¢ Discharge temperature thermistor
Temperature (°C)
-30.0
-25.0
-20.0
-15.0
-10.0
-5.0
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
110.0
115.0
120.0
5-2. Outdoor unit
Resistance (kΩ)
1,013.11
729.09
531.56
392.31
292.91
221.09
168.60
129.84
100.91
79.12
62.55
49.84
40.01
32.35
26.34
21.58
17.79
14.75
12.30
10.32
8.70
7.36
6.27
5.36
4.60
3.96
3.43
2.98
2.60
2.27
2.00
- (03-60) -
Voltage (V)
0.06
0.09
0.12
0.16
0.21
0.28
0.36
0.46
0.57
0.71
0.86
1.03
1.23
1.43
1.65
1.88
2.11
2.34
2.57
2.79
3.00
3.19
3.37
3.54
3.69
3.83
3.96
4.07
4.17
4.26
4.33
5. Thermistor resistance values