Fujitsu AO G22KBTB Series Service Manual
Fujitsu AO G22KBTB Series Service Manual

Fujitsu AO G22KBTB Series Service Manual

Split type room air conditioner
Hide thumbs Also See for AO G22KBTB Series:

Advertisement

Quick Links

SERVICE
INSTRUCTION
SPLIT TYPE
ROOM AIR CONDITIONER
DUCT
INVERTER
Models Indoor unit
ARXG22KMLA
RDG22KMLA
type
Outdoor unit
AO*G22KBTB
ROG22KBTB

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AO G22KBTB Series

  • Page 1 SPLIT TYPE ROOM AIR CONDITIONER DUCT type INVERTER SERVICE INSTRUCTION Models Indoor unit Outdoor unit AO*G22KBTB ARXG22KMLA RDG22KMLA ROG22KBTB...
  • Page 2: Control And Functions

    1. CONTROL AND FUNCTIONS 2019.10.17 SR_CH04_AR003EF_01...
  • Page 3: Table Of Contents

    CONTENTS 1. CONTROL AND FUNCTIONS 1. Compressor frequency control..............01-1 1-1. Cooling operation ......................01-1 1-2. Heating operation ......................01-2 1-3. Dry operation ........................01-3 1-4. Compressor frequency at normal start-up ..............01-4 2. Auto changeover operation................01-5 3. Fan control....................01-7 3-1. Indoor fan control......................01-7 3-2. Outdoor fan control......................01-9 4.
  • Page 4: Compressor Frequency Control

    1. Compressor frequency control 1-1. Cooling operation A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation frequency of the compressor. •...
  • Page 5: Heating Operation

    1-2. Heating operation A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or variation between setting temperature and present room temperature, and controls operation fre- quency of compressor. • If the room temperature is 6.0 °C lower than a set temperature, the compressor operation frequen- cy will attain to maximum performance.
  • Page 6: Dry Operation

    1-3. Dry operation The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the table below. Zone is defined by set temperature and room temperature. •...
  • Page 7: Compressor Frequency At Normal Start-Up

    1-4. Compressor frequency at normal start-up ¢ Model: AOYG22KBTB Compressor frequency soon after starting is controlled as below. Frequency VI Frequency V Frequency IV Frequency III Frequency II Frequency I Time 1 Time 2 Time 3 Time 4 Time 5 Time 6 Frequency (rps)
  • Page 8: Auto Changeover Operation

    2. Auto changeover operation When the air conditioner is set to AUTO mode by remote controller, operation starts in the optimum mode from among heating, cooling, dry and monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set be- tween 18°C and 30°C in 1.0°C steps.
  • Page 9 Operation flow chart Start Ts: Setting temperarure Monitor mode Room temp. > Ts+2°C? Room temp. < Ts-2°C? Middle zone Auto change over is second or more? Operation mode before the monitor mode is cooling mode? Operation mode of Heating operation Cooling operation outdoor unit: Cooling? Thermostat remains...
  • Page 10: Fan Control

    3. Fan control Tr: Room temperature Ts: Setting temperature 3-1. Indoor fan control ¢ Fan speed Indoor fan speed is defined as below. Speed (rpm) Operation mode Fan mode ARXG22KMLA HIGH Heating QUIET S-LOW HIGH Cooling/ Fan QUIET Soft quiet 350* S-LOW 350*...
  • Page 11 ¢ Heating operation Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be- low. On the other hand, if switched in HIGH—QUIET, the indoor motor will run at a constant airflow of HEAT operation modes QUIET, LOW, MED, HIGH as shown in “Fan speed”...
  • Page 12: Outdoor Fan Control

    3-2. Outdoor fan control ¢ Outdoor fan motor This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.) ¢ Fan speed  Model: AOYG22KBTB Fan speed is defined by outdoor temperature and compressor frequency. •...
  • Page 13: Timer Operation Control

    4. Timer operation control 4-1. Wireless remote control On/Off timer Program timer Sleep timer Weekly timer ○ ○ ○ ○ ¢ On/Off timer • Off timer: When the clock reaches the set timer, the air conditioner will be turned off. Operation mode Stop mode Set time of timer...
  • Page 14 ¢ Sleep timer If the sleep timer is set, the room temperature is monitored and the operation is stopped auto- matically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time on. •...
  • Page 15: Wired Remote Control

