22 or 24 guage
AT&T P7 Cable
Figure 3. Daisy-Chained Total Access 3000/3010 Shelves
1.4.2

Alarm Input and Outputs

For alarms, the physical wiring will depend on which alarming equipment is used.
ADTRAN recommends referring to the Alarm Equipment manufacturer's instructions
for alarm wiring.
The shelf currently supports six dedicated alarm outputs and two spare alarm outputs.
The dedicated outputs are Critical Visual (CRI-V), Major Visual (MAJ-V), Minor
Visual (MIN-V), Critical Audible (CRI-A), Major Audible (MAJ-A), and Minor
Audible (MIN-A). Each alarm supports Normally Open or Normally Closed relay
contacts.
Four alarm inputs are supported. They are ACO, Remote, AUX 1, and AUX 2. The
active alarm state is -48 V or contact closure.
Alarm relays are supported by all versions of the SCU and no additional ADTRAN
equipment needs to be provided to utilize the alarming features.
®
Total Access
3000/3010 System Manual
TOTAL ACCESS 3000/3010
RS485
A
B
A
B
Shelf 32
IN
OUT
RS485
A
B
A
B
Shelf 2
IN
OUT
RS485
A
B
A
B
Shelf 1
IN
OUT
6TAENG201-1E
ENG-201
Page 17 of 32
© 2002, ADTRAN, Inc.