Toshiba MMY-MAP0806FT8P-TR Service Manual page 173

Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
Duplicated indoor address
E08
E08
E09
E10
01:
Indoor-outdoor
communication
02:
Outdoor-outdoor
E12
E12
communication
E15
E15
00:
Overloading
01-:
No. of units connected
E16
E16
E17
Location
of
Description
System status
detection
Indoor
Duplicated
All stop
unit
indoor address
I/F
Remote
Duplicated
Stop of
controller
master remote
corresponding
controller
unit
Indoor
Indoor inter-
Stop of
unit
MCU
corresponding
communication
unit
trouble
I/F
Automatic
All stop
address starting
trouble
I/F
Indoor unit not
All stop
found during
automatic
address setting
I/F
Too many
All stop
indoor units
connected
Indoor units(s)
Stop of
Indoor
-FS unit(s)
corresponding
unit
communication
unit(s)
trouble
− 172 −
Check code detection
Check items (locations)
condition(s)
More than one indoor unit
• Check indoor addresses.
are assigned same address.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
In two remote controller
• Check remote controller
configuration (including
settings.
wireless), both controllers are
• Check remote controller
set up as master. (Header
P.C. boards.
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
Communication cannot be
• Check for trouble in indoor
established/maintained upon
P.C. board
turning on of power or during
communication.
• Indoor automatic address
• Perform automatic address
setting is started while
setting again after
automatic address setting
disconnecting
for equipment in other
communication cable to
refrigerant line is in
that refrigerant line.
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
Indoor unit cannot be
• Check connection of
indoor-outdoor
detected after indoor
communication line.
automatic address setting is
• Check for trouble in indoor
started.
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for trouble in indoor
P.C. board.
• Combined capacity of
• Check capacities of indoor
indoor units exceeds 135%
units connected.
of combined capacity of
• Check combined HP
outdoor units.
capacities of indoor units.
• Check HP capacity
Note:
settings of outdoor units.
If this code comes up
• Check No. of indoor units
after backup setting for
connected.
outdoor unit failure is
• Check for trouble in
performed, perform "No
outdoor
overloading detected"
P.C. board (I/F).
setting.
<"No overloading detected"
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
• More than 64 indoor units
are connected.
There is no
・Check order in which power
was turned on.
communication from
FS unit(s)
・Check indoor unit(s)-FS
unit(s) cable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents