Configuration

11 Configuration

11.1 Facility setting

11.1.1 To set the facility mode

Installer reference guide
52
Use this function for cooling at low outdoor temperature. This function is designed
for facilities such as equipment of computer rooms. NEVER use in a residence or
office where people occupy the space.
When cutting jumper J6 on the PCB, the operation range will expand to –15°C. The
facility mode will stop if the outdoor temperature drops below –20°C and resume
when the temperature rises again.
INFORMATION
The indoor unit may produce Intermittent noise due to the outdoor unit fan
turning ON and/or OFF.
Do NOT place humidifiers or other items which might raise humidity in rooms
when you use the facility mode.
Cutting jumper J6 sets the indoor unit fan to the highest speed.
Do NOT use this setting in residences or offices with people.