AFFINITY & AFFINITY ADVANCED SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Electrical Data cont.
Dual Capacity Unit with Variable Speed ECM Motor
Rated
Voltage
Model
Voltage
Min/Max
026
208-230/60/1
187/253
038
208-230/60/1
187/253
049
208-230/60/1
187/253
064
208-230/60/1
187/253
072
208-230/60/1
187/253
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Dual Capacity Unit with 5-Speed ECM Motor
Rated
Voltage
Model
Voltage
Min/Max
026
208-230/60/1
187/253
038
208-230/60/1
187/253
049
208-230/60/1
187/253
064
208-230/60/1
187/253
072
208-230/60/1
187/253
** With optional IntelliStart
®
Rated voltage of 208/230/60/1
All fuses Class RK-5
HACR circuit breaker in USA only
Compressor
MCC
RLA
LRA
18.2
11.6
58.3
23.8
15.2
83.0
33.0
21.1
104.0
42.3
27.1
152.9
46.3
29.6
179.2
Compressor
MCC
RLA
LRA
18.2
11.6
58.3
23.8
15.2
83.0
33.0
21.1
104.0
42.3
27.1
152.9
46.3
29.6
179.2
HWG
Ext
Pump
Loop
LRA**
FLA
FLA
21.0
0.4
5.4
30.0
0.4
5.4
37.0
0.4
5.4
54.0
0.4
5.4
63.0
0.4
5.4
HWG
Ext
Pump
Loop
LRA**
FLA
FLA
21.0
0.4
5.4
30.0
0.4
5.4
37.0
0.4
5.4
54.0
0.4
5.4
63.0
0.4
5.4
22
Blower
Total
Min
Motor
Unit
Circ
FLA
FLA
Amp
4.0
21.4
24.4
4.0
25.0
28.8
4.0
30.9
36.2
7.0
39.9
46.6
7.0
42.4
49.8
Blower
Total
Min
Motor
Unit
Circ
FLA
FLA
Amp
4.1
21.5
24.5
4.1
25.1
28.9
7.6
34.5
39.8
7.6
40.5
47.2
7.6
43.0
50.4
Max
Fuse/
HACR
35
40
50
70
70
07/15/22
Max
Fuse/
HACR
35
40
60
70
80
9/1/15