2.6
Optional Integrated Two-Button Assembly (Standard Display)
The standard display does not support all the transmitter configuration parameters and has limited
features.
The optional Integrated two-button assembly for the standard display provides the following features
and capabilities:
•
Menu and enter key functionality.
•
With the menu-driven display:
o Comprehensive on-screen menu for navigation.
o Transmitter configuration: enter LRV, enter URV and loop test.
o Transmitter calibration.
o Display configuration (contrast only).
o Set zero and span parameters.
Revision 13
If you are using the optional external two-button assembly with the
standard display then you can perform all the above operations without
removing external glass cap using the external buttons.
Lower range value (LRV): A display parameter (standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 4mA.
Upper range value (URV): A display parameter (standard display), which
allows users to enter the measuring value for which the analog output will
be scaled to 20mA.
ST 700 SmartLine Pressure Transmitters User's Manual
Page 7