    4-2. Wired remote control Temperature set On/Off timer Program timer Sleep timer Weekly timer back timer ○ ○ ○ ○ ○ ¢ On/Off timer • Off timer: When the clock reaches the set timer, the air conditioner will be turned off. Operation mode Stop mode Set time of timer...
  • Page 16 ¢ Sleep timer If the sleep timer is set, the room temperature is monitored and the operation is stopped auto- matically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time on. •...
  • Page 17 ¢ Temperature set back timer • The SET BACK timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation. • The SET BACK timer can be set to operate up to two times per day but only one temperature setting can be used.
  • Page 18: Defrost Operation Control

    5. Defrost operation control Tn: outdoor unit heat exchanger temperature Ta: Outdoor temperature Tn10: Temperature at 10 minutes after compressor start Tnb: Temperature before 5 minutes Triggering condition • The defrost operation starts when outdoor unit heat exchanger temperature sensor detects the temperature lower than the values shown below.
  • Page 19: Defrost Operation In Heating Operation Stopped

    5-1. Defrost operation in heating operation stopped If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto- matic defrosting operation. In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al- low the heat exchanger to defrost, and then stop.
  • Page 20: Various Control

    6. Various control 6-1. Auto restart When the power was interrupted by a power failure etc. during operation, the operation contents at that time are memorized and when the power is recovered, operation is automatically started with the memorized operation contents. Operation contents memorized when the power is interrupted Operation mode Setting temperature...
  • Page 21: Forced Cooling Operation

    6-3. Forced cooling operation The outdoor unit may not operate depending on the room temperature. When FORCED COOLING OPERATION button is pressed more than 10 seconds, forced cooling operation starts as shown in the table below. Operation mode Cooling Fan mode HIGH Timer mode Continuous (no timer setting available)
  • Page 22: Compressor Preheating

    6-6. Compressor preheating By preheating the compressor, warm airflow is quickly discharged when the operation is started. • Triggering condition – 30 minutes after compressor stopped. – Outdoor unit heat exchanger temperature (Tn) -4°C -2°C When the jumper wire (JM2) is disconnected: 7°C 5°C 6-7.
  • Page 23: Drain Pump Control

    6-9. Drain pump control ¢ Drain control for cooling operation  During the compressor in operation • Triggering condition The thermostat is turned on during cooling or dry mode. • Operation details The drain pump is turned on. • Release condition –...
  • Page 24  Overflow control • Triggering condition The float switch is turned on. • Operation details – The drain pump is turned on. – When the operation mode is cooling or dry, operate the followings. • The compressor is stopped. • Then indoor fan control is turned off. •...
  • Page 25 ¢ Drain control for dehumidification operation  During cooling or dry mode • When the compressor starts, the drain pump starts simultaneously. • The drain pump operates continuously for 3 minutes after the compressor is turned off. Compressor Drain pump 3 minutes •...
  • Page 26: Prevention To Restart For 3 Minutes (3 Minutes St)

     During heating mode or fan mode and when operation is stopped • Triggering condition Drain pump is turned on at the same time that the float switch is turned on. • Operation details When the float switch turns on continuously for 3 minutes, "failure indication" operates. There- after, even if the float switch turns off, the "failure indication"...
  • Page 27: Outdoor Unit Low Noise Operation

    6-12. Outdoor unit low noise operation The outdoor unit low noise operation functions by OUTDOOR UNIT LOW NOISE button on the re- mote controller. This operation stops the PFC control, and changes the current value. Current Operation mode Trigger condition Release condition Cooling/Dry mode 7.0 A...
  • Page 28: Various Protections

    7. Various protections 7-1. Discharge gas temperature over-rise prevention control The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis- charge gas temperature. • When the discharge temperature becomes higher than the trigger condition, the compressor fre- quency is decreased as the table below, and it continues to decrease until the discharge tempera- ture becomes lower than the trigger condition.
  • Page 29: Current Release Control

    7-3. Current release control The compressor frequency is controlled so that the outdoor unit input current does not exceeds cur- rent limit value set according to the outdoor temperature. The compressor frequency returns according to the operation mode, when the current becomes low- er than the release value.
  • Page 30: High Temperature And High Pressure Release Control (Heating Mode)

