7-8. High temperature and high pressure release control

The compressor is controlled as follows.
¢ Models: AOYG36KRTA and AOYG45KRTA
• Cooling mode
Indoor unit heat exchanger
temperature rises
AB
BC
Zone C
Zone
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
Zone C
The protection is released and the operation is returned to normal mode.
Zone D
• Heating mode
Indoor unit heat exchanger
temperature rises
AB
BC
CD
Zone D
Zone
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
Zone C
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
7-8. High temperature and high pressure release control
Indoor unit heat exchanger
temperature drops
Zone A
Zone B
Stable zone
CD
Zone D
Indoor unit heat exchanger
temperature drops
Zone A
Zone B
Zone C
Stable zone
DE
Zone E
- (04-29) -
AB:
64°C
BC:
60°C
CD:
58°C
Operation
AB:
63°C
BC:
55°C
CD:
53°C
DE:
50°C
Operation
-7 rps/120 sec.
-15 rps/120 sec.
-2 rps/120 sec.