Battery Replacement Procedure - Mitsubishi MELSEC- Q Q12PHCPU User Manual

Process cpu
Hide thumbs Also See for MELSEC- Q Q12PHCPU:
Table of Contents

Advertisement

10 MAINTENANCE AND INSPECTION

10.3.2 Battery replacement procedure

Replacing battery
Turn off the PLC power supply.
.
Remove the CPU module from the
base unit.
Open the cover of the CPU module.
Remove the old battery from
its holder.
Insert a new battery into the holder in
the correct direction.
Connect the lead to the connector.
Close the cover of the CPU module.
Install the CPU module into the
base unit.
Turn on the PLC power supply.
Monitor
SM51 to verify on/off.
ON
Monitor
SD52 to verify the bit number
that is on.
Bit 0 is on.
The CPU module battery is faulty.
10 - 7
(1) CPU module battery replacement procedure
When the CPU module battery has been exhausted, replace the battery with a
new one according to the procedure shown below. The PLC power must be on
for 10 minutes or longer before dismounting the battery.
Even when the battery is dismounted, the memories are backed up by the
capacitor for a while. However, if the replacement time exceeds the guaranteed
value specified in the table below, the contents stored in the memories may be
erased. To prevent this trouble, replace the battery speedily.
OFF
Bits other than 0 are on.
The memory card battery is faulty.
Refer to Section 10.3.2 (2).
Backup time by capacitor
Backup time by capacitor[min]
Side of the CPU module
Completion
MELSEC-Q
3
Front
10 - 7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec- q q25phcpu

Table of Contents