9.5 Repair
9.5.9

Replacing the current transformer

The current transformer may only be replaced by technicians trained by Siemens.
9.5.10

Door interlock system

Contact Technical Support (Page 171) if the door interlock system becomes defective.
9.5.11

Replacing the precharging transformer

Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
● Follow "the five safety rules (Page 15)".
● Before replacing the precharging transformer, open the safety disconnector for the 400 V
● Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the 400 V connecting cables
2. Remove the high-voltage cables
3. Release the PE conductor.
4. Remove the fixing screws on the base brackets
5. Remove the transformer.