Fujitsu ARXG45KMLA Service Manual page 105

Hide thumbs Also See for ARXG45KMLA:
Table of Contents

Advertisement

¢ Heat exchanger temperature thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
¢ Outdoor temperature thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
5-2. Outdoor unit
Resistance (kΩ)
95.58
68.90
50.31
37.19
27.81
21.02
16.05
12.38
9.63
7.56
5.98
4.77
3.84
3.11
2.53
2.08
1.71
1.42
1.19
1.00
0.84
0.71
0.61
Resistance (kΩ)
224.33
159.71
115.24
84.21
62.28
46.58
35.21
26.88
20.72
16.12
12.64
10.00
7.97
6.40
5.18
4.21
3.45
2.85
- (03-61) -
Voltage (V)
0.24
0.32
0.43
0.57
0.73
0.92
1.14
1.39
1.65
1.93
2.21
2.49
2.77
3.02
3.26
3.48
3.68
3.85
4.00
4.13
4.25
4.35
4.43
Voltage (V)
0.73
0.97
1.25
1.56
1.90
2.26
2.61
2.94
3.25
3.52
3.76
3.97
4.14
4.28
4.41
4.51
4.59
4.65
5. Thermistor resistance values

Advertisement

Table of Contents
loading

This manual is also suitable for:

Arxg36kmlaAoyg36krtaAoyg45krta

Table of Contents