Display Functions; User Settings - Eaton 9SX 6000VA Installation And User Manual

Table of Contents

Advertisement

2.6

Display functions

Press the Enter (
through the menu structure. Press the Enter (
or return to the previous menu.
Main menu
Measurements
Control
Settings
Event log
Fault log
Identification
Register product
2.7

User settings

The following table displays the options that can be changed by the user.
Local settings
In/Out settings
5-6kVA EU_EN
) button to activate the menu options. Use the two middle buttons (
Submenu
Display information or Menu function
[Load] W VA A pf / [Input/Bypass] V Hz /
[Output/Efficiency] V Hz % / [Battery] % min V n° /
[DCbus] V / [Average power usage] Wh /
[Cumulat. power usage] Wh since date
Go to Bypass
Transfers the UPS on Bypass mode
Load segments On/Off
Commands the load segments
Start battery test
Starts a manual battery test
Reset fault state
Clears active fault
Restore factory set
Returns all settings to original values
Reset average power
Clears average power usage measurement
Reset cumul. power
Clears cumulated power usage measurement
Dry contacts test
Tests dry contact relay outputs
Local settings
Sets product general parameters
In/Out settings
Sets Output parameters
On/Off settings
Sets On/Off conditions
Battery settings
Sets battery configuration
Event filter
Selects faults, alarms and/or events to display
Event list
Displays the events stored
Reset event list
Clears events
Fault list
Displays the faults stored
Reset fault list
Clears faults
[Product type/model] / [Part/Serial number] / [UPS/NMC
firmware] / [Com card IPv4], [Com card IPv6], [Com card MAC] /
[Detected accessories]
Links to Eaton registration website
Submenu
Available settings
Language
[English] [Français] [Deutsch] [Español]
[Русский] [Português] [Italiano]
Menus, status, notices and alarms,
UPS fault, Event Log data and
settings are in all supported
languages.
Date/ time
Format:
[International] [US]
LCD
Modify LCD screen brightness and
contrast to be adapted to room light
conditions.
Audible alarm
[Enabled] [Disabled on battery] [Always
disabled]
Enable or disable the buzzer
if an alarm occurs.
Output voltage
[200V] [208V] [220V] [230V] [240V]
Can be changed only in Standby mode
Output frequency
Frequency converter:
[Enabled] [Disabled]
Frequency settable in frequency
converter mode
Load segments
[Auto start delay]
[Auto shutdown delay]
Output mode
[Industrial] [Network]
Set UPS behavior regarding transfer
on Bypass
Input volt hysteresis Sets input voltage hysteresis
from 1 to 10V
High Efficiency
[Enabled] [Disabled]
mode
Power the output from Bypass
for high efficiency
Bypass transfer
[Transfer if BP AC NOK]
[Enabled] [Disabled]
Allow transfer on Bypass out
of tolerance
) button to select an option. Press the
2. Presentation
and
) to scroll
button to cancel
Default settings
[English]
User selectable when UPS is
powered for the first time.
[International]
[Enabled]
[230V]
Disabled
Group1: [3s] Group2: [6s]
Group1: [Disabled]
Group2: [Disabled]
[Industrial]
[10V]
[Disabled]
[Enabled]
Page 13