Fujitsu AUXG07-22KVLA Design & Technical Manual

Fujitsu AUXG07-22KVLA Design & Technical Manual

Air conditioner 4-unit multi-split type, 5-unit multi-split type
Table of Contents

Advertisement

Quick Links

AIR CONDITIONER
4-unit multi-split type,
5-unit multi-split type
DESIGN & TECHNICAL MANUAL
INDOOR
ASYG07-14KGTB
ASYG07-14KETA-B
ASYG07-14KETE-B
AUXG07-22KVLA
ARXG07-14KSLAP
ASYG07-14KGTE
ASYG18-24KMTB
ASYG18-24KMTE
ABYG18-22KRTA
AGYG09-14KVCA
ARXG07-14KLLAP
ARXG18KSLAP
ARXG18KLLAP
ASYG07-14KMTB
ASYG07-14KMCC
ASYG07-14KMCE
OUTDOOR
ARXG22KMLB
ASYG07-14KETA
ASYG07-14KETE
AOYG30KBTA4
AOYG36KBTA5
DR_MU025EF_06
2022.03.11

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AUXG07-22KVLA

  • Page 1 AIR CONDITIONER 4-unit multi-split type, 5-unit multi-split type DESIGN & TECHNICAL MANUAL INDOOR AUXG07-22KVLA ARXG07-14KSLAP ARXG07-14KLLAP ARXG22KMLB ARXG18KSLAP ARXG18KLLAP ASYG07-14KGTB ASYG07-14KGTE ASYG18-24KMTB ASYG07-14KMTB ASYG07-14KETA ASYG18-24KMTE ASYG07-14KMCC ASYG07-14KETE ASYG07-14KMCE OUTDOOR ASYG07-14KETA-B ABYG18-22KRTA AGYG09-14KVCA AOYG30KBTA4 ASYG07-14KETE-B AOYG36KBTA5 DR_MU025EF_06 2022.03.11...
  • Page 2 • Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
  • Page 3: Table Of Contents

    CONTENTS Part 1. INDOOR UNIT................1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................4 2. Specifications....................11 2-1. Compact cassette type ....................11 2-2. Mini duct type.........................13 2-3. Slim duct type ........................15 2-4. Medium static pressure duct type ..................17 2-5. Wall mounted type ......................18 2-6.
  • Page 4 CONTENTS (continued) 7-4. Medium static pressure duct type ................132 7-5. Wall mounted type .......................133 7-6. Ceiling type ........................139 7-7. Floor type........................140 8. Noise level curve..................141 8-1. Compact cassette type ....................141 8-2. Mini duct type.......................144 8-3. Slim duct type ......................147 8-4. Medium static pressure duct type ................150 8-5.
  • Page 5 CONTENTS (continued) 14-4.Indoor unit (setting by simple remote controller) ............300 14-5.Function details......................307 14-6.Wired remote controller (UTY-RNNYM) ..............316 14-7.Wired remote controller (UTY-RVNYM) ..............318 14-8.Wired remote controller (UTY-RLRY) .................319 14-9.Wired remote controller (UTY-RNRYZ*) ..............319 14-10.Simple remote controller (UTY-RSNYM)..............320 15. Accessories ....................321 15-1.Compact cassette type ....................321 15-2.Mini duct type......................322 15-3.Slim duct type ......................324 15-4.Medium static pressure duct type ................325...
  • Page 6 CONTENTS (continued) Part 2. OUTDOOR UNIT (4 UNITS TYPE) ........349 1. Specifications....................350 2. Dimensions....................352 2-1. Model: AOYG30KBTA4 ....................352 3. Installation space ..................353 3-1. Model: AOYG30KBTA4 ....................353 4. Refrigerant circuit ..................356 4-1. Model: AOYG30KBTA4 ....................356 5. Wiring diagram ..................357 5-1. Model: AOYG30KBTA4 ....................357 6.
  • Page 7 CONTENTS (continued) Part 3. OUTDOOR UNIT (5 UNITS TYPE) ........431 1. Specifications....................432 2. Dimensions....................434 2-1. Model: AOYG36KBTA5 ....................434 3. Installation space ..................435 3-1. Model: AOYG36KBTA5 ....................435 4. Refrigerant circuit ..................438 4-1. Model: AOYG36KBTA5 ....................438 5. Wiring diagram ..................439 5-1. Model: AOYG36KBTA5 ....................439 6.
  • Page 8 CONTENTS (continued) 17-2.Points to remember when installing ................515...
  • Page 9: Part 1. Indoor Unit

    Part 1. INDOOR UNIT COMPACT CASSETTE MINI DUCT TYPE: TYPE: AUXG07-22KVLA ARXG07-14KSLAP ARXG18KSLAP SLIM DUCT TYPE: MEDIUM STATIC PRES- SURE DUCT TYPE: ARXG07-14KLLAP ARXG18KLLAP ARXG22KMLB WALL MOUNTED TYPE: ASYG07-14KGTB ASYG07-14KGTE ASYG18-24KMTB ASYG18-24KMTE ASYG07-14KMTB ASYG07-14KETA ASYG07-14KETA-B ASYG07-14KMCC ASYG07-14KETE ASYG07-14KETE-B ASYG07-14KMCE CEILING TYPE:...
  • Page 10: Model Lineup

    1. Model lineup Indoor unit AUXG07KVLA ARXG07KSLAP ARXG07KLLAP ARXG22KMLB AUXG09KVLA ARXG09KSLAP ARXG09KLLAP AUXG12KVLA ARXG12KSLAP ARXG12KLLAP AUXG14KVLA ARXG14KSLAP ARXG14KLLAP AUXG18KVLA ARXG18KSLAP ARXG18KLLAP AUXG22KVLA ASYG07KGTB ASYG07KGTE ASYG18KMTB ASYG07KMTB ASYG09KGTB ASYG09KGTE ASYG22KMTB ASYG09KMTB ASYG12KGTB ASYG12KGTE ASYG24KMTB ASYG12KMTB ASYG14KGTB ASYG14KGTE ASYG18KMTE ASYG14KMTB ASYG22KMTE ASYG07KMCC ASYG24KMTE ASYG09KMCC ASYG12KMCC...
  • Page 11 Outdoor unit AOYG30KBTA4 AOYG36KBTA5 - 3 - 1. Model lineup...
  • Page 12: Indoor Unit Connection Patterns

    1-1. Indoor unit connection patterns ¢ 4-unit multi-split type AOYG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — — — — — —...
  • Page 13 AOYG30KBTA4 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Total — — — — — — — — — — — — — — — - 5 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 14 Numbers in column Unit 1 to 4, and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..- 6 - 1-1. Indoor unit connection patterns 1. Model lineup...
  • Page 15 ¢ 5-unit multi-split type AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 16 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 17 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total — — — — — — — — — — — — — — — — — — — — — — — — — — —...
  • Page 18 AOYG36KBTA5 Combination no. Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 Total Numbers in column Unit 1 to 5 and Total indicate the indoor unit capacities as follows: 7: 7,000 Btu/h, 9: 9,000 Btu/h, 12: 12,000 Btu/h, 14: 14,000 Btu/h ..*: As for the 22 model, wall-mounted type indoor unit is only connectable.
  • Page 19: Specifications

    2. Specifications 2-1. Compact cassette type Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.19 0.22 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 20 Model name AUXG18KVLA AUXG22KVLA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.30 0.62 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Turbo fan × 1 Motor output HIGH Cooling...
  • Page 21: Mini Duct Type

    2-2. Mini duct type Model name ARXG07KSLAP ARXG09KSLAP ARXG12KSLAP ARXG14KSLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.29 0.33 0.38 0.58 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET...
  • Page 22 Model name ARXG18KSLAP Power supply 1Ø 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class HIGH Input power QUIET Running current 0.49 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 50...
  • Page 23: Slim Duct Type

    2-3. Slim duct type Model name ARXG07KLLAP ARXG09KLLAP ARXG12KLLAP ARXG14KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.33 0.30 0.35 0.51 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 24 Model name ARXG18KLLAP Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.44 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco fan × 3 Motor output Recommended static pressure 0 to 90 HIGH...
  • Page 25: Medium Static Pressure Duct Type

    2-4. Medium static pressure duct type Model name ARXG22KMLB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.60 HIGH 1,100 Cooling QUIET Airflow rate HIGH 1,100 Heating QUIET Type × Q'ty Sirocco fan ×...
  • Page 26: Wall Mounted Type

    2-5. Wall mounted type Model name ASYG07KGTB ASYG09KGTB ASYG12KGTB ASYG14KGTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 27 Model name ASYG07KGTE ASYG09KGTE ASYG12KGTE ASYG14KGTE Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.29 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 28 Model name ASYG18KMTB ASYG22KMTB ASYG24KMTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power 37.5 47.0 61.6 Running current 0.35 0.39 0.44 HIGH 1,060 1,170 Cooling QUIET Airflow rate HIGH 1,020 1,060 1,170 Heating QUIET...
  • Page 29 Model name ASYG18KMTE ASYG22KMTE ASYG24KMTE Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power 37.5 47.0 61.6 Running current 0.35 0.39 0.44 HIGH 1,060 1,170 Cooling QUIET Airflow rate HIGH 1,020 1,060 1,170 Heating QUIET...
  • Page 30 Model name ASYG07KMTB ASYG09KMTB ASYG12KMTB ASYG14KMTB Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 31 Model name ASYG07KMCC ASYG09KMCC ASYG12KMCC ASYG14KMCC Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 32 Model name ASYG07KMCE ASYG09KMCE ASYG12KMCE ASYG14KMCE Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Crossflow fan ×...
  • Page 33 ASYG07KETA ASYG09KETA ASYG12KETA ASYG14KETA Model name ASYG07KETA-B ASYG09KETA-B ASYG12KETA-B ASYG14KETA-B Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 34 ASYG07KETE ASYG09KETE ASYG12KETE ASYG14KETE Model name ASYG07KETE-B ASYG09KETE-B ASYG12KETE-B ASYG14KETE-B Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.20 0.24 0.24 0.30 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type ×...
  • Page 35: Ceiling Type

    2-6. Ceiling type Model name ABYG18KRTA ABYG22KRTA Power supply 1Ø 230 V ~50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.21 0.25 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Sirocco × 2 Motor output HIGH Cooling...
  • Page 36: Floor Type

    2-7. Floor type Model name AGYG09KVCA AGYG12KVCA AGYG14KVCA Power supply 230 V ~ 50 Hz Available voltage range 198—264 V Capacity kW class Input power Running current 0.15 0.18 0.20 HIGH Cooling QUIET Airflow rate HIGH Heating QUIET Type × Q'ty Cross flow fan ×...
  • Page 37: Dimensions

    3. Dimensions 3-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Unit: mm Grid type grille Hanging bolt position IR receiver Drain hose View A Ceiling Control Box View C View B - 29 - 3-1. Compact cassette type 3.
  • Page 38  Installation space requirement Unit: mm Strong and durable ceiling or more 1,000 1,000 or more or more 1,800 or more Obstruction Floor Maximum height from floor to ceiling (Unit: mm) 07 and 09 models 12 or larger models Standard 2,700 High ceiling —...
  • Page 39: Mini Duct Type

    3-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Unit: mm Rear view View A Drain port P 100 × 6 = 600 Top view Side view Front view Bottom view - 31 - 3-2. Mini duct type 3.
  • Page 40 ¢ Model: ARXG18KSLAP Unit: mm Rear view View A Drain port P 100 × 8 = 800 Top view Side view Front view Bottom view - 32 - 3-2. Mini duct type 3. Dimensions...
  • Page 41  Installation space requirement Provide sufficient installation space for product safety. Unit: mm Strong and durable ceiling Indoor unit Left Right side side or more* or more *: 400 or more when drain from drain pipe • When intaking air from back: •...
  • Page 42: Slim Duct Type

