For connectors, check there is no missing or contact failure.
3) Attach the Electric parts cover. (Refer to 1. of 2 Attachment)
Cover
Hook to the screw
Black
White
White
White
Terminal block 2P
Faston tab
− 308 −