Honeywell SmartLine ST 700 User Manual page 178

Pressure transmitters
Hide thumbs Also See for SmartLine ST 700:
Table of Contents

Advertisement

DAC Zero Trim
[5ZEROTR]
Note: Loop must
DAC Zero Trim
be removed
from Automatic
Control
DAC Span Trim
[6SPANTR]
Note: Loop must
DAC Span Trim
be removed
from Automatic
Control
Loop Test
[7 LPTEST]
Loop Test
Note: Loop must
12.000
be removed
from Automatic
Control
Set LRV
Set LRV
[ 8SETLRV]
Set URV
Set URV
[ 9SETURV]
Contrast
Contrast level
[10CNTRST]
Page 162
This selection allows the loop
zero output 4mA value to be
trimmed.
Note: You must connect a
current meter to the transmitter
to monitor the loop output.
This selection allows the loop
span output 20mA value to be
trimmed.
Note: You must connect a
current meter to the transmitter
to monitor the loop output.
This selection allows the user
to force the DAC output to any
value between 3.8 and 20.8
mA.
Note: This selection will put the
DAC into Fixed Output Mode,
as indicated by the flashing
output value. Navigation away
from this menu item will return
the loop to Normal (Automatic)
Mode.
Executing this selection
performing for Zero operation.
Note: The PV value shown in
bottom line will be available in
Pressure Units (Simple Display
pressure unit)
Executing this selection for
Span operation
Note: The PV value shown in
bottom line will be available in
Pressure Units (Simple Display
pressure unit)
Adjust the LCD contrast level.
Range from » (1) to
»»»»»»»»» (7)
Default: »»»»»»» (7)
ST 700 SmartLine Pressure Transmitters User's Manual
Press  to
enter menu
selection.
 Menu to
select
number.
 to enter
and shift to
the next digit
to the right.
Press  to
enter menu
selection
 to select
number.
 to enter
and shift to
the next digit
to the right
Press  to
enter menu
selection.
Press  to
initiate
action.
Press  to
enter Menu
selection.
Menu to
select level.
 to Enter
Revision 13