Toshiba MMY-MAP0806FT8P-TR Service Manual page 224

Table of Contents

Advertisement

(4)Display of Outdoor Cycle Data (Displayed at Header Unit)
* This method is used when displaying follower unit information on the 7-segment display of the header unit.
S
W
0
1
S
W
0
2
S
W
0
3
Check code data
1
Type of compressor installed
2
Outdoor unit HP capacity
3
Compressor operation command
4
1~3
3
Fan operation mode
5
Release signal
6
Oil level judgment
7
Compressor 1 operating current
8
Compressor 2 operating current
9
Note: Follower unit is selected by setting SW03.
SW03
7-segment display section A
1
2
U2
U3
D
s i
p
a l
y
d
e
a t
l i
A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B Check code is displayed (latest one only).
If there is no check code: [– – –].
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B 8HP: [... 8], 10HP: [... 10], 12HP: [... 12],
14HP: [14], 16HP: [16], 18HP: [18], 20HP: [20]
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B Indicates which compressor is ON.
Any unconnected compressors is represented by "–".
W
h
e
n
c
o
m
p
e r
s s
r o
N
. o
1
W
h
e
n
c
o
m
p
e r
s s
r o
N
. o
2
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B At rest: [F ... 0], In mode 63: [F 6 3]
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B Normal: [r ... ...], Upon receiving release signal: [r ... 1]
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B Normal: [... ... ...], Low level: [... ... L]
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B [ . ],
. is value of operating current in decimal format.
A [U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U3)
B [ . ],
. is value of operating current in decimal format.
− 223 −
s i
O
N
s i
O
N
B
1 0
0 1

Hide quick links: