Compressor Frequency At Normal Start-Up - Fujitsu ARXG45KMLA Service Manual

Hide thumbs Also See for ARXG45KMLA:
Table of Contents

Advertisement

1-4. Compressor frequency at normal start-up

¢ Model: AOYG36KRTA
Compressor frequency soon after starting is controlled as below.
Frequency VIII
Frequency VII
Frequency VI
Frequency V
Frequency IV
Frequency III
Frequency II
Frequency I
• Normal operation
I
Frequency
(rps)
25
1
Time (sec)
90
• Special operation
I
Frequency
(rps)
25
1
Time (sec)
225
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– →hen the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
Time 1
Time 2
Time 3
II
III
42
53
2
3
150
270
II
III
42
53
2
3
305
605
- (04-3) -
Time 4
Time 5
Time 6
IV
V
VI
61
65
75
4
5
6
330
390
450
IV
V
VI
61
65
75
4
5
6
665
725
785
Time 7
Time 8
VII
VIII
85
92
7
8
570
630
VII
VIII
85
92
7
8
855
1,000
1. Compressor frequency control