Fan-Ipdu P.c. Board (Mcc-1659) Replacement Procedure - Toshiba MMY-MAP0806FT8P-TR Service Manual

Table of Contents

Advertisement

13-1-7.Fan-IPDU P.C. Board (MCC-1659) Replacement Procedure

This board is commonly installed in different models before shipment. Set the DIP switch (SW800) setting of the
service board to the switch setting before replacement.
Replacement steps:
(1) Turn off the power supply of the outdoor unit and allow at least 3 minutes for the capacitor to discharge.
(2) Remove all the connectors and the Faston and screw terminals(①) connected to the FAN IPDU.
(Remove the connectors and Faston terminals by pulling the connector body. Do not pull the wire).
(3) Remove all the two screws(②) which secures the FAN IPDU to the Heat sink.
(These screws are to be re-used after procedure.)
(4) Remove the Fan IPDU from the four PCB Mounts (③).
Ex. MMY-MAP1006FT8P
FAN IPDU
(MCC-1659)
(5) Confirm that no dirt or damage is on the sub heat sink. As it can reduce the heat transfer efficiency, and cause a
breakdown.
FAN-IPDU
(43T6V627)
SW800
②Screw
①Faston terminal
YELLOW lead wire
Remove the PCB
Sub Heat Sink
Heat Sink
− 294 −
①Screw terminal
BLUE lead wire
①Faston terminal
RED lead wire
①Faston terminal
WHITE lead wire
①Faston terminal
BLACK lead wire
Push this part to
the direction of the
arrow. And remove
the PCB.
PCB Mounts ③
IC302

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents