Emc And Low Voltage Directive; Requirements For Conformance To Emc Directive; Standards Applicable To The Emc Directive - Mitsubishi MELSEC- Q Q12PHCPU User Manual

Process cpu
Hide thumbs Also See for MELSEC- Q Q12PHCPU:
Table of Contents

Advertisement

8 EMC AND LOW VOLTAGE DIRECTIVE

8 EMC AND LOW VOLTAGE DIRECTIVE
For the products sold in European countries, the conformance to the EMC Directive,
which is one of the European Directive, has been a legal obligation since 1996. Also,
conformance to the Low Voltage Directive, another European Directive, has been a
legal obligation since 1997.
Manufacturers who recognize their products must conform to the EMC and Low
Voltage Directive required to declare that their products conform to these Directives
and put a "CE mark" on their products.

8.1 Requirements for Conformance to EMC Directive

The EMC Directive specifies that products placed on the market must "be so
constructed that they do not cause excessive electromagnetic interference (emissions)
and are not unduly affected by electromagnetic interference (immunity)".
The applicable products are requested to meet these requirements. The sections 8.1.1
through 8.1.5 summarize the precautions on conformance to the EMC Directive of the
machinery constructed using the MELSEC-Q series PLCs.
The details of these precautions has been prepared based on the control requirements
and the applicable standards control. However, we will not assure that the overall
machinery manufactured according to these details conforms to the above-mentioned
directives. The method of conformance to the EMC Directive and the judgment on
whether or not the machinery conforms to the EMC Directive must be determined
finally by the manufacturer of the machinery.

8.1.1 Standards applicable to the EMC Directive

The standards applicable to the EMC Directive are listed below.
Specification
Test item
EN55011
Radiated noise 2
EN50081-2 :
1995
EN55011
Conducted noise
EN61000-4-2
Electrostatic immunity 2
EN61000-4-4
Fast transient burst noise 2
EN61131-2 :
1996
EN61000-4-3
Radiated field AM
modulation 2
EN61000-4-12
Damped oscillatory wave
immunity
( 1) QP : Quasi-peak value, Mean : Average value
( 2) The PLC is an open type device (device installed to another device) and must be installed in a conductive control panel.
The tests for the corresponding items were performed while the PLC was installed inside a control panel.
8 - 1
Test details
Electromagnetic emissions from the
product are measured.
Electromagnetic emissions from the
product to the power line is
measured.
Immunity test in which static
electricity is applied to the cabinet of
the equipment.
Immunity test in which burst noise is
applied to the power line and signal
lines.
Immunity test in which field is
irradiated to the product.
Immunity test in which a damped
oscillatory wave is superimposed on
the power line.
MELSEC-Q
Standard value
30 M-230 MHz QP
: 30 dB
(30 m in measurement range)
230 M-1000 MHz QP : 37 dB
(30 m in measurement range)
150 k-500 kHz QP
: 79 dB, Mean : 66 dB 1
500 k-30 MHz QP
: 73 dB, Mean : 60 dB
15 k V Aerial discharge
Power line
: 2 kV
Digital I/O (24 V or higher) : 1 kV
(Digital I/O (24 V or less)) > 250 V
(Analog I/O, signal lines) > 250 V
10 V/m, 26-1000 MHz,
80%AM modulation@1 kHz
Power line
: 1 kV
Digital I/O (24 V or higher) : 1 kV
V/m
1
V/m
8
8 - 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec- q q25phcpu

Table of Contents