    7-6. High temperature and high pressure release control (heating mode) In heating mode, the compressor is controlled as follows. ¢ Model: AOYG22KBTB Indoor unit heat exchanger Indoor unit heat exchanger temperature rises temperature drops 61°C Zone A 55°C 53°C Zone B 50°C Zone C Zone D...
  • Page 31 DUCT type INVERTER 2 . TROUBLE SHOOTING...
  • Page 32 2 ERROR DISPLAY 2-1 WIRED REMOTE CONTROLLER DISPLAY (OPTION) 1. Check the error 1. If an error occurs, an error icon appears on the “Monitor mode screen”. Touch the [Status] on the “Monitor mode screen”.The “Status” screen is displayed. 2. Touch the [Error Information] on the “Status”screen. The “Error Information”screen is displayed. (If there are no errors, the [Error Information] will not be displayed.) 3.
  • Page 33 2-2 TROUBLE SHOOTING WITH ERROR CODE Indicate or Display: Trouble shooting 1 OUTDOOR UNIT Error Method: Error code : 11 Outdoor unit : No indication Serial communication error (Serial Reverse Transfer Error) Detective details: Detective Actuators: When the indoor unit cannot receive the serial signal from Outdoor unit Outdoor unit Main PCB more than 2minutes after power ON, or the indoor unit cannot receive Outdoor unit fan motor...
  • Page 34 Indicate or Display: Trouble shooting 2 INDOOR UNIT Error Method: Error code : 11 Outdoor unit : No indication Serial communication error (Serial Forward Transfer Error) Detective details: Detective Actuators: When the outdoor unit cannot properly receive the serial signal from Indoor unit Controller PCB indoor unit for 10 seconds or more.
  • Page 35 Indicate or Display: Trouble shooting 3 INDOOR UNIT Error Method: Error code : 12 Outdoor unit : No indication Wired Remote Controller Communication Error Detective details: Detective Actuators: When the outdoor unit cannot properly receive the serial signal from Indoor unit Controller PCB indoor unit for 10 seconds or more.
  • Page 36 Indicate or Display: Trouble shooting 4 INDOOR UNIT Error Method: Outdoor unit : No indication Error code : 15 Automatic Air flow Adjustment Error Detective Actuators: Detective details: Indoor unit controller PCB On automatic airflow adjustment operation, when the fan speed other than 0rpm is detected at the 0rpm operation.
  • Page 37 Indicate or Display: Trouble shooting 5 INDOOR UNIT Error Method: Outdoor unit : No indication Error code : 18 External communication error Detective Actuators: Detective details: After receiving a signal from the external I/O PCB, External communication error the same a signal has not been received for 15sec Forecast of Cause : 1.
  • Page 38 Trouble shooting 6 Indicate or Display: INDOOR UNIT Error Method: Outdoor unit : No indication Error code : 23 Combination error Detective Actuators: Detective details: 1. The outdoor unit receives the serial signal of applied refrigerant Indoor unit information from Indoor unit. When the refrigerant is R410a. 2.
  • Page 39 Trouble shooting 7 Indicate or Display: INDOOR UNIT Error Method: Outdoor unit : No indication Error code : 26 Indoor unit address setting error Detective Actuators: Detective details: When the address number set by auto setting and manual setting are Wired remote controller ( 2-Wire ) mixed in one RC group.
  • Page 40 Trouble shooting 8 Indicate or Display: INDOOR UNIT Error Method: Connection unit number error (Indoor Outdoor unit : No indication Error code : 29 unit in Wired remote controller system) Detective Actuators: Detective details: Wired remote controller ( 2-Wire ) When the number of connecting indoor units are out of specified rule.
  • Page 41 Trouble shooting 9 Indicate or Display: INDOOR UNIT Error Method: Error code : 32 Outdoor unit : No indication Indoor unit PCB model information error Detective Actuators: Detective details: When power is on and there is some below case. Indoor unit Controller PCB 1.
  • Page 42 Trouble shooting 10 Indicate or Display: INDOOR UNIT Error Method: Error code : 33 Outdoor unit : No indication Indoor unit motor electricity consumption detection error Detective Actuators: Detective details: Indoor unit fan motor When the voltage value or the current value of the motor go beyond the limits. Indoor unit Controller PCB circuit Forecast of Cause: 1.
  • Page 43 Trouble shooting 11 Indicate or Display: INDOOR UNIT Error Method: Error code : 39 Outdoor unit : No indication Indoor unit power supply error for fan motor Detective Actuators: Detective details: Indoor unit Power Supply PCB When a momentary power cut off. When do not start fan motor.
  • Page 44 Trouble shooting 12 Indicate or Display: INDOOR UNIT Error Method: Indoor unit Communication circuit Outdoor unit : No indication Error code : 3A (wired remote controller) error Detective Actuators: Detective details: Indoor unit Controller PCB circuit Detect the communication error of microcomputer and communication PCB. Forecast of Cause : 1.Communication PCB defective 2.
