Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
#0:Element short circuit
#1:Position detection circuit
trouble
#3:Motor lock trouble
P22
P22
#4:Motor current trouble
#C:TH sensor
temperature trouble
#D:TH sensor short
circuit/release trouble
#E:Vdc voltage trouble
01: Compressor 1 side
02: Compressor 2 side
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
P31
Location
of
Description
System status
detection
Outdoor fan
IPDU
All stop
IPDU trouble
*Put in Fan
IPDU No. in [#]
mark
All stop
All stop
All stop
All stop
All stop
All stop
IPDU
IPM short-
All stop
circuit protection
trouble
IPDU
Compressor
All stop
position
detection circuit
trouble
Indoor
Other indoor
Stop of
unit
trouble
corresponding
(group follower
unit
unit trouble)
− 184 −
Check code detection
Check items (locations)
condition(s)
(Sub code: #0)
• Check fan motor.
Fan IPDU over current
• Check for trouble in fan IPDU
protection circuit
P.C. board
Flow of current equal to or
greater than the specified
value is detected during
startup of the fan.
(Sub code: #1)
• Check fan motor.
Fan IPDU position
• Check connection of fan motor
detection circuit Position
connector.
detection is not going on
• Check for trouble in fan IPDU
P.C. board.
normally.
(Sub code: #3)
• Check fan motor.
Gusty wind, an obstruction,
• Check for trouble in fan
or another external factor
IPDU P.C. board
Speed estimation is not
going on normally.
(Sub code: #4)
• Check fan motor.
Fan IPDU over current
• Check connection of fan
protection circuit
motor connector.
Flow of current equal to or
Check for trouble in fan IPDU
greater than the specified
P.C. board.
value is detected during
operation of the fan.
(Sub code: #C)
• Check fan motor.
Higher temperature than
• Check for trouble in fan
the specified value is
IPDU P.C. board
detected during operation
of the fan.
(Sub code: #D)
Check for trouble in fan IPDU
The resistance value of
P.C. board.
the sensor is infinite or
zero (open or short circuit).
Check power voltage of
(Sub code: #E)
the main power supply.
Fan IPDU DC voltage
Check for trouble in fan IPDU
protection circuit
P.C. board.
The DC voltage higher or
Check connection of fan
lower than the specified
IPDU P.C. board.
value is detected.
Overcurrent is momentarily
Check connector
connection and wiring on
detected during startup of
A3-IPDU P.C. board.
compressor.
Check for trouble in
compressor (layer short-
circuit).
• Check for trouble in
outdoor P.C. board
(A3-IPDU).
Position detection is not
• Check wiring and
going on normally.
connector connection.
• Check for compressor
layer short-circuit.
• Check for trouble in
A3-IPDU P.C. board.
There is trouble in other
• Check indoor P.C. board.
indoor unit in group,
resulting in detection of
E07/L07/L03/L08.