4.1 Prestart Installation Check

DANGER
WARNING
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless,
colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when
working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where
exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other
openings.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is a
poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
Light-headedness, dizziness
Physical fatigue, weakness in joints and muscles
Sleepiness, mental fatigue, inability to concentrate or speak clearly, blurred vision
Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active.
Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the
condition of affected persons does not improve within minutes of breathing fresh air.
Review the previous installation sections. Inspect all wiring and connections to verify that the generator set is ready for operation.
Check all items in the following Prestart Checklist.
Prestart Checklist
Air Cleaner. Check that a clean air cleaner element is installed to prevent unfiltered air from entering the engine. See the
generator set operation manual for instructions.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult the battery manufacturer's instructions regarding battery care and
maintenance.
Enclosure. Check that all enclosure panels and internal baffling are in place.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
1.
Inspect the exhaust system components for cracks, leaks, and corrosion. Check for tight exhaust system connections.
2.
Check for corroded or broken metal parts and replace them as needed.
3.
Check that the exhaust outlet is unobstructed.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave
rags, tools, or debris on or near the generator set.
TP-7091
4/23
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures are in place.
Carbon monoxide.
Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Section 4. Prestart
45