Specifications Of Standard Wiring Components; To Connect The Electrical Wiring To The Outdoor Unit - Daikin RXTM30R2V1B Installer's Reference Manual

Hide thumbs Also See for RXTM30R2V1B:
Table of Contents

Advertisement

9.1.3 Specifications of standard wiring components

9.2 To connect the electrical wiring to the outdoor unit

RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 split series
4P518023-11H – 2021.03
Wire type
Stranded conductor wire
with round crimp-style
terminal
Tightening torques
Item
M4 (X1M)
M4 (earth)
The earth wire between the wire retainer and the terminal must be longer than
the other wires.
Component
Power supply cable
Interconnection cable (indoor↔outdoor)
Recommended circuit breaker
Residual current device
1 Remove the service cover. See
2 Strip insulation (20 mm) from the wires.
c b
B
a
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
1-3
Voltage
Phase
Frequency
Wire sizes
"6.2.2 To open the outdoor
9
Electrical installation
|
Installation method
a
b
c
B
Tightening torque (N•m)
1.5~1.6
1.4~1.5
220~240 V
1~
50 Hz
3-core cable
2(a)(b)
2.5 mm
/ 4.0 mm
(a)
H05RN-F (60245 IEC 57)
(b)
H07RN-F (60245 IEC 66)
4-core cable
2
1.5 mm
~2.5 mm
applicable for 220~240 V
H05RN-F (60245 IEC 57)
16 A
MUST comply with applicable
legislation
4
unit" [
Installer reference guide
2(b)
2
and
 28].
49