    3-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, and ARXG14KLLAP Unit: mm View A Rear view Drain port 100 x 6 = 600 Side view Top view Front view Bottom view - 34 - 3-3. Slim duct type 3. Dimensions...
  • Page 43 ¢ Model: ARXG18KLLAP Unit: mm Rear view View A Drain port 100 × 8 = 800 Top view Side view Front view Bottom view - 35 - 3-3. Slim duct type 3. Dimensions...
  • Page 44  Installation space requirement Provide sufficient installation space for product safety. In ceiling-concealed installations: Unit: mm 300 or more Strong and durable ceiling 20 or more Indoor unit Left Right side side 20 or more Service access Ceiling or more or more Floor ...
  • Page 45: Medium Static Pressure Duct Type

    3-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Unit: mm Φ205 Φ3.2 Front view 1,177 Gas pipe Drain port Liquid pipe Φ200 Knockout Drain port for fresh air Φ5 Φ3.2 80 80 P125 × 3 = 375 P125 × 3 = 375 Φ5 1,015 1,135...
  • Page 46  Maintenance space requirement Unit: mm • Provide a service access for maintenance purposes. Maintenance hole Control box • The service access necessary for fan units and filter maintenance. Maintenance hole Intake panel Control box 1,550 • When using a square duct P174 ×...
  • Page 47: Wall Mounted Type

    3-5. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG12KGTB, and ASYG14KGTB Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 39 - 3-5. Wall mounted type 3. Dimensions...
  • Page 48  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 49 ¢ Models: ASYG07KGTE, ASYG09KGTE, ASYG12KGTE, and ASYG14KGTE 373.5 417.5 (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 41 - 3-5. Wall mounted type 3. Dimensions...
  • Page 50  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more The flare connection part should be installed outdoors.
  • Page 51 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 43 - 3-5. Wall mounted type 3. Dimensions...
  • Page 52  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more Wall hook bracket 70 or more Outline of the indoor unit 160 or more 117 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 53 ¢ Models: ASYG18KMTE, ASYG22KMTE, and ASYG24KMTE Unit: mm Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 45 - 3-5. Wall mounted type 3. Dimensions...
  • Page 54  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more Wall hook bracket 70 or more 117 or more Outline of the indoor unit 160 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 55 ¢ Models: ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, ASYG14KMTB, ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 47 - 3-5. Wall mounted type 3. Dimensions...
  • Page 56  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket Outline of the indoor unit 107 or more 183 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 57 ¢ Models: ASYG07KMCE, ASYG09KMCE, ASYG12KMCE, and ASYG14KMCE Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 49 - 3-5. Wall mounted type 3. Dimensions...
  • Page 58  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 70 or more Wall hook bracket 107 or more 183 or more Outline of the indoor unit 1,500 or more The flare connection part should be installed outdoors.
  • Page 59 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, ASYG14KETA-B, ASYG07KETE, ASYG09KETE, ASYG12KETE, ASYG14KETE, ASYG07KETE-B, ASYG09KETE-B, ASYG12KETE-B, and ASYG14KETE-B Unit: mm 373.5 417.5 (950) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 51 - 3-5. Wall mounted type 3.
  • Page 60  Installation space requirement Provide sufficient installation space for product safety. Unit: mm 40 or more 40 or more Wall hook bracket Outline of the indoor unit 166 or more 211 or more 1,500 or more The flare connection part should be installed outdoors.
  • Page 61: Ceiling Type

    3-6. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA Unit: mm 1,080 49 84 125 103 Side view Top view ø100-mm hole Rear view Suspension bolt pitch Dimensions Indoor unit (Top view) (Space required for installation) The length of the bolt here is 30 mm.
  • Page 62 ¢ Installation space requirement Unit: mm Ceiling Indoor unit 30 or more Ceiling 200 or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height (m) Ceiling mode Standard High ceiling 18, 22 models...
  • Page 63: Floor Type

    3-7. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Unit: mm Side view Front view - 55 - 3-7. Floor type 3. Dimensions...
  • Page 64  Installation space Unit: mm 100 or more 80 or more 80 or more 50 or more 150 or below from the floor PROHIBITED Grating WARNING • The appliance shall be installed, operated and stored in a room with a floor area larger than X Minimum room area Amount of refrigerant charge M (kg)
  • Page 65: Wiring Diagrams

    4. Wiring diagrams 4-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA - 57 - 4-1. Compact cassette type 4. Wiring diagrams...
  • Page 66: Mini Duct Type And Slim Duct Type

    4-2. Mini duct type and Slim duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, ARXG14KSLAP, ARXG18KSLAP, ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP WLAN adapter, Converter etc. (Option) - 58 - 4-2. Mini duct type and Slim duct type 4. Wiring diagrams...
  • Page 67: Medium Static Pressure Duct Type

    4-3. Medium static pressure duct type ¢ Model: ARXG22KMLB - 59 - 4-3. Medium static pressure duct type 4. Wiring diagrams...
  • Page 68: Wall Mounted Type

    4-4. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG12KGTB, and ASYG14KGTB - 60 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 69 ¢ Models: ASYG07KGTE, ASYG09KGTE, ASYG12KGTE, and ASYG14KGTE - 61 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 70 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB - 62 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 71 ¢ Models: ASYG18KMTE, ASYG22KMTE, and ASYG24KMTE - 63 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 72 ¢ Models: ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, and ASYG14KMTB - 64 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 73 ¢ Models: ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, and ASYG14KMCC - 65 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 74 ¢ Models: ASYG07KMCE, ASYG09KMCE, ASYG12KMCE, and ASYG14KMCE - 66 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 75 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, and ASYG14KETA-B - 67 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 76 ¢ Models: ASYG07KETE, ASYG09KETE, ASYG12KETE, ASYG14KETE, ASYG07KETE-B, ASYG09KETE-B, ASYG12KETE-B, and ASYG14KETE-B - 68 - 4-4. Wall mounted type 4. Wiring diagrams...
  • Page 77: Ceiling Type

    4-5. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA - 69 - 4-5. Ceiling type 4. Wiring diagrams...
  • Page 78: Floor Type

    4-6. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA - 70 - 4-6. Floor type 4. Wiring diagrams...
  • Page 79: Air Velocity And Temperature Distributions

    5. Air velocity and temperature distributions 5-1. Compact cassette type ¢ Models: AUXG07KVLA and AUXG09KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 4 (m) Unit : m/s Side view...
  • Page 80 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE: Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions...
  • Page 81 ¢ Model: AUXG12KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
  • Page 82 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
  • Page 83 ¢ Model: AUXG14KVLA • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit : m/s 0.25 Top view Vertical airflow direction louver: up 0.25 0.25 0.25 4 (m) Unit : m/s Side view Vertical airflow direction louver: up 0.25 0.25 4 (m)
  • Page 84 • Air velocity distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data HIGH HEAT 4-way air outlet Unit : m/s Side view Vertical airflow direction louver: down 0.25 4 (m) • Air temperature distribution Fan speed Operation mode Outlet directions Measuring conditions NOTE:Reference data...
  • Page 85 ¢ Model: AUXG18KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25 0.25...
  • Page 86 ¢ Model: AUXG22KVLA Fan speed Operation mode Ceiling mode Measuring conditions HIGH STANDARD Unit: m/s 0.25 Top view Vertical airflow direction louver: Upward 0.25 0.25 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Upward 0.25 0.25 Unit: m/s Side view Vertical airflow direction louver: Downward 0.25...
  • Page 87: Mini Duct Type

    5-2. Mini duct type ¢ Model: ARXG07KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 88 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 89 ¢ Model: ARXG09KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 90 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 91 ¢ Model: ARXG12KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 92 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 93 ¢ Model: ARXG14KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 94 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 95 ¢ Model: ARXG18KSLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 96 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 97: Slim Duct Type

    5-3. Slim duct type ¢ Model: ARXG07KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 98 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 99 ¢ Model: ARXG09KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 100 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 101 ¢ Model: ARXG12KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 102 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 103 ¢ Model: ARXG14KLLAP NOTE: This data is measured after installing optional Auto louver grille kit. • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 104 • Air velocity distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Fan speed Operation mode Measuring conditions HIGH HEAT Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center...
  • Page 105 ¢ Model: ARXG18KLLAP NOTE: This data is measured installing the Auto louver grille kit (option). Fan speed Operation mode Measuring conditions HIGH • Air velocity distribution Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up...
  • Page 106 Fan speed Operation mode Measuring conditions HIGH HEAT • Air velocity distribution Unit: m/s Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center • Air temperature distribution Unit: °C Side view Vertical airflow direction louver: Down Horizontal airflow direction louver: Center - 98 - 5-3.
  • Page 107: Wall Mounted Type

    5-4. Wall mounted type ¢ Models: ASYG07KGTB, ASYG09KGTB, ASYG07KGTE, ASYG09KGTE, ASYG07KMTB, ASYG09KMTB, ASYG12KMTB, ASYG07KMCC, ASYG09KMCC, ASYG12KMCC, ASYG07KMCE, ASYG09KMCE, ASYG12KMCE, ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, ASYG07KETE, ASYG09KETE, ASYG12KETE, ASYG07KETE-B, ASYG09KETE-B, and ASYG12KETE-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
  • Page 108 ¢ Models: ASYG18KMTB, ASYG22KMTB, ASYG24KMTB, ASYG18KMTE, ASYG22KMTE, and ASYG24KMTE Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right Unit: m/s Side view Vertical airflow direction louver: Up...
  • Page 109 ¢ Models: ASYG12KGTB, ASYG14KGTB, ASYG12KGTE, ASYG14KGTE, ASYG14KMTB, ASYG14KMCC, ASYG14KMCE, ASYG14KETA, ASYG14KETA-B, ASYG14KETE, and ASYG14KETE-B Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 110: Ceiling Type

    5-5. Ceiling type ¢ Model: ABYG18KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25...
  • Page 111 ¢ Model: ABYG22KRTA Fan speed Operation mode Measuring conditions HIGH 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center 0.25 Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left & Right 0.25 Side view 0.25 Vertical airflow direction louver: Up Horizontal airflow direction louver: Center...
  • Page 112: Floor Type

    5-6. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Fan speed Operation mode Fan select Measuring conditions HIGH Upper and lower Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center UPPER LOWER Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
  • Page 113: Fan Performance

    6. Fan performance NOTE: Airflow and capacity/outlet temperature curve data are measured based on the same condi- tions mentioned in "Specifications". 6-1. Mini duct type ¢ Model: ARXG07KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Quiet (SP mode 03) Hi (SP mode 03) Normal SP upper limit...
  • Page 114  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 106 - 6-1. Mini duct type 6. Fan performance...
  • Page 115 ¢ Model: ARXG09KSLAP Quiet (SP mode 00) SP mode 03 upper limit Quiet (Normal SP) Hi (SP mode 03) Quiet (SP mode 03) SP mode 00 upper limit SP mode 03 lower limit Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 116  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 108 - 6-1. Mini duct type 6. Fan performance...
  • Page 117 ¢ Model: ARXG12KSLAP SP mode 03 upper limit Quiet (SP mode 03) Hi (SP mode 03) Quiet Normal SP (Normal SP) upper limit Quiet SP mode 03 (SP mode 00) lower limit SP mode 00 (Normal SP) upper limit Hi (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 03)
  • Page 118  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 110 - 6-1. Mini duct type 6. Fan performance...
  • Page 119 ¢ Model: ARXG14KSLAP Hi (SP mode 05) SP mode 05 upper limit Quiet (SP mode 00) Nomal SP Quiet upper limit (Nomal SP) Quiet Hi (Normal SP) (SP mode 05) SP mode 05 lower limit SP mode 00 upper limit (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 120  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 112 - 6-1. Mini duct type 6. Fan performance...
  • Page 121 ¢ Model: ARXG18KSLAP SP mode 05 Hi (SP mode 05) upper limit Quiet (SP mode 05) SP mode 05 lower limit Quiet (Normal SP) Quiet (SP mode 00) Normal SP upper limit Hi (Normal SP) Hi (SP mode 00) SP mode 00 upper limit 1,000 1,100...
  • Page 122  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacity 1,000 1,100 Airflow (m - 114 - 6-1. Mini duct type 6. Fan performance...
  • Page 123: Slim Duct Type

