VERSION Command:
Description: - Transmit model number, firmware version, and output
mode.
Syntax:
VERSION CR [LF]
None. There are no parameters for this command.
Parts:
Remarks:
Units with a display attached will transmit "OS102E" as the model
number. The example below shows a unit without a display attached.
The firmware version is a six-digit number following the "FW:" shown
below. Depending on the model suffix (the first characters immediately
following OS101-/OS102-), the "OUTPUT:" will be transmitted as
follows:
Model Suffix OUTPUT:
K
TC-K
MV-C
mV/Deg C
MV-F
mV/Deg F
V1
0-5V
V2
0-10V
MA
4-20mA
Example:
The following is shown on the PC (terminal) screen after typing
"VERSION" and "Enter":
>VERSION
OMEGA ENGINEERING
OS101E FW: 061013
OUTPUT: mV/Deg F
>
AMODE Command:
Description: - Set/Transmit alarm activation mode rising/falling.
Syntax:
AMODE[SP MODE] CR [LF]
Parts:
MODE (OPTIONAL)
Specifies whether the alarm will activate at the setpoint with rising
temperature, or falling temperature. The valid range for this parameter is
0 to 1. A value of 1 will cause the alarm to activate on rising temperature,
and 0 will cause activation on falling temperature. If this parameter is not
specified, the mode currently set will be transmitted.
Remarks:
The default mode for alarm activation is "rising". The only way to change
the activation mode is through the RS232 "AMODE" command.
OS100E Series - Operation
3
3-7