Fujitsu ARXG45KMLA Service Manual page 80

Hide thumbs Also See for ARXG45KMLA:
Table of Contents

Advertisement

Check point 4. Check the solenoid coil and 4-way valve
NOTE: Refer solenoid coil and 4-way valve in
Solenoid coil
Remove P60 from PCB and check the resistance value of coil. Resistance value is 1.97 kΩ.
If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 5. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
2-30. E: 99. 4-way valve error (Outdoor unit)
End
"Service parts information"
- (03-36) -
on page 03-49.
2. Troubleshooting with error code