  • Page 45 Trouble shooting 13 Indicate or Display: INDOOR UNIT Error Method: Error code : 41 Outdoor unit : No indication Indoor Room Thermistor Error Detective details: Detective Actuators: Indoor unit Controller PCB Circuit Indoor unit thermistor is open or short is detected always. Indoor Temperature Thermistor Forecast of Cause : 1.
  • Page 46 Trouble shooting 14 Indicate or Display: INDOOR UNIT Error Method: Error code : 42 Outdoor unit : No indication Indoor Heat Ex. Thermistor Error Detective details: Detective Actuators: Indoor unit Controller PCB Circuit Indoor unit thermistor is open or short is detected always. Heat Exchanger (MID) Thermistor Forecast of Cause : 1.
  • Page 47 Trouble shooting 15 Indicate or Display: INDOOR UNIT Error Method: Error code : 51 Outdoor unit : No indication Indoor Unit Fan Motor Error Detective Actuators: Detective details: Indoor unit Power Supply PCB When the fan motor speed is less than 1/3 of the target fan speed for 56 seconds.
  • Page 48 Indicate or Display: Trouble shooting 16 INDOOR UNIT Error Method: Error code : 53 Outdoor unit : No indication Drain Pump Error Detective details: Detective Actuators: Indoor unit Controller PCB Circuit When Float switch is ON for more than 3 minutes. Float switch Forecast of Cause : 1.
  • Page 49 Trouble shooting 17 Indicate or Display: OUTDOOR UNIT Error Method: Outdoor unit main PCB model Outdoor unit : No indication Error code : 62 information error Detective Actuators: Detective details: Access to EEPROM failed due to some cause after outdoor unit started. Outdoor unit Main PCB Forecast of Cause: 1.
  • Page 50 Trouble shooting 18 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 63 Outdoor unit : No indication Inverter error Detective Actuators: Detective details: Outdoor unit Main PCB Error information received from Outdoor unit Main PCB Forecast of Cause : 1.
  • Page 51 Indicate or Display: Trouble shooting 19 OUTDOOR UNIT Error Method: Outdoor unit : No indication Error code : 64 PFC circuit error Detective Actuators: Detective details: When inverter output DC voltage is higher than 420V for over 3 seconds, Outdoor unit Main PCB the compressor stops.
  • Page 52 Trouble shooting 20 Indicate or Display: OUTDOOR UNIT Error Method: Outdoor unit : No indication Error code : 65 Trip terminal L error Detective Actuators: Detective details: Outdoor unit Main PCB When the signal from FO terminal of IPM is "L"(=0V) while the compressor stops.
  • Page 53 Trouble shooting 21 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 71 Outdoor unit : No indication Discharge Thermistor Error Detective Actuators: Detective details: Discharge temperature thermistor Discharge temperature thermistor short or open detected Forecast of Cause : 1.
  • Page 54 Trouble shooting 22 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 72 Outdoor unit : No indication Compressor Temp. Thermistor Error Detective Actuators: Detective details: Compressor temperature thermistor Compressor temperature thermistor short or open detected Forecast of Cause : 1.
  • Page 55 Trouble shooting 23 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 73 Outdoor unit : No indication Heat Ex. Outlet / Middle Temp. Thermistor Error Detective Actuators: Detective details: Heat exchanger Outlet / Middle temperature Heat exchanger outlet temperature thermistor short or open detected thermistor Heat exchanger middle temperature thermistor short or open detected Forecast of Cause :...
  • Page 56 Trouble shooting 24 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 74 Outdoor unit : No indication Outdoor Thermistor Error Detective Actuators: Detective details: Outdoor temperature thermistor Outdoor temperature thermistor short or open detected Forecast of Cause : 1.
  • Page 57 Trouble shooting 26 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 84 Outdoor unit : No indication Current sensor error Detective Actuators: Detective details: When Input Current Sensor has detected 0A, while Inverter Compressor is Outdoor unit Main PCB operating at higher than 56rps, after 1minute upon starting the Compressor.
  • Page 58 Trouble shooting 28 Indicate or Display: OUTDOOR UNIT Error Method: Error code : 94 Outdoor unit : No indication Trip detection Detective details: Detective Actuators: "Protection stop by overcurrent generation after inverter compressor start Outdoor unit Main PCB processing completed'' generated consecutively 10 times. Compressor *The number of generations is reset if the start-up of the compressor succeeds.
