Maintenance - Honeywell HP600ULM Manual

Access control power supply/charger with power distribution controller

Advertisement

5 Battery Stand-By Mode Specification Chart
Output Battery
Capacity
17Ah-12V
55Ah-12V
17Ah-24V
55Ah-24V
UL Listing

6 Maintenance

This unit should be tested at least once a year to verify correct operation in accordance with the following
recommendations;
Output Voltage Test - Voltage output should be tested under normal load conditions to verify correct levels.
Battery Test - Battery should be checked for full charge under normal load conditions. This check should verify correct
voltage at both battery terminals and also at the Battery output point on the board to ensure the integrity of all connecting
wiring. It is recommended to replace the battery at least every 4 years.
LED Test (Distribution Board only) - Verify yellow LED operation by pushing LED test button. All yellow LED's
should illuminate.
WARNING: To reduce risk of electric shock, do not expose unit to rain or excess moisture, and disconnect
!
power before servicing unit.
For continuous protection against hazard, replace fuses only with exact type and rating. A readily accessible
switched circuit breaker must be available to disconnect main power as required. All 120V wiring should be routed
so that it cannot touch 24V wiring; minimum spacing 3/8" (0.953cm). Installation and servicing should only be
made by qualified personnel; contains no user-serviceable parts. Install in accordance with all local regulations
and the National Electrical Code.
4
4Hr Stand-By
STBY/ALRM
15Mins/ALRM
STBY
2.00A
ALRM
6.00A
STBY
6.00A
ALRM
6.00A
STBY
2.00A
ALRM
6.00A
STBY
6.00A
ALRM
6.00A
UL294
UL603
24Hr Stand-By
60Hr Stand-By
15Mins/ALRM
5Mins/ALRM
200mA
6.00A
1.50A
300mA
6.00A
200mA
300mA
6.00A
1.50A
300mA
6.00A
UL294
UL603
UL1481
UL1481
Continued on next page...
HP600ULM Installation Document P/N 52393:A 1/05/06
N/A
N/A
6.00A
6.00A
6.00A