    6-2. Slim duct type ¢ Model: ARXG07KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Normal SP upper limit lower limited Quiet (SP mode 00)
  • Page 124  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 116 - 6-2. Slim duct type 6. Fan performance...
  • Page 125 ¢ Model: ARXG09KLLAP Hi (SP mode 09) SP mode 09 upper limit Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) Hi (SP mode00) SP mode 00 upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level) Hi (SP mode 09)
  • Page 126  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 118 - 6-2. Slim duct type 6. Fan performance...
  • Page 127 ¢ Model: ARXG12KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) Hi (Normal SP) SP mode 00 Hi (SP mode 00) upper limit Quiet (SP mode 00) Airflow (m Available airflow rate range (High level)
  • Page 128  Characteristics of air volume and capacity • Cooling Capacity Airflow (m • Heating Capacity Airflow (m - 120 - 6-2. Slim duct type 6. Fan performance...
  • Page 129 ¢ Model: ARXG14KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) Nomal SP upper limit SP mode 09 lower limit Quiet (Nomal SP) Hi (Normal SP) SP mode 00 upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000...
  • Page 130  Characteristics of air volume and capacity • Cooling Capacity 1,000 Airflow (m • Heating Capacity 1,000 Airflow (m - 122 - 6-2. Slim duct type 6. Fan performance...
  • Page 131 ¢ Model: ARXG18KLLAP SP mode 09 upper limit Hi (SP mode 09) Quiet (SP mode 09) SP mode 09 lower limit Normal SP upper limit Quiet (Normal SP) SP mode 00 Hi (Normal SP) upper limit Hi (SP mode 00) Quiet (SP mode 00) 1,000 1,100...
  • Page 132  Characteristics of air volume and capacity • Cooling Capacity 1,000 1,100 Airflow (m • Heating Capacitty 1,000 1,100 Airflow (m - 124 - 6-2. Slim duct type 6. Fan performance...
  • Page 133: Medium Static Pressure Duct Type

    6-3. Medium static pressure duct type ¢ Model: ARXG22KMLB (Normal mode) Static pressure (Pa) Fan speed Item — — — — — — — 1200 1100 1000 HIGH — — — — — — — — — — — — —...
  • Page 134 ¢ Model: ARXG22KMLB (Static pressure mode 1) Static pressure (Pa) Fan speed Item — — — — — — 1200 1000 HIGH — — — — — — — — — — — — — — — — 1000 — —...
  • Page 135 ¢ Model: ARXG22KMLB (Static pressure mode 2) Static pressure (Pa) Fan speed Item — — — — — — 1160 HIGH — — — — — — — — — — — — — — — — 1020 — — —...
  • Page 136 ¢ Model: ARXG22KMLB (Static pressure mode 3) Static pressure (Pa) Fan speed Item — — — — — — 1100 HIGH — — — — — — — — — — — — — — — — 1000 — — —...
  • Page 137: Airflow

    7. Airflow Conversion factor: • 1 m /h = 0.2778 l/s = 0.5886 CFM • 3.6 m /h = 1 l/s • 1.699 m /h = 1 CFM 7-1. Compact cassette type Airflow Model Operation mode Fan speed High Cooling AUXG07KVLA Quiet AUXG09KVLA...
  • Page 138: Mini Duct Type

    7-2. Mini duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KSLAP High Heating Quiet High Cooling Quiet ARXG09KSLAP High Heating Quiet High Cooling Quiet ARXG12KSLAP High Heating Quiet High Cooling Quiet ARXG14KSLAP High Heating Quiet High Cooling Quiet ARXG18KSLAP High...
  • Page 139: Slim Duct Type

    7-3. Slim duct type Airflow Model Operation mode Fan speed High Cooling Quiet ARXG07KLLAP High Heating Quiet High Cooling Quiet ARXG09KLLAP High Heating Quiet High Cooling Quiet ARXG12KLLAP High Heating Quiet High Cooling Quiet ARXG14KLLAP High Heating Quiet High Cooling Quiet ARXG18KLLAP High...
  • Page 140: Medium Static Pressure Duct Type

    7-4. Medium static pressure duct type Airflow Model Operation mode Fan speed High 1,100 Cooling Quiet ARXG22KMLB High 1,100 Heating Quiet - 132 - 7-4. Medium static pressure duct type 7. Airflow...
  • Page 141: Wall Mounted Type

    7-5. Wall mounted type Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KGTB High Heating Quiet High Cooling Quiet ASYG09KGTB High Heating Quiet High Cooling Quiet ASYG12KGTB High Heating Quiet High Cooling Quiet ASYG14KGTB High Heating Quiet High Cooling Quiet ASYG07KGTE High...
  • Page 142 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG12KGTE High Heating Quiet High Cooling Quiet ASYG14KGTE High Heating Quiet High Cooling Quiet ASYG18KMTB High 1,020 Heating Quiet High 1,060 Cooling Quiet ASYG22KMTB High 1,060 Heating Quiet High 1,170 Cooling Quiet ASYG24KMTB High...
  • Page 143 Airflow Model Operation mode Fan speed High 1,060 Cooling Quiet ASYG22KMTE High 1,060 Heating Quiet High 1,170 Cooling Quiet ASYG24KMTE High 1,170 Heating Quiet High Cooling Quiet ASYG07KMTB High Heating Quiet High Cooling Quiet ASYG09KMTB High Heating Quiet High Cooling Quiet ASYG12KMTB High...
  • Page 144 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG07KMCC High Heating Quiet High Cooling Quiet ASYG09KMCC High Heating Quiet High Cooling Quiet ASYG12KMCC High Heating Quiet High Cooling Quiet ASYG14KMCC High Heating Quiet High Cooling Quiet ASYG07KMCE High Heating Quiet High Cooling...
  • Page 145 Airflow Model Operation mode Fan speed High Cooling Quiet ASYG12KMCE High Heating Quiet High Cooling Quiet ASYG14KMCE High Heating Quiet High Cooling ASYG07KETA Quiet ASYG07KETA-B High Heating Quiet High Cooling ASYG09KETA Quiet High ASYG09KETA-B Heating Quiet High Cooling ASYG12KETA Quiet High ASYG12KETA-B Heating...
  • Page 146 Airflow Model Operation mode Fan speed High Cooling ASYG07KETE Quiet ASYG07KETE-B High Heating Quiet High Cooling ASYG09KETE Quiet High ASYG09KETE-B Heating Quiet High Cooling ASYG12KETE Quiet ASYG12KETE-B High Heating Quiet High Cooling ASYG14KETE Quiet High ASYG14KETE-B Heating Quiet - 138 - 7-5.
  • Page 147: Ceiling Type

    7-6. Ceiling type Airflow Model Operation mode Fan speed High Cooling Quiet ABYG18KRTA High Heating Quiet High Cooling Quiet ABYG22KRTA High Heating Quiet - 139 - 7-6. Ceiling type 7. Airflow...
  • Page 148: Floor Type

    7-7. Floor type Airflow Model Operation mode Fan speed High Cooling Quiet AGYG09KVCA High Heating Quiet High Cooling Quiet AGYG12KVCA High Heating Quiet High Cooling Quiet AGYG14KVCA High Heating Quiet - 140 - 7-7. Floor type 7. Airflow...
  • Page 149: Compact Cassette Type

    8. Noise level curve 8-1. Compact cassette type ¢ Model: AUXG07KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000...
  • Page 150 ¢ Model: AUXG12KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 151 ¢ Model: AUXG18KVLA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET NC-25 QUIET NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 152: Mini Duct Type

    8-2. Mini duct type ¢ Model: ARXG07KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH NC-35 NC-35 HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 153 ¢ Model: ARXG12KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 154 ¢ Model: ARXG18KSLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency ,Hz Octave band center frequency ,Hz...
  • Page 155: Slim Duct Type

    8-3. Slim duct type ¢ Model: ARXG07KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000...
  • Page 156 ¢ Model: ARXG12KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 HIGH HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 157 ¢ Model: ARXG18KLLAP  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 HIGH NC-45 NC-40 NC-40 HIGH NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 QUIET NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 158: Medium Static Pressure Duct Type

    8-4. Medium static pressure duct type ¢ Model: ARXG22KMLB  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 HIGH HIGH NC-30 NC-30 NC-25 NC-25 QUIET NC-20 QUIET NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000...
  • Page 159: Wall Mounted Type

    8-5. Wall mounted type ¢ Models: ASYG07KGTB and ASYG07KGTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 HIGH HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000...
  • Page 160 ¢ Models: ASYG12KGTB and ASYG12KGTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH NC-45 NC-45 HIGH NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 161 ¢ Models: ASYG18KMTB and ASYG18KMTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 162 ¢ Models: ASYG24KMTB and ASYG24KMTE  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET NC-20 NC-20 QUIET NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000...
  • Page 163 ¢ Models: ASYG09KMTB, ASYG09KMCC, ASYG09KMCE, ASYG09KETA, ASYG09KETA-B, ASYG09KETE, and ASYG09KETE-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 QUIET QUIET 1,000 2,000 4,000...
  • Page 164 ¢ Models: ASYG14KMTB, ASYG14KMCC, ASYG14KMCE, ASYG14KETA, ASYG14KETA-B, ASYG14KETE, and ASYG14KETE-B  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 HIGH HIGH NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 QUIET NC-15 NC-15 QUIET 1,000 2,000 4,000...
  • Page 165: Ceiling Type

    8-6. Ceiling type ¢ Model: ABYG18KRTA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 QUIET QUIET NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 166: Floor Type

    8-7. Floor type ¢ Model: AGYG09KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 HIGH HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000...
  • Page 167 ¢ Model: AGYG14KVCA  Cooling  Heating NC-65 NC-65 NC-60 NC-60 HIGH NC-55 NC-55 HIGH NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 QUIET QUIET NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000 2,000 4,000 8,000 Octave band center frequency, Hz Octave band center frequency, Hz...
  • Page 168: Sound Level Check Point

    8-8. Sound level check point ¢ Compact cassette type Microphone 1.5 m Microphone - 160 - 8-8. Sound level check point 8. Noise level curve...
  • Page 169 ¢ Mini duct type, Slim duct type, and Medium static pressure duct type Product Measuring duct Measuring duct (Set the static pressure as rating in this area.) Microphone Microphone Front view Side view ¢ Wall mounted type Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above.
  • Page 170 ¢ Floor type Microphone Microphone ● ● Airflow Airflow - 162 - 8-8. Sound level check point 8. Noise level curve...
  • Page 171: Electrical Characteristics

    9. Electrical characteristics Wiring spec. of connection Power supply cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Cross- Limited Input sectional wiring power Type Model name area length AUXG07KVLA 0.19 0.15 AUXG09KVLA 0.19 0.15 AUXG12KVLA 0.24 0.19 Compact cassette AUXG14KVLA...
  • Page 172 Wiring spec. of connection Power supply cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Cross- Limited Input sectional wiring power Type Model name area length ASYG07KGTB 0.25 0.20 ASYG09KGTB 0.30 0.24 ASYG12KGTB 0.30 0.24 ASYG14KGTB 0.37 0.29 ASYG07KGTE 0.25...
  • Page 173 Wiring spec. of connection Power supply cable Indoor rated (50 Hz, 230 V) (Indoor unit to outdoor unit) Cross- Limited Input sectional wiring power Type Model name area length ABYG18KRTA 0.39 0.21 Ceiling ABYG22KRTA 0.49 0.25 AGYG09KVCA 0.19 0.15 Floor AGYG12KVCA 0.23 0.18...
  • Page 174: Safety Devices

    10. Safety devices Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse AUXG07KVLA AUXG09KVLA Activate: 100 ±15 °C Fan motor stop AUXG12KVLA Compact cassette Reset: 95 ±10 °C AUXG14KVLA AUXG18KVLA Fan motor restart AUXG22KVLA ARXG07KSLAP ARXG09KSLAP...
  • Page 175 Terminal Indoor unit Float Model name PCB* fuse Fan motor thermal protector thermal type switch fuse ASYG07KMCC Activate: 170 °C ASYG09KMCC Fan motor stop ASYG12KMCC Reset: 145 °C ASYG14KMCC Fan motor restart ― ASYG07KMCE Activate: 170 °C ASYG09KMCE Fan motor stop ASYG12KMCE Reset: 145 °C...
  • Page 176: External Input And Output

    11. External input and output 11-1. Compact cassette type, Mini duct type, Slim duct type, and Medium static pressure duct type Exterior of the indoor unit PCB and the component location differ by the type of the indoor unit as follows.
  • Page 177 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m. •...
  • Page 178 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input External output Mode Function setting Terminal CN47 60—00...
  • Page 179 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 Function setting External input Input signal Command Off → On Operation 46—00 Terminal On → Off Stop Input Operation Indoor unit Stop Remote controller NOTES: •...
  • Page 180 • When function setting is "Operation/Stop" mode 2 Function setting External input Input signal Command Off → On Operation 46—03 Terminal On → Off Stop (R.C. disabled) Input Operation Indoor unit Stop (R.C. disabled) Remote controller NOTE: When "Operation/Stop" mode 2 function is used with forming a remote controller group, connect the same equipment to each indoor unit within the group.
  • Page 181  Indoor unit fan operation status Function setting External output Output signal Command Low → High Fan run 60—10 CN47 High → Low Fan stop Output signal Condition The indoor unit fan is operating. Low → High The fan is stopped or during cold air prevention. During thermostat off when in dry mode operation.
  • Page 182: 11-2.Wall Mounted Type (Kgtb, 18-24Kmtb, Keta, And Keta-B)

    11-2. Wall mounted type (KGTB, 18-24KMTB, KETA, and KETA- External input and output PCB SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 To CN6 on Indoor unit PCB Input External input External output Connector Input select signal Operation/Stop CN313/ Edge/Pulse Dry contact/...
  • Page 183 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 184 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  External input and output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 185 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
  • Page 186  Input signal type External input and output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out- put PCB. The width of pulse must be longer than 200 msec.
  • Page 187 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-00...
  • Page 188 • When function setting is "Forced stop" mode – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Forced stop External input and 46-02 60-00 / 1 CN313 output PCB...
  • Page 189 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input: Rotary SW on Function External input and External input Input signal Command setting / output PCB Off → On Operation External input and 46-03 60-00 / 1 CN313 Stop (R.C.
  • Page 190 • Forced thermostat off function Rotary SW on Function External input and External input Input signal Command setting / output PCB Thermostat 60-00 / 2 Off → On External input and output 60-09 / B CN313 Normal 60-10 / C On →...
  • Page 191  Control output function • Operation/Stop status Rotary SW on Function Output External input and External output Command setting / signal output PCB Off → On Operation External input and output 60-00 / 1 CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 192: 11-3.Wall Mounted Type (07-14Kmtb And Kmcc)

    11-3. Wall mounted type (07-14KMTB and KMCC) With using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks CNA01 Control input — See external input/output CNB01 — Operation status output settings for details.
  • Page 193 • Circuit diagram example • Contact capacity: DC 24 V or more, 10 Indoor unit mA or more. Communication kit Connected unit control PCB • *: Make the distance from the PCB to Example: Switch Connector the connected unit within 10 m. •...
  • Page 194 • Optional part Part name Model name Exterior External input wire External connect kit UTY-XWZXZ5 Communication kit UTY-TWBXF2 * For operating the external function, the wall mounted type requires the communication kit in addi- tion to the wire (UTY-XWZXZ5). - 186 - 11-3.
  • Page 195 ¢ External output With using external output function, operating status of this product can be transmitted to the exter- nal device, and also, this product can be inter-connected with the external device.  Operation status output Air conditioner operation status signal can be output. •...
  • Page 196  Error status output Air conditioner error status signal can be output. • Circuit diagram example: Indoor unit control PCB Communication kit Connected unit Connector DC 24 V Example: Relay unit Example: Display Relay power supply 10 m* Signal Optional parts Locally purchased –...
  • Page 197: 11-4.Wall Mounted Type (Kgte, Kmte, Kmce, Kete, And Kete-B)

    11-4. Wall mounted type (KGTE, KMTE, KMCE, KETE, and KETE-B) External input and output PCB Indoor unit PCB CN47 (Ext. out) CN65 (Ext. in/out PCB) CN46 (Ext. in) SW301 SW302 Rotary switch CN314 CN313 CN312 CN311 CN310 CN308 Input External input External output Connector Input select...
  • Page 198 ¢ External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
  • Page 199  External input and output PCB The indoor unit Operation/Stop can be set by using the input connector on the PCB. • Input select: Use either one of these types of connectors according to the application. (Both types of connec- tors cannot be used simultaneously.) –...
  • Page 200 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable should be used. Maximum length of cable is 25 m. •...
  • Page 201  External input and output PCB • A twisted pair cable should be used. Maximum length of cable is 25 m. • Output voltage: High DC 12 V±2 V, Low 0 V. • Permissible current: 50 mA • For details, refer to "Combination of external input and output"...
  • Page 202 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input Function Rotary...
  • Page 203  Input signal type External input and output PCB: The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch SW302 on the External input and out- put PCB. The width of pulse must be longer than 200 msec.
  • Page 204 ¢ Details of function  Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-00...
  • Page 205 • When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Forced stop External input and 46-02 CN313 output PCB On →...
  • Page 206 • When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-03 CN313 Stop (R.C. output PCB On →...
  • Page 207 • Forced thermostat off function Rotary SW on Input Function setting / External input External input Command signal and output PCB Thermostat 60-00 Off → On External input and 60-09 CN313 output PCB Normal On → Off 60-10 operation Input Compressor Room temp.
  • Page 208  Control output function • Operation/Stop status Rotary SW on Output Function setting / External input External output Command signal and output PCB 60-00 / 1 Off → On Operation Output of indoor unit CN47 60-00 / 2 On → Off Stop 60-00 / 1 Off →...
  • Page 209 • Indoor unit fan operation status Rotary SW on Output Function setting / External input External output Command signal and output PCB Off → On Fan run 60-10 / C Output of indoor unit CN47 On → Off Fan stop 60-00 / 2 Off →...
  • Page 210: 11-5.Ceiling Type

    11-5. Ceiling type Rotary switch CN65 CN47 (Ext.in/out PCB) (Ext.out) Terminal (Ext.in) Fig. Indoor unit PCB Fig. External input and output PCB External Input connect kit External input External output Connector Input select signal (Optional parts) Operation/Stop — Terminal Dry contact Edge —...
  • Page 211  External input and output PCB The indoor unit Operation/Stop can be set by using the input terminal on the PCB.  Input select Use either one of these types of terminals according to the application. (Both types of terminals cannot be used simultaneously.) •...
  • Page 212 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
  • Page 213 ¢ Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Function...
  • Page 214  Input signal type • Indoor unit Input signal type is only "Edge". Edge • External input and output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (SW2) on the External input and output PCB.
  • Page 215 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Pulse" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Input 1 Pulse Operation External input and...
  • Page 216 • When function setting is "Forced stop" mode – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Forced stop Input of indoor unit Terminal On →...
  • Page 217 • When function setting is "Operation/Stop" mode 2 – In the case of "Edge" input Rotary SW of Function External input and External input Input signal Command setting / output PCB Off → On Operation Input of indoor unit Terminal Stop (R.C.
  • Page 218  Forced thermostat off function Function Rotary SW of External External input Input signal Command setting / input and output PCB 60-00 / 2 Off → On Thermostat off 60-09 / B External input and output Input 1 60-10 / C Normal On →...
  • Page 219  Error status Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Error 60-09 / B Output of indoor unit CN47 High → Low Normal Off → On Error 60-00 / 2 Output 1 On →...
  • Page 220  External heater output Function Rotary SW of External External output Output signal Command setting / input and output PCB Low → High Heater on 60-11 / D Output of indoor unit CN47 High → Low Heater off 60-00 / 2 Off →...
  • Page 221: 11-6.Floor Type

    11-6. Floor type Indoor unit PCB CN 23 CN 21 CN 15 CN 14 P 190 External input External output Connector Input signal Operation/Stop CN14 Forced stop — Edge Forced thermostat off CN15 Operation status Indoor unit Error status CN20/CN21/ —...
  • Page 222 ¢ External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed.  Indoor unit • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m . •...
  • Page 223 ¢ Combination of external input and output By combining the function setting of the indoor unit, you can select various combinations of func- tions. Combination examples of external input and output are as follows: External input Function Mode Indoor unit setting CN14 CN15...
  • Page 224 ¢ Details of function  Control input function • When function setting is "Operation/Stop" mode 1 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 On → Off Stop 46-00 Input of indoor unit...
  • Page 225 • When function setting is "Operation/Stop"mode 2 – In the case of "Edge" input Mode Function setting External input Input signal Command Off → On Operation — CN14 Stop (R.C. On → Off disabled) 46-03 Input of indoor unit Off → On Operation 60-00 CN15...
  • Page 226  Control output function • Operation/Stop status Output Mode Function setting External output Command signal Low → High Operation 60-00 CN15 High → Low Stop Output of indoor unit Off → On Operation 60-00 CN20 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
  • Page 227 • Indoor unit fan operation status Output Mode Function setting External output Command signal Low → High Fan run 60-10 CN15 High → Low Fan stop Output of indoor unit Off → On Fan run 60-00 CN22 On → Off Fan stop Output signal Condition...
  • Page 228 • Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 220 - 11-6.
  • Page 229 • Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 230: Group Connection

    12. Group connection NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
  • Page 231 2. Set the R.C. address. (Function setting) • Addresses will be automatically set when initially starting up this unit. In such a case, do not change the remote controller address for the indoor unit, and keep it at the initial setting of “00”.
  • Page 232: Remote Controller

    13. Remote controller 13-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) ¢ Overview AR-REW4E Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button...
  • Page 233 To facilitate explanation, the accompanying illustration has been drawn to show all possible indicators; in actual operation, however, the display will only show those indicators appropriate to the current oper- ation. - 225 - 13-1. Wireless remote controller (AR-REW4E, AR-REM4E, and AR-REB1E) 13.
  • Page 234 AR-REM4E Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button RESET button NEXT button...
  • Page 235 AR-REB1E Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button CLOCK ADJUST button TIMER CANCEL button NOTE: Functions may differ by type of the indoor unit.
  • Page 236 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 237: 13-2.Wireless Remote Controller (Ar-Rew3E)

    13-2. Wireless remote controller (AR-REW3E) ¢ Overview Signal SENSOR button transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button...
  • Page 238 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 239: 13-3.Wireless Remote Controller (Ar-Rew2E)

    13-3. Wireless remote controller (AR-REW2E) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 240 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 125 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 241: 13-4.Wireless Remote Controller (Ar-Rem7E)

