Operation
8.5 Functions
Signal
Phase current actual value
Control factor
Field-generating current setpoint
Field-generating actual current
Torque-generating current setpoint
Torque-generating actual current
Flux setpoint
Actual flux
DC-link voltage
Phase voltage
For further diagnostic purposes
Speed controller output
I component of speed controller
Scaling
Variable
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference control factor
Reference flux
Reference temperature
Example: Changing analog output 0 from current to voltage output –/+ 10 V
Figure 8-5
108
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = p2003
100% = r2004
100 % = r2000 / 60
100% = Maximum output voltage
without overload
100% = Rated motor flux
100% = 100° C
Example: Setting analog output 0
Parameter
Unit
r0069
A
r0074
%
r0075
A
r0076
A
r0077
A
r0078
A
r0083
%
r0084
%
r0088
V
r0089
V
r1480
Nm
r1482
Nm
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x pi) / 30
SINAMICS SM150 6SL3845-2NN41-8AD2
Operating Instructions Rev.201910281310 EXAMPLE
Scaling
(100% = ...)
p2002
Reference control
factor
p2002
p2002
p2002
p2002
Reference flux
Reference flux
p2001
p2001
p2003
p2003