  • Page 59 Trouble shooting 29 Indicate or Display: OUTDOOR UNIT Error Method: Compressor rotor position Outdoor unit : No indication Error code : 95 detection error Detective details: Detective Actuators: Outdoor unit Main PCB "Protection stop by "overcurrent generation at inverter compressor starting" Compressor restart"...
  • Page 60 Indicate or Display: Trouble shooting 30 OUTDOOR UNIT Error Method: Error code : 97 Outdoor unit : No indication Outdoor Unit Fan Motor Error Detective Actuators: Detective details: When outdoor fan rotation speed is less than 100rpm in 20 seconds Outdoor unit Main PCB after fan motor starts, fan motor stops.
  • Page 61 Indicate or Display: Trouble shooting 31 OUTDOOR UNIT Error Method: Error code : 99 Outdoor unit : No indication 4-Way Valve Error Detective Actuators: Detective details: When the indoor heat exchanger temperature is compared with Indoor Unit Controller PCB Circuit the room temperature, and either following condition is detected Heat Exchanger Temperature Thermistor continuously two times, the compressor stops.
  • Page 62 Trouble shooting 32 Indicate or Display: OUTDOOR UNIT Error Method: Error code : A1 Outdoor unit : No indication Discharge Temp. Error Detective Actuators: Detective details: °C "Protection stop by "discharge temperature during compressor Discharge temperature thermistor operation'''' generated 2 times within 24 hours. Forecast of Cause : 1.
  • Page 63 2-3 TROUBLESHOOTING WITH NO ERROR CODE Forecast of Cause: Trouble shooting 34 1. Power Supply failure 2. External cause Indoor Unit - No Power 3. Electrical Components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable. >>If abnormal condition is found, correct it by referring to Installation Manual or Data &...
  • Page 64 Forecast of Cause: Trouble shooting 35 1.Power Supply failure 2. External cause Outdoor unit - No Power 3.Electrical Components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable. >>If abnormal condition is found, correct it by referring to Installation Manual or Data &...
  • Page 65 Trouble shooting 36 Forecast of Cause: 1. Setting/ Connection failure 2. External cause No Operation (Power is ON) 3. Electrical Component defective Check Point 1 : Check indoor and outdoor installation condition Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection.
  • Page 66 Forecast of Cause: Trouble shooting 37 1. Indoor Unit error 2. Outdoor Unit error No Cooling / No Heating 3. Effect by Surrounding environment 4. Connection Pipe / Connection Wire failure 5. Refrigeration cycle failure Check Point 1 : Check Indoor Unit Does Indoor unit FAN run on HIGH FAN? Is Air Filter dirty? Is Heat Exchanger clogged?
  • Page 67 Forecast of Cause : Trouble shooting 38 1. Abnormal installation (Indoor/ Outdoor) 2. Fan failure (Indoor/ Outdoor) Abnormal Noise 3. Compressor failure (Outdoor) Diagnosis method when Abnormal Noise is occurred Abnormal noise is coming from Indoor Unit. Abnormal noise is coming from Outdoor Unit. (Check and correct followings) (Check and correct followings) Is Main Unit installed in stable condition?
  • Page 68 2-4 SERVICE PARTS INFORMATION SERVICE PARTS INFORMATION 1 Compressor Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting ) Abnormal noise Stops soon after starting up Does not start up Is there open or loose connection Check if vibration noise by Is there open or loose connection cable?
  • Page 69 SERVICE PARTS INFORMATION 2 Inverter Compressor Check Point 1 : Check Connection Check terminal connection of Compressor (loose or incorrect wiring) Terminal cover opened Main PCB W(C) U(R) (BLACK) (RED) W400 W401 W402 V(S) (WHITE) BLACK WHITE Compressor Check Point 2 : Check Winding Resistance Check winding resistance of each terminal If the resistance value is 0 or infinite, replace Compressor.
  • Page 70 SERVICE PARTS INFORMATION 3 Outdoor unit Electronic Expansion Valve ( EEV ) Check Point 1 : Check Connections Check connection of connector ( Loose connector or open cable ) EXPANSION VALVE COIL BLUE ORANGE YELLOW WHITE Check Point 2 : Check Coil of EEV Check Point 3 : Check Noise at start up Remove connector, check each winding Turn on Power and check operation noise.
  • Page 71 SERVICE PARTS INFORMATION 4 Indoor unit fan motor Check Point 1 : Check rotation of Fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) >>If Fan or Bearing is abnormal, replace it. Check Point 2 : Check resistance of Indoor unit Fan Motor Refer to below.
  • Page 72 SERVICE PARTS INFORMATION 8 Thermistor Check Point : Check Thermistor resistance value Remove connector and check Thermistor resistance value. Resistance Value [ k ] Temperature [°C] Thermistor A Thermistor B Thermistor C 1013.1 95.6 224.3 531.6 50.3 115.2 292.9 27.8 62.3 168.6 16.1...
  • Page 73 3-3-17,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan Aug. 2019 Printed in Japan...