    13-4. Wireless remote controller (AR-REM7E) ¢ Overview Signal transmitter MODE button FAN button 10 °C HEAT button SWING button ECONOMY button TEMP. button OUTDOOR UNIT SET button LOW NOISE button POWERFUL button WEEKLY button TIMER SETTING button Start/Stop button ON/OFF button SEND button SLEEP button SELECT button...
  • Page 242 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 243: 13-5.Wireless Remote Controller (Ar-Rmb1E)

    13-5. Wireless remote controller (AR-RMB1E) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button ECONOMY button SWING button OUTDOOR UNIT SET button LOW NOISE button TEMP. button ON TIMER button POWERFUL button OFF TIMER button Start/Stop button TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button...
  • Page 244 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 245: 13-6.Wireless Remote Controller (Uty-Lnty: Optional Part)

    13-6. Wireless remote controller (UTY-LNTY: Optional part) ¢ Overview Signal transmitter MODE button FAN button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button TEST RUN button TIMER CANCEL button...
  • Page 246 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 247: 13-7.Ir Receiver Kit With Wireless Remote Controller (Uty-Lbtym: Optional Part)

    13-7. IR receiver kit with Wireless remote controller (UTY- LBTYM: Optional part) ¢ Overview Signal transmitter FAN button MODE button 10°C HEAT button TEMP. SWING button button SET button Economy button ON TIMER button OFF TIMER button Start/Stop button REG1U TIMER SELECT button RESET button SLEEP TIMER button...
  • Page 248 ¢ Specifications  Controller Unit: mm Top view Front view Side view Size (H × W × D) 205 × 61 × 17 Weight 124 (without batteries)  Holder Unit: mm 48.5 Ø 3.5 (Hole) Hole 26.2 69.3 Front View Side View Bottom View Size (H ×...
  • Page 249  IR receiver Unit: mm 13.6 57.4 13.6 11.5 18.5 Front view Side view Rear view Size (H × W × D) 145 × 90 × 30 Weight - 241 - 13-7. IR receiver kit with Wireless remote controller (UTY-LBTYM: Optional part) 13.
  • Page 250: 13-8.Wired Remote Controller (Uty-Rnnym: Optional Part)

    13-8. Wired remote controller (UTY-RNNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b SET TEMP. button Selects the setting temperature. c MODE button Selects the operating mode (AUTO , HEAT ,FAN COOL , and DRY d FAN button Selects the fan speed AUTO ,QUIET , LOW...
  • Page 251 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 252 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Front view Side view Size (H × W × D) 120 × 120 × 18 Weight Cable length (accessory) Power  Wiring specifications Cable size Wire type Remarks Remote controller cable...
  • Page 253  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 254: 13-9.Wired Remote Controller (Uty-Rlry: Optional Part)

    13-9. Wired remote controller (UTY-RLRY: Optional part) ¢ Overview a LED lamp (Operation indicator) Lights while the indoor unit is operating. Blinks when an error occurred. b FAN button Each time the button is pressed, fan speed switches as follows: Auto High Quiet...
  • Page 255 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 256 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm Hole: 9 × 4.5 Hole: 12.5 × 4.5 Hole: 6 × 4.5 Front view Side view Rear view Size (H × W × D) 120 ×...
  • Page 257: 13-10.Wired Remote Controller (Uty-Rvnym: Optional Part)

    13-10. Wired remote controller (UTY-RVNYM: Optional part) ¢ Overview a Display panel (with backlight) b Screen switch button (Left) c Menu button d Cancel button e Cursor button f Screen switch button (Right) g Power indicator h On/off button i Enter button - 249 - 13-10.
  • Page 258 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 259 ¢ Specifications Unit: mm 21.3 Front view Side view Size (H × W × D) 120 × 120 × 21.3 Weight  Wiring specifications Cable size Wire type Remarks Remote controller cable Polar 3 core Use sheathed PVC cable. 0.33 mm - 251 - 13-10.
  • Page 260 ¢ Installation (Remote control main unit) Installation space: Unit : mm or more or more or more 220 or more* NOTE: Secure enough space where a flat-blade screwdriver to remove the case can be inserted. Installation procedures: 1. Process the remote controller cable. Unit : mm 1.
  • Page 261 3. Attach the remote controller. • When attaching to switch box: a. Seal the wiring hole of the remote controller cable. b. Put a remote controller cable through the hole of the rear case. c. Fix the rear case by securing it with attached screws (2 places). •...
  • Page 262 4. Connect the cable to the terminals on the front case. Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie. Tightening torque Terminal screw 0.8 to 1.2 N•m 1. 12V (Red) 2. Signal (White) 3.
  • Page 263 5. Attach the front case. • Insert after adjusting upper part of front case. • When insert the front case, do not pinch the cable. Front case Click! Good Prohibited Prohibited Prohibited CAUTION Insert the upper case firmly. If improperly attached, it will cause the upper case to fall off. ¢...
  • Page 264  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 265: 13-11.Wired Remote Controller (Uty-Rnryz*: Optional Part)

    13-11. Wired remote controller (UTY-RNRYZ*: Optional part) ¢ Overview a Remote temperature sensor (inside) b On/off button Operable only while displaying the “Monitor mode” screen. c LED lamp (operation indicator) d Touch panel display e Set temperature Operating temperature can be set. f Remote controller group name g Mode Operation mode can be set.
  • Page 266 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 267 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. [Unit : mm] 20.4 Model name UTY-RNRYZ* Display 3.8-inch FSTN LCD (255 × 160 dots) with touch panel Dimensions (H × W × D) 120 × 120 × 20.4 Weight Input voltage DC 12...
  • Page 268: 13-12.Wired Remote Controller (Uty-Rcryz1: Optional Part)

    13-12. Wired remote controller (UTY-RCRYZ1: Optional part) ¢ Overview a Display panel b MODE button c Menu button buttons (Set temperature buttons) e FAN button f On/off button g Wireless remote controller signal receiving section - 260 - 13-12. Wired remote controller (UTY-RCRYZ1: Optional part) 13.
  • Page 269 ¢ System diagrams • Single remote control I.U. Remote controller cable A ≤ 500 m ¢ Electrical wiring Indoor unit Remote controller - 261 - 13-12. Wired remote controller (UTY-RCRYZ1: Optional part) 13. Remote controller...
  • Page 270 ¢ Specifications Unit: mm Hole × 2 (for M4 screws) Size (H × W × D) 86 × 86 × 32 Weight  Wiring specifications Cable size Wire type Remarks Remote controller 0.33 to 1.25 mm Non polar 2-core Use sheathed twist pair cable.* cable (22 to 16 AWG) *: Use shielded cable (locally purchased) in accordance with the regional cable standard.
  • Page 271 • Pattern B 1. Use a tool to cut off the terminal on the end of the remote controller cable, and then remove the insulation from the cut end of the cable as shown below. 20 mm Remote controller cable (Non-polar) 2.
  • Page 272: 13-13.Simple Remote Controller (Uty-Rsnym: Optional Part)

    13-13. Simple remote controller (UTY-RSNYM: Optional part) ¢ Overview a START/STOP button Starts and stops operation. b Display backlight button Lights during operation. c Operation lamp Lights during operation. d FAN button Selects the fan speed (AUTO ,HIGH , MED , and QUIET ).
  • Page 273 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 274 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm hole x 2 hole x 2 Front View Side View Rear View Size (H × W × D) 120 × 75 × 14 Weight Cable length (accessory) Power ...
  • Page 275  When connecting to Communication kit (for KM models in Wall mounted type) When connecting the remote controller to optional Communication kit, follow the procedures men- tioned below. Modify the remote controller cable as follows: • Use a tool to cut off the terminal on the end of the remote controller cable and then remove the insulation from the cut end of the cable as shown in following figure.
  • Page 276: 13-14.Simple Remote Controller (Uty-Rsry And Uty-Rhry: Optional Parts)

    13-14. Simple remote controller (UTY-RSRY and UTY-RHRY: Optional parts) ¢ Overview a LED lamp Lights during operation. b Louver button Adjusts the airflow direction. c START/STOP button Starts and stops operation. d FAN control button Switches the fan speed as follows: Auto High Quiet...
  • Page 277 ¢ System diagram 1 remote controller: 2 remote controllers: Indoor unit Indoor unit A, B, C: Remote controller cable A ≤ 500 m;B + C ≤ 500 m Primary Secondary Remote controllers Remote controller ¢ Electrical wiring 1 remote controller: 2 remote controllers: Indoor unit Indoor unit...
  • Page 278 ¢ Specifications Dimensions and other specifications on the wired remote controller are as follows. Unit: mm 30.0 30.0 Hole: 9 × 4.5 23.0 Hole: 6 × 4.5 Hole: 12.5 × 4.5 Front View Side View Rear View Size (H × W × D) 120 ×...
  • Page 279: Function Settings

    14. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 14-1. Compact cassette, Mini duct, Slim duct types indoor unit (setting by DIP switch) By using some components on the PCB, you can change the function settings.
  • Page 280 ¢ DIP switch setting • SW100: Remote controller address setting When operating a number of indoor units by using a wired remote controller, DIP switch set- ting for assigning unit number to each indoor unit is required. The slide switches are normally set to make the unit number 00. Remote Switch number controller...
  • Page 281: 14-2.Indoor Unit (Setting By Wireless Remote Controller)

    14-2. Indoor unit (setting by wireless remote controller) CAUTION This setting changes the function settings used to control the indoor unit according to the installa- tion conditions. Incorrect settings can cause a product malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 282 ¢ AR-REM4E (for Wall mounted type KGTB), AR-REW3E (for Wall mounted type KGTE), AR-REW4E (for Wall mounted type KETA and KETE), AR-REW2E (for Wall mounted type KMTB and KMTE), and AR-REM7E (for Floor type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller.
  • Page 283  Function setting procedure Connect the power supply of the outdoor unit. To enter the function setting mode, while holding down the POWERFUL and TEMP. button, press the RESET button. POWERFUL TEMP. ( RESET Function setting mode display Select the function number by pressing the or the buttons.
  • Page 284 Press the MODE button once to transmit the function mode information. Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted.
  • Page 285  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 286  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the TEMP.
  • Page 287 ¢ AR-REB1E (for Wall mounted type KMCC) and AR-RMB1E (for Wall mounted type KMCE)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 288 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the POWERFUL button. (To return to the function number selection, press the POWERFUL button again.) Select the function number by pressing the or the...
  • Page 289 Press the button once to transmit the function setting information. 2 short beeps will be emitted from the indoor unit when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 2 short beeps NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 290  Resetting the power after setting up all indoor units Important: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 291  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 292 ¢ UTY-LNTY (for Compact cassette type) or AR-REJ1E (included in UTY-LBTYM for Duct type)  Button name and function During address setting mode, indoor unit reject the any operation command from remote con- troller. Function number Refer to Function details. Setting number Refer to Function details.
  • Page 293 Select the function number by pressing the or the buttons. Each time the 10°C HEAT button is pressed, it switches between the right digit and the left digit. Change digit Change digit Proceed to the setting number by pressing the ECONOMY button. (To return to the function number selection, press the ECONOMY button again.) Select the function number by pressing the or the...
  • Page 294 Press the button once to transmit the function setting information. 1 short beep will be emit- ted from the indoor unit or the IR receiver when the signal is received correctly. If wrong code is set, no beep sound will be emitted. 1 short beep NOTE: Press button within 30 seconds after pressing MODE button.
  • Page 295  Setting up each indoor unit Repeat step from 1. to 8. to set up each indoor unit. If the custom code is other than " ", steps from 1. to 2. and 8. need to be performed.  Resetting the power after setting up all indoor units Important: •...
  • Page 296  Remote controller custom code setting Custom code setting of wireless remote controller needs to be same as the setting of the indoor unit. When you change the custom code setting of the wireless remote controller, do as follows: Press the START/STOP button until only the clock is displayed on the display. Press the MODE button for at least 5 seconds to display the current custom code (initially set to Press the SET TEMP.
  • Page 297: 14-3.Indoor Unit (Setting By Wired Remote Controller)

    14-3. Indoor unit (setting by wired remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 298 ¢ UTY-RNNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Refer to Function details Remote controller address Setting number Refer to Function details Λ SET TEMP. “V” and “ ”...
  • Page 299 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit. Not good Good ● Data is not set up on the indoor unit Data is correctly set up on the indoor unit correctly (-- is displayed.) (Flashing display changes to illuminated display.) ●...
  • Page 300 ¢ UTY-RLRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 301 Pressing the "+" or "-" button, to select the function number. Then press the "ENTER" button. Function number Pressing the "+" or "-" button, to select the setting number. Then press the "ENTER" button. Setting number Example: Function number 30 Setting number 01 Error Good...
  • Page 302 ¢ UTY-RVNYM  Function setting procedure Connect the power supply of the outdoor unit. Switch to the function setting mode. When [Menu button] is pressed twice while “Monitor” screen is displayed, it switches to the “Submenu” screen. If [Menu button] is pressed while the “Submenu” screen is displayed, the display returns to the “Monitor”...
  • Page 303 Select the [Function No.] with pressing the [Cursor button (Left/Right)], and select the Function No. to be set with pressing the [Cursor button (Up/Down)]. Function setting Mo 10:00AM R.C. Function Setting address Cancel: Version Error history Select the [Setting No.] with pressing the [Cursor button (Left/Right)], and select the Setting No. to be set with pressing the [Cursor button (Up/Down)].
  • Page 304 When [Cancel button] is pressed twice while “Function setting” screen is displayed, it switches to the “Submenu” screen. Function setting Mo 10:00AM R.C. Function Setting Submenu Mo 10:00AM address Date and time Screen Cancel: Filter sign Version Error history R.C. sensor control Room temp.
  • Page 305 ¢ UTY-RNRYZ*  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 306 “Function No.” screen is displayed. Set the “Function No.” with Function No. Cancel When the “OK” is touched, the display returns to the “Function Setting” screen. Touch the “Function No.” on the “Function Setting” screen. Function Setting Address [002–01] Function No. [30] Setting No.
  • Page 307 Touch the “Yes” of the verification screen. Function Setting Function setting will be performed. OK? In case of “ERROR” In case of “OK” Function Setting Function Setting Address [002–01] Address [002–01] Function No. [30] Function No. [30] Setting No. [01] Setting No.
  • Page 308 14-4. Indoor unit (setting by simple remote controller) • The function settings of the control of the indoor unit can be changed by this procedure according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. • After the power is turned on, perform the “Function setting” according to the installation conditions using the remote controller.
  • Page 309 ¢ UTY-RSNYM  Button name and function During address setting mode, indoor unit reject the any operation command from remote controller. Function number Setting number Refer to Function details Refer to Function details Remote controller address START/STOP button Transmits function setting FAN button SET TEMP.
  • Page 310 Select the setting number by pressing the SET TEMP. or SET TEMP. button. The setting number indicator flashes during setting number selection. Setting number Example) Function number : 30, Setting number : 01 Confirm the setting by pressing the TIMER SET button. The data will be transferred to the indoor unit.
  • Page 311  Resetting the power after setting up function of all indoor units NOTES: • If the reset is not performed, function cannot be read correctly. • After all the functions have been set, the circuit breaker needs to be switched off for at least 2 minutes.
  • Page 312 ¢ UTY-RSRY/UTY-RHRY  Setting procedure by using wired remote controller The function number and the associated setting value are displayed on the LCD of the remote con- troller. Follow the instructions written in the local setup procedure supplied with the remote controller, and select appropriate setting according to the installation environment.
  • Page 313 Select the item number to be set with the SET TEMP. or SET TEMP. button, and press button to switch to the setting screen. Select the “13” in Menu 2-F1 settings. Then, press the button. Select the 2-wire remote controller address with the SET TEMP. or SET TEMP.
  • Page 314 Setting results are displayed after data transmission. Press the button to return to the 2-wire remote controller address selection screen of step 9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se- lection screen.
  • Page 315 14-5. Function details ¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected.  Function setting list Medium Functio Compact...
  • Page 316 Wall mounted Functio Functions n no. KGTB KGTE KMTB KMTE KMCC KMCE KETA KETE Remote controller ● — ● — ● — ● — address setting Filter sign ● ● ● ● ● ● ● ● Ceiling height — — —...
  • Page 317 1) Remote controller address setting (for Wall-mounted type only) NOTES: • Because this setting is normally done automatically when 2-wire-type wired remote controller is installed, setting is unnecessary. • This setting is configurable only by wireless remote controller, but not configurable by Polar 3- wired remote controller.
  • Page 318 3) Ceiling height (for Compact cassette type and Ceiling type only) Select the appropriate ceiling height according to the place of installation. Function number Setting value Setting description Factory setting Standard ♦ High ceiling For the specific height for each setting value, refer to “Installation space” in Chapter 3. "Dimensions"...
  • Page 319 6) Static pressure (for Mini duct type and Slim duct type) Select the appropriate static pressure according to the installation conditions. For mini duct type: Function number Setting value Setting description Factory setting 0 Pa 10 Pa 20 Pa 30 Pa 40 Pa 50 Pa Standard...
  • Page 320 8) Room temperature control for indoor unit sensor NOTE: If the remote sensor unit option is selected, perform this setting. Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 321 9) Room temperature control for wired remote controller sensor (for other than Floor type) Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 322 12) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 13) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
  • Page 323 16) Switching functions for external output terminal (For other than 18-24KMTB and KETA models in Wall-mounted type) Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦...
  • Page 324 14-6. Wired remote controller (UTY-RNNYM) Prohibited Dual remote controller setting Prohibited DIP switch 1 °F/°C switch Prohibited Memory backup setting * Do not use DIP switch 2. ¢ Switch location Front case (back side) DIP switch 2 DIP switch 1 ¢...
  • Page 325  SW6: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure. Memory backup Factory setting Disable ♦...
  • Page 326 14-7. Wired remote controller (UTY-RVNYM) Memory backup setting DIP switch 1 Dual remote controller setting ¢ Switch location ¢ DIP switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 327 14-8. Wired remote controller (UTY-RLRY) DIP switch Memory backup setting ¢ Switch location Front case (back side) Set the DIP switch to ON ¢ Dip switch setting  SW1: Memory backup setting Set to “ON” to use batteries for the memory backup. When batteries are not used, all of settings stored in memory will be deleted if there is a power failure.
  • Page 328 14-10. Simple remote controller (UTY-RSNYM) Prohibited Dual remote controller setting °F/°C switch DIP switch Prohibited Prohibited Prohibited ¢ Switch location DIP Switch ¢ DIP switch setting  SW2: Dual remote controller setting Set the remote controller SW2 according to the following table. Primary unit Secondary unit Number of remote controller...
  • Page 329 15. Accessories 15-1. Compact cassette type ¢ Models: AUXG07KVLA, AUXG09KVLA, AUXG12KVLA, AUXG14KVLA, AUXG18KVLA, and AUXG22KVLA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose insulation Operating manual Hose band (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Template (Carton top) (small) M10 nut A...
  • Page 330 15-2. Mini duct type ¢ Models: ARXG07KSLAP, ARXG09KSLAP, ARXG12KSLAP, and ARXG14KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation...
  • Page 331 ¢ Model: ARXG18KSLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Drain hose Operating manual Hose band (CD-ROM) Installation manual Drain hose insulation B Installation template Washer (Carton top) Coupler heat insulation Cable tie (large) (large) Coupler heat insulation Cable tie (medium) (small) Insulation...
  • Page 332 15-3. Slim duct type ¢ Models: ARXG07KLLAP, ARXG09KLLAP, ARXG12KLLAP, ARXG14KLLAP, and ARXG18KLLAP Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (Large) Installation manual Cable tie (Small) Installation template Drain hose Washer Hose band Coupler heat insulation Drain hose insulation B (Large) Coupler heat insulation...
  • Page 333 15-4. Medium static pressure duct type ¢ Model: ARXG22KMLB Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cable tie (medium) Operating manual Cable tie (small) (CD-ROM) Coupler heat insulation Installation manual (large) Coupler heat insulation Hanger (small) M10 nut A Drain hose insulation (with flange) M10 nut B...
  • Page 334 15-5. Wall mounted type ¢ Models: ASYG07-14KGTB, ASYG07-14KMTB, and ASYG07-14KMCC Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder...
  • Page 335 ¢ Models: ASYG07KGTE, ASYG09KGTE, ASYG12KGTE, and ASYG14KGTE Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 327 -...
  • Page 336 ¢ Models: ASYG18KMTB, ASYG22KMTB, and ASYG24KMTB Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Tapping screw (large) Installation manual Tapping screw (small) Remote controller Battery Remote controller Filter holder holder Cloth tape Air cleaning filters Wall hook bracket - 328 - 15-5.
  • Page 337 ¢ Models: ASYG18KMTE, ASYG22KMTE, and ASYG24KMTE Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Remote controller Filter holder holder Battery Air cleaning filters - 329 - 15-5.
  • Page 338 ¢ Models: ASYG07KMCE, ASYG09KMCE, ASYG12KMCE, and ASYG14KMCE Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery Filter holder Remote controller Air cleaning filters holder - 330 -...
  • Page 339 ¢ Models: ASYG07KETA, ASYG09KETA, ASYG12KETA, ASYG14KETA, ASYG07KETA-B, ASYG09KETA-B, ASYG12KETA-B, ASYG14KETA-B, ASYG07KETE, ASYG09KETE, ASYG12KETE, ASYG14KETE, ASYG07KETE-B, ASYG09KETE-B, ASYG12KETE-B, and ASYG14KETE-B Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Cloth tape Operating manual Tapping screw (large) (CD-ROM) Installation manual Tapping screw (small) Remote controller Wall hook bracket Battery...
  • Page 340 15-6. Ceiling type ¢ Models: ABYG18KRTA and ABYG22KRTA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual Insulation Operating manual Drain hose (CD-ROM) Installation manual Hose band Template Cable tie (large) M10 nut A Cable tie (small) (with flange) M10 nut B Remote controller cable (with spring lock...
  • Page 341 15-7. Floor type ¢ Models: AGYG09KVCA, AGYG12KVCA, and AGYG14KVCA Part name Exterior Q’ty Part name Exterior Q’ty Operating manual (CD- Operating manual ROM) Installation manual Cloth tape Wall hook bracket Tapping screws (large) Remote controller Tapping screws (small) Battery Air cleaning filters Remote controller holder - 333 -...
  • Page 342 16. Optional parts 16-1. Controllers ¢ Lineup Type Indoor unit type Wireless remote controller AR-REM4E AR-REM7E AR-REB1E AR-REW2E Compact cassette — — — — Mini duct — — — — Slim duct — — — — Medium static pressure duct —...
  • Page 343 Type Indoor unit type Wired remote controller UTY-RNNYM UTY-RVNYM UTY-RLRY UTY-RNRYZ* UTY-RCRYZ1 Compact cassette ◌ ◌ ◌ ◌ ◌ Mini duct ◌ ◌ ◌ ◌ ◌ Slim duct ◌ ◌ ◌ ◌ ◌ Medium static pressure duct ◌ ◌ ◌ ◌...
  • Page 344 ¢ Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD Wired remote panel. Backlit LCD enables easy UTY-RNRYZ* controller operation in a dark room. Wire type: Non-polar 2-wire High visibility and easy operation. Room temperature can be accurately Wired remote controlled using the built-in thermo UTY-RLRY...
  • Page 345 Exterior Part name Model name Summary Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, Simple remote temperature setting, and operation UTY-RSNYM controller mode. Wire type: Polar 3-wire IR receiver kit Unit control is performed by wireless with wireless UTY-LBTYM remote controller.
  • Page 346 16-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-UFYF-W ¢ Part Exterior Part name Model name Summary This cassette grille can be installed Cassette grille UTG-UFYF-W appropriately on the grid type ceiling common in the office. - 338 - 16-2.
  • Page 347 16-3. Others ¢ Lineup Type Air outlet shutter Insulation kit for Fresh air intake Half concealed Indoor unit type plate high humidity UTR-YDZB UTZ-KXGC UTZ-VXAA UTR-STA Compact cassette ◌ ◌ ◌ — Mini duct — — — — Slim duct —...
  • Page 348 Type External input and output Indoor unit type External connect kit UTY-XWZX UTY-XWZXZ5 UTY-XWZXZG UTY-XCSXZ2 UTY-XCSX Compact cassette — — ◌ — ◌ Mini duct — — ◌ — — Slim duct — — ◌ — — Medium static pressure duct —...
  • Page 349 Type Indoor unit type Communication kit Air cleaning filter UTY-TWBXF2 UTY-TWRXZ2 UTY-TWRXZ3 UTR-FA16-5 Compact cassette — — — — Mini duct — — — — Slim duct — — — — Medium static pressure duct — — — — KGTB —...
  • Page 350 Type Drain pump Indoor unit type Square flange Round flange Long-life filter unit UTD-SF045T UTD-RF204 UTD-LF25NA UTZ-PX1NBA Compact cassette — — — — Mini duct — — — — Slim duct — — — — Medium static pressure duct ◌ ◌...
  • Page 351 ¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote sensor UTY-XSZX temperature of arbitrary place in the unit room. Width: 683 mm Auto louver For 07, 09, 12, and 14 models UTD-GXTA-W grille kit Width: 883 mm Auto louver UTD-GXTB-W grille kit...
  • Page 352 Exterior Part name Model name Summary Required when external device is connected. External UTY-XWZXZ5 connect kit Use to connect with various peripheral devices and air conditioner PCB. External UTY-XWZXZG connect kit For control output port. Air outlet shutter Installed at the air outlet when 3- UTR-YDZB plate directions mode is performed.
  • Page 353 Exterior Part name Model name Summary Communication Use to connect Non-polar 2-core wired UTY-TWRXZ2 remote controller. Remotely manage an air conditioning system using mobile devices such as smartphones and tablets. For connection indoor unit with UART Wireless LAN interface. UTY-TFSXZ1 adapter Appropriate application for each region is required to use this option.
  • Page 354 17. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 355 Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 30 °C RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
  • Page 356 Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 30 °C Figure 17-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
  • Page 357: Part 2. Outdoor Unit (4 Units Type)

    Part 2. OUTDOOR UNIT (4 UNITS TYPE) MULTI-SPLIT TYPE: AOYG30KBTA4...
  • Page 358: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG30KBTA4 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASYG07KMCC ×4 Rated Btu/h 27,300 Cooling 2.4—10.1 Min.—Max. Btu/h 8,200—34,500 Capacity Rated Btu/h 32,800 Heating 3.0—11.2 Min.—Max.
  • Page 359 Specifications for ErP Lot10 Model name AOYG30KBTA4 Cooling Energy efficiency class Heating (Average) Cooling 8.0 (35 °C) Pdesign Heating (Average) 6.5 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 1,978 Cooling Sound power level HIGH dB (A) Heating...
  • Page 360: Dimensions

    2. Dimensions 2-1. Model: AOYG30KBTA4 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 352 - 2-1. Model: AOYG30KBTA4 2. Dimensions...
  • Page 361: Installation Space

    3. Installation space 3-1. Model: AOYG30KBTA4 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 362  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 363  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 364: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOYG30KBTA4 Pressure switch CONDENSER - 356 - 4-1. Model: AOYG30KBTA4 4. Refrigerant circuit...
  • Page 365: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOYG30KBTA4 - 357 - 5-1. Model: AOYG30KBTA4 5. Wiring diagram...
  • Page 366: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOYG30KBTA4  Cooling Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
  • Page 367 Combination of indoor Rated capacity for each indoor unit Total capacity Input power (kW) Seasonal data unit (kW) (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.37 1.37 1.76 3.50 8.00 10.1...
  • Page 368  Heating Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class —...
  • Page 369 Rated capacity for each indoor Total capacity Combination of indoor unit Input power (kW) Seasonal data unit (kW) (kW) Room Room SCOP Energy (W/W) Pdesign Min. Rated Max. Min. Rated Max. (kWh/ efficien- Total (kW) kWh) cy class 1.54 1.96 3.05 3.05 9.60...
  • Page 370: Cooling Capacity

    6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG30KBTA4 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 371 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 372 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.94 1.97 1.99 10.1 2.01 10.8 2.03...
  • Page 373 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 1.71 1.74 1.76 1.78 1.80 10.2 1.81...
  • Page 374  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 375 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.88 5.37 3.28 5.66 3.78 6.06 4.24 6.48 4.64 6.68 5.32 -5.0 4.75...
  • Page 376  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 377 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68 5.47 -5.0 4.75...
  • Page 378  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 379 Model: ARXG18KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68 5.47 -5.0 4.75...
  • Page 380  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78...
  • Page 381 Model: ASYG07KGTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 382 Model: ASYG18KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 3.21 5.37 3.65 5.66 4.21 6.06 4.73 6.48 5.17 6.68 5.92 -5.0 4.75...
  • Page 383 Model: ASYG18KMTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 3.21 5.37 3.65 5.66 4.21 6.06 4.73 6.48 5.17 6.68 5.92 -5.0 4.75...
  • Page 384 Model: ASYG07KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 385 Model: ASYG07KMCC Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 386 Model: ASYG07KMCE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 387 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 388 Model: ASYG07KETE, ASYG07KETE-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 389  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.75 2.96 5.37 3.37 5.66 3.88 6.06 4.36 6.48 4.77 6.68...
  • Page 390  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 391: Heating Capacity

    6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG30KBTA4 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96...
  • Page 392 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 393 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.96 3.02 3.08 3.14 3.20 -10.0 -11.0 3.24 3.31 3.38 3.45 3.51 -5.0 -7.0 3.13 3.20 3.26 3.33 3.39 -2.0...
  • Page 394 NOTES: • TC: Total Capacity (kW), IP: Input Power (kW) • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit) •...
  • Page 395  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 396 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.66 4.55 4.44 4.33 4.22 -10.0 -11.0 5.80 5.67 5.53 5.39 5.25 -5.0 -7.0 6.91 6.74 6.58 6.41 6.25 -2.0 8.12 7.93 7.73 7.54 7.35 8.93 8.71...
  • Page 397  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 398 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 399  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 400 Model: ARXG18KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 401  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55...
  • Page 402 Model: ASYG07KGTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 403 Model: ASYG18KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 404 Model: ASYG18KMTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96 5.81 7.06 6.89...
  • Page 405 Model: ASYG07KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 406 Model: ASYG07KMCC Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 407 Model: ASYG07KMCE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94 2.87...
  • Page 408 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94...
  • Page 409 Model: ASYG07KETE, ASYG07KETE-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.54 1.50 1.46 1.43 1.39 -10.0 -11.0 1.91 1.87 1.82 1.78 1.73 -5.0 -7.0 2.27 2.22 2.17 2.11 2.06 -2.0 2.68 2.61 2.55 2.48 2.42 2.94...
  • Page 410  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 3.69 3.60 3.51 3.42 3.33 -10.0 -11.0 4.59 4.48 4.37 4.26 4.15 -5.0 -7.0 5.46 5.33 5.20 5.07 4.94 -2.0 6.42 6.27 6.11 5.96...
  • Page 411  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.97 1.93 1.88 1.83 1.79 -10.0 -11.0 2.46 2.40 2.34 2.28 2.22 -5.0 -7.0 2.92 2.86 2.79 2.72 2.65 -2.0 3.44 3.36 3.28 3.19...
  • Page 412: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG30KBTA4 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 413 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.992 0.985 0.971 0.957 0.943 1.003 0.996 0.989 0.975 0.961 0.947 1.007 1.000 0.993...
  • Page 414 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.992 0.982 0.970 0.952 0.937 0.999 0.996 0.986 0.974 0.956 0.941 1.005 1.000 0.990...
  • Page 415 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.992 0.994 0.994 0.984 0.968 0.993 0.996 0.998 0.998 0.988 0.972 0.997 1.000 1.002...
  • Page 416: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOYG30KBTA4 Refrigerant type Refrigerant amount 2,200 Refrigerant charge Total pipe length 40 or less 70 (Max.) 20 g/m Additional charge amount - 408 - 8-1. Model: AOYG30KBTA4 8. Additional charge calculation...
  • Page 417: Airflow

    9. Airflow 9-1. Model: AOYG30KBTA4  Cooling 2,400 1,413  Heating 2,950 1,736 - 409 - 9-1. Model: AOYG30KBTA4 9. Airflow...
  • Page 418: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOYG30KBTA4  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 419: Electrical Characteristics

    11. Electrical characteristics Model name AOYG30KBTA4 Voltage 230 ~ Power supply Frequency 18.5 Maximum operating current * Starting current Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 420: Safety Devices

    12. Safety devices Model Type of Protection form protection AOYG30KBTA4 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
  • Page 421: Function Settings

    13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 422 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 423 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 424: 13-2.Outdoor Unit Low Noise Operation Function (Option)

    13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 425: Check And Test

    14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 426 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 427 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 428 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 429 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 430 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 431: 14-2.Test Run

    14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 432: 14-3.Error Code

    Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 433 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 434 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 435: 14-4.Pump Down

    14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
  • Page 436 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 437: Accessories

    15. Accessories 15-1. Model: AOYG30KBTA4 Part name Exterior Q’ty Part name Exterior Q’ty Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Drain pipe - 429 - 15-1. Model: AOYG30KBTA4 15. Accessories...
  • Page 438: Outdoor Unit Installation Precautions

    16. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 16-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
  • Page 439: Part 3. Outdoor Unit (5 Units Type)

    Part 3. OUTDOOR UNIT (5 UNITS TYPE) MULTI-SPLIT TYPE: AOYG36KBTA5...
  • Page 440: Specifications

    1. Specifications Type Inverter heat pump Model name AOYG36KBTA5 Power source 230 V 50 Hz Available voltage range 198—264V Wall mounted Standard combination of indoor unit ASYG07KMCC ×5 Rated Btu/h 32,400 Cooling 3.0—11.0 Min.—Max. Btu/h 10,200—37,500 Capacity 10.6 Rated Btu/h 36,200 Heating 3.5—12.0...
  • Page 441 Specifications for ErP Lot10 Model name AOYG36KBTA5 Cooling Energy efficiency class Heating (Average) Cooling 9.5 (35 °C) Pdesign Heating (Average) 7.0 (-10 °C) SEER Cooling 8.50 kWh/kWh SCOP Heating (Average) 4.60 Annual energy consumption kWh/a QHE (Average) 2,130 Cooling Sound power level HIGH dB (A) Heating...
  • Page 442: Dimensions

    2. Dimensions 2-1. Model: AOYG36KBTA5 Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 434 - 2-1. Model: AOYG36KBTA5 2. Dimensions...
  • Page 443: Installation Space

    3. Installation space 3-1. Model: AOYG36KBTA5 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
  • Page 444  Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
  • Page 445  Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
  • Page 446: Refrigerant Circuit

