< For remote controller >
1.
Remove cover of remote controller by sliding down and take it out.
If batteries are exist, please take them out. The combination of
2.
using wire controller and batteries may cause of batteries
explosion.
3.
Make hole for insert control wire by use screwdriver break the
polyester sheet as shown on figure 4.
4.
Insert control wire from rear side of remote controller as shown on
figure 5.
Fix control wire which arrange as shown on figure 6 and 7 to
5.
terminal by provided screws (tighten firmly but not over 0.25 N·m
(0.03 kgf·m)).
6.
Set control wire through gutter way at rear side of remote controller
as shown on f gure 8.
7.
Fix provided screw (Ø3.1×16L) on the wall to hang remote
controller as shown on figure 9.
8.
Mark and arrange hole for fix below screw (Ø3.1×25L) as
shown on figure 9.
9.
Assembly battery cover which provided with accessory bag then
use provide screw (Ø3.1×25L) to fix battery cover together with
wall as shown on figure ! (tighten firmly but not over 0.15
N·m (0.02 kgf·m)).
10. Reassembly cover of remote controller.
4
5
Plastic for cover hole
7
Type A
Terminal
Control wire
* Terminals for wiring can be either on right (type A) or left (type B), depending
on the controller packed in carton.
Control wire
Hole for hang
remote controller
Remote controller
Remote controller
8
Type A
Battery cover
Screw
Tighten fi rmly but not over
0.15 N·m (0.02 kgf·m)
6
30 mm
10 mm
* Wire size 28-22AWG
Control wire
or 0.08-0.32 mm
2
Outer diameter not over 4.7 mm,
control wire length 30 m. or less.
Type B
Control wire
Screw (Ø3.1×16L)
for hang remote
controller
Wall
Screw (Ø3.1×25L)
for fi x battery cover
9
Type B
!
*Remark : 1. Recommend to use double insulation lead wire for
connect remote control and air conditioner.
2.
For wire operation, 1 remote control can control
only 1 indoor unit
3.
In wire operation, remote controller will return to
initial condition (PRESET, TIMER and CLOCK will
return to initial condition) when user shutdown
power supply of air conditioner.
10-3-4. Piping and drain hose installation
<Piping and Drain Hose Forming>
* Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes.
(Use polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Left
Bottom right
Right
1. Die-cutting front panel slit
Cut out the slit on the left or right side of the front panel
for the left or right connection and the slit on the bottom
left or right side of the front panel for the bottom left or
right connection with a pair of nippers.
2. Changing drain hose
For leftward connection, bottom-leftward connection
and rear-leftward connection's piping, it is necessary to
change the drain hose and drain cap.
- 57 -
Fig. 10-3-6