13) Apply mains power. Check green Mains LED is on.
14) Check there is no fault indication on Red LED.
15) Disconnect mains power. Check that the batteries continue to supply voltage and
current to the load. The Green LED should be off.
NOTE: Batteries must have sufficient charge to supply the load
16) Reconnect mains power. Green LED should be on.
Tamper
17) Check that the tamper screw makes good contact with the mounting surface.
Check that the tamper switch is:
closed when the lid is closed, and the lid screw is fitted
open when the lid is open.
18) Close cover and secure using fastening screw(s) provided.
O
I
PERATING
NSTRUCTIONS
This unit is intended for use by Service Personnel only. There are NO USER
SERVICEABLE parts inside.
The green Mains LED will be illuminated whilst the mains supply is present. In the
event of a fault condition the red Fault LED will flash and the corresponding (EPS or
GEN) fault signal contacts will open.
P
M
REVENTATIVE
This unit is intended for use by Service Personnel only. There are NO USER
SERVICEABLE parts inside.
There is no regular maintenance required of the PSU other than periodic testing,
calibration check and replacement of the standby batteries. Reference should be
made to the battery manufacturer's documentation to determine typical/expected
battery life with a view to periodic replacement of the battery.
Dispose of used batteries according to the battery manufacturer's
instructions and all local and national regulations.