    4. Refrigerant circuit 4-1. Model: AOYG36KBTA5 Pressure switch CONDENSER - 438 - 4-1. Model: AOYG36KBTA5 4. Refrigerant circuit...
  • Page 447: Wiring Diagram

    5. Wiring diagram 5-1. Model: AOYG36KBTA5 - 439 - 5-1. Model: AOYG36KBTA5 5. Wiring diagram...
  • Page 448: Capacity Table

    6. Capacity table 6-1. Combinations ¢ Model: AOYG36KBTA5  Cooling Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max.
  • Page 449 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class — 1.90 1.90 1.90 3.80 —...
  • Page 450 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room (W/W) Pdesign SEER Energy effi- Min. Rated Max. Min. Rated Max. Total (kW) (kWh/kWh) ciency class 1.33 1.33 1.71 1.71 3.42 9.50...
  • Page 451  Heating Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — —...
  • Page 452 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class — 1.55 1.55 2.64 4.86 —...
  • Page 453 Total capacity Combination of indoor unit Rated capacity for each indoor unit (kW) Input power (kW) Seasonal data (kW) Room Room Energy ef- (W/W) Pdesign SCOP Min. Rated Max. Min. Rated Max. ficiency Total (kW) (kWh/kWh) class 1.50 1.95 1.95 2.60 2.60 10.60...
  • Page 454: Cooling Capacity

    6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG36KBTA5 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB...
  • Page 455 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 456 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 457 Indoor temperature Indoor unit connect- Outdoor temperature 18.0 °CDB 21.0 °CDB 23.0 °CDB 27.0 °CDB 29.0 °CDB 32.0 °CDB ing capacity 12.0 °CWB 15.0 °CWB 16.0 °CWB 19.0 °CWB 21.0 °CWB 23.0 °CWB kBtu/h °CDB -10.0 2.31 2.36 10.3 2.37 11.0 2.40 11.8...
  • Page 458  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.32 2.22 1.51 2.34 1.74 2.50 1.95 2.67 2.13...
  • Page 459 Model: AUXG18KVLA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 2.94 5.48 3.35 5.78 3.86 6.19 4.33 6.62 4.74 6.82 5.43 -5.0 4.85...
  • Page 460  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 461 Model: ARXG18KSLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82 5.58 -5.0 4.85...
  • Page 462  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.36 2.22 1.55 2.34 1.78 2.50 2.00 2.67 2.19...
  • Page 463 Model: ARXG18KLLAP Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.80 2.99 5.42 3.41 5.72 3.92 6.12 4.41 6.54 4.82 6.74 5.52 -5.0 4.80...
  • Page 464  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78...
  • Page 465 Model: ASYG07KGTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 466 Model: ASYG18KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.27 5.48 3.73 5.78 4.30 6.19 4.83 6.62 5.28 6.82 6.05 -5.0 4.85...
  • Page 467 Model: ASYG18KMTE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.27 5.48 3.73 5.78 4.30 6.19 4.83 6.62 5.28 6.82 6.05 -5.0 4.85...
  • Page 468 Model: ASYG07KMTB Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 469 Model: ASYG07KMCC Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 470 Model: ASYG07KMCE Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0 1.96...
  • Page 471 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 472 Model: ASYG07KETE, ASYG07KETE-B Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 1.96 1.10 2.22 1.26 2.34 1.45 2.50 1.63 2.67 1.78 2.76 2.04 -5.0...
  • Page 473  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 4.85 3.02 5.48 3.45 5.78 3.97 6.19 4.46 6.62 4.87 6.82...
  • Page 474  Floor type Model: AGYG09KVCA Indoor temperature (°CDB / °CWB) Outdoor temperature 18.0 / 12.0 21.0 / 15.0 23.0 / 16.0 27.0 / 19.0 29.0 / 21.0 32.0 / 23.0 (°CDB) -10.0 2.51 1.71 2.84 1.95 2.99 2.25 3.20 2.53 3.42 2.76 3.53...
  • Page 475: Heating Capacity

    6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOYG36KBTA5 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88...
  • Page 476 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 477 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.88 2.94 3.00 3.06 3.12 -10.0 -11.0 3.25 3.32 3.39 3.46 3.53 -5.0 -7.0 2.93 2.99 3.05 3.11 3.17 -2.0...
  • Page 478 Indoor temperature Indoor unit connecting Outdoor temperature capacity 16.0 °CDB 18.0 °CDB 20.0 °CDB 22.0 °CDB 24.0 °CDB kBtu/h °CDB °CWB -15.0 -16.0 2.50 2.56 2.61 2.66 2.71 -10.0 -11.0 2.83 2.89 2.95 3.01 3.07 -5.0 -7.0 2.55 2.60 2.65 2.71 2.76 -2.0...
  • Page 479  Compact cassette type Model: AUXG07KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 480 Model: AUXG22KVLA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 5.55 5.41 5.28 5.15 5.02 -10.0 -11.0 6.44 6.29 6.13 5.98 5.83 -5.0 -7.0 6.80 6.64 6.48 6.31 6.15 -2.0 7.78 7.60 7.41 7.23 7.04 8.95 8.73...
  • Page 481  Mini duct type Model: ARXG07KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 482 Model: ARXG18KSLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 483  Slim duct type Model: ARXG07KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 484 Model: ARXG18KLLAP Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 485  Wall mounted type Model: ASYG07KGTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44...
  • Page 486 Model: ASYG07KGTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 487 Model: ASYG18KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 488 Model: ASYG18KMTE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73 5.58 7.09 6.92...
  • Page 489 Model: ASYG07KMTB Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 490 Model: ASYG07KMCC Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 491 Model: ASYG07KMCE Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94 2.87...
  • Page 492 Model: ASYG07KETA, ASYG07KETA-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94...
  • Page 493 Model: ASYG07KETE, ASYG07KETE-B Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 1.82 1.78 1.74 1.69 1.65 -10.0 -11.0 2.12 2.07 2.02 1.97 1.92 -5.0 -7.0 2.23 2.18 2.13 2.07 2.02 -2.0 2.56 2.50 2.44 2.38 2.31 2.94...
  • Page 494  Ceiling type Model: ABYG18KRTA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 4.39 4.29 4.19 4.08 3.98 -10.0 -11.0 5.10 4.98 4.86 4.74 4.62 -5.0 -7.0 5.39 5.26 5.13 5.00 4.87 -2.0 6.17 6.02 5.87 5.73...
  • Page 495  Floor type Model: AGYG09KVCA Indoor temperature (°CDB) Outdoor temperature 16.0 18.0 20.0 22.0 24.0 (°CDB) (°CWB) -15.0 -16.0 2.34 2.29 2.23 2.18 2.12 -10.0 -11.0 2.72 2.66 2.59 2.53 2.46 -5.0 -7.0 2.87 2.80 2.74 2.67 2.60 -2.0 3.29 3.21 3.13 3.05...
  • Page 496: Capacity Compensation Rate For Pipe Length And Height Difference

    7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOYG36KBTA5 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
  • Page 497 ¢ Indoor unit: 9,000 Btu/h Pipe length Cooling — — — 0.956 0.942 0.928 — — 0.977 0.963 0.950 0.936 Indoor unit is higher than outdoor unit *1 — 0.992 0.985 0.971 0.957 0.943 0.996 0.996 0.989 0.975 0.961 0.947 1.000 1.000 0.993...
  • Page 498 ¢ Indoor unit: 14,000 Btu/h Pipe length Cooling — — — 0.955 0.937 0.922 — — 0.974 0.962 0.945 0.930 Indoor unit is higher than outdoor unit *1 — 0.992 0.982 0.970 0.952 0.937 0.996 0.996 0.986 0.974 0.956 0.941 1.000 1.000 0.990...
  • Page 499 ¢ Indoor unit: 22,000 Btu/h Pipe length Cooling — — — 0.978 0.969 0.953 — — 0.986 0.986 0.977 0.961 Indoor unit is higher than outdoor unit *1 — 0.992 0.994 0.994 0.984 0.968 0.996 0.996 0.998 0.998 0.988 0.972 1.000 1.000 1.002...
  • Page 500: Additional Charge Calculation

    8. Additional charge calculation 8-1. Model: AOYG36KBTA5 Refrigerant type Refrigerant amount 2,500 Refrigerant charge Total pipe length 40 or less 75 (Max.) 20 g/m Additional charge amount - 492 - 8-1. Model: AOYG36KBTA5 8. Additional charge calculation...
  • Page 501: Airflow

    9. Airflow 9-1. Model: AOYG36KBTA5  Cooling 2,450 1,501  Heating 2,900 1,766 - 493 - 9-1. Model: AOYG36KBTA5 9. Airflow...
  • Page 502: Operation Noise (Sound Pressure)

    10. Operation noise (sound pressure) 10-1. Noise level curve ¢ Model: AOYG36KBTA5  Cooling  Heating NC-65 NC-65 NC-60 NC-60 NC-55 NC-55 NC-50 NC-50 NC-45 NC-45 NC-40 NC-40 NC-35 NC-35 NC-30 NC-30 NC-25 NC-25 NC-20 NC-20 NC-15 NC-15 1,000 2,000 4,000 8,000 1,000...
  • Page 503: Electrical Characteristics

    11. Electrical characteristics Model name AOYG36KBTA5 Voltage 230 ~ Power supply Frequency 20.0 Maximum operating current * Starting current 11.1 Main fuse (Circuit breaker) current Power cable Wiring spec. * Connection Cross-sectional area cable * Limited wiring length : Maximum operating current is the total current of the indoor unit and the outdoor unit. : Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
  • Page 504: Safety Devices

    12. Safety devices Model Type of Protection form protection AOYG36KBTA5 250 V, 5 A Current fuse Circuit protection 250 V, 20 A (Main PCB) 250 V, 3.15 A 125 ±10 °C Activate Fan motor stop Fan motor Thermal protector protection 120 ±10 °C Reset Fan motor restart...
  • Page 505: Function Settings

    13. Function settings 13-1. Setting methods WARNING Never touch electrical components such as the terminal blocks or reactor except the switch on the display board. It may cause a serious accident such as electric shock. CAUTION • Once refrigerant charging is completed, be sure to open the valve prior to performing the local settings.
  • Page 506 ¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
  • Page 507 ¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
  • Page 508: 13-2.Outdoor Unit Low Noise Operation Function (Option)

    13-2. Outdoor unit low noise operation function (option) Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- NOTES: •...
  • Page 509: Check And Test

    14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
  • Page 510 ¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
  • Page 511 After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
  • Page 512 [How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
  • Page 513 c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
  • Page 514 ¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
  • Page 515: 14-2.Test Run

    14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
  • Page 516: 14-3.Error Code

    Push TEST RUN switch for more than 3 seconds. POWER MONITOR ERROR /MODE ( GRN ) ( RED ) POWER/MODE LED will turn on, and test run stops. 14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed.
  • Page 517 ¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
  • Page 518 Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
  • Page 519: 14-4.Pump Down

    14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant piping. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury.
  • Page 520 7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
  • Page 521: Accessories

    15. Accessories 15-1. Model: AOYG36KBTA5 Part name Exterior Q’ty Part name Exterior Q’ty Adapter K: mm (in) Installation manual 12.70 (1/2) to 9.52 (3/8) Adapter H: mm (in) Drain pipe 9.52 (3/8) to 12.70 (1/2) Cable tie (small) - 513 - 15-1.
  • Page 522: Optional Parts

    16. Optional parts Exterior Part name Model name Summary Set temperatures on timers to best meet individuals’ needs. Includes a large backlit LCD and 4-way navigation pad. Remote controller cable: 0.33 mm² (22AWG) NOTES: • The remote controller cable supplied with this controller is for indoor use.
  • Page 523: Outdoor Unit Installation Precautions

    17. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 17-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.

Table of Contents