2 SYSTEM CONFIGURATION FOR SINGLE CPU SYSTEM

2.2 Precaution on System Configuration

2 - 4
This section describes hardware and software packages compatible with Process
CPU.
(1) Hardware
(a) The Process CPU can be used with the MELSEC-Q series I/O and intelligent
function modules.
It cannot be used with the MELSEC-AnS/Q2AS series I/O and special
function modules.
(b) The number of modules to be installed and functions are limited depending on
the type of the modules.
Applicable Module
Q Series MELSECNET/10H
network module
Q series Ethernet interface
module
Q series CC-Link system
master local module
Interrupt module
: A maximum of 4 modules if the network parameters for CC-Link are set and
controlled by the GX Developer. There is no restriction in the number of modules
when the parameters are set by the special-purpose instructions for the CC-Link.
For details on the CC-Link System Master Local Unit that can set parameters with
the special-purpose instructions, refer to the user's manual for the CC-Link Master
Local module.
(c) A graphic operation terminal can be used only for the GOT900 series (Basic
OS matching Q mode and communication driver must be installed).
The GOT800 series, A77GOT, and A64GOT cannot be used.
(2) Software package
You can use GX Developer Version 7.10L or later to create the programs of the
Process CPU.
Do not use GX Developer Version 7.09K or earlier.
Type
• QJ71LP21
• QJ71BR11
• QJ71LP21-25
• QJ71LP21G
• QJ71LP21GE
• QJ71E71
• QJ71E71-B2
• QJ71E71-100
• QJ61BT11
• QI60
MELSEC-Q
Limit of number of modules
to be installed
Up to 4 inter-PLC network
and remote I/O network
modules in total
Up to 4 units
No limit
One unit only
2 - 4