Table 6. Electrical output
All models
Voltage regulation
Efficiency
Frequency regulation
Nominal output
Frequency
Output overload
Output overload
(Bypass mode)
Voltage waveform
Harmonic distortion
Transfer time
Power factor
Load crest ratio
Table 7. Electrical output connections
Model
9SX5KiRT
9PX5Ki
9SX6KiRT
9PX6Ki
Table 8. Environmental and safety
EMC certifications
EMC (Emissions)*
EMC (Immunity)
* for output cable < 10m.
5-6kVA EU_EN
Normal mode
±1%
> 98% (High Efficiency mode)
> 93%
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5%
of auto-selected nominal frequency)
200/208/220/230/240V (voltage configurable)
5000/6000VA 4500/5400W
50 or 60Hz, autosensing or configurable as a frequency converter
100-102% : no alarm
102-110% : load transfers to Bypass mode after 2 minutes
110-125% : load transfers to Bypass mode after 1 minute
125-150% : load transfers to Bypass mode after 10s
> 150%
: load transfers to Bypass mode after 500ms
100-125% : no alarm
125-150% : UPS shuts down after 1 minute
> 150%
: UPS shuts down after 1s
Sinewave
< 2% THDV on linear load
< 5% THDV on non-linear load
Online mode: 0 ms (no break)
High Efficiency mode: 10ms maximum (due to loss of utility)
0.9
3 to 1
Output connection
Hardwired
(2) IEC16A
(4) IEC10A group 1
(4) IEC10A group 2
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
UL 1778 4
th
CSA 22.2
CISPR22 Class A
AS/NZS 22 Class A
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
FCC part 15 Class A
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
9. Specifications
Battery mode
±1%
> 91%
±0.5% of auto-selected nominal
frequency
Output cable
(2) IEC 10A
Page 41