Clearance To Combustibles, Masonry & Zero Clearance; Minimum Opening For Masonry And Factory-Built Fireplace; Floor Protection; Prefabricated Metal Chimney - Quadra-Fire CASTILE Owner's Manual Installation And Operation

Pellet insert
Table of Contents

Advertisement

R
B. Masonry and Factory-Built Fireplaces *
(Shown on a CASTILE INSERT)
Maximum Mantel Depth: 12 inches (305mm)
B
A
F
Figure 22.1
A
Insert side to combustible side wall
B
Insert top to mantel
C
Insert top to maximum. 2-1/4 inch
(57mm) face trim
D
Insert side to maximum. 2-1/4 inch
(57mm) face trim
* the Castile and Santa Fe inserts are only intended
for installation into a masonry or factory built fire-
place
C. Minimum Opening for Masonry and
Factory-Built Fireplaces
B
Figure 22.2
Location
A
Rear Width
B
Depth
C
Height
D
Front Width
October 27, 2011
Face
Mantel
Trim
C
D
E
Inches
Millimeters
16
12
4-3/4
10
C
A
D
Millimeters (Castile/Santa Fe)
600/ 610
432/ 406
540/ 591
714/ 743
D. Floor Protection
E
Floor protection hearth extension from
door opening
F
Floor protection to the side of door
opening
E. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
• M ust be minimum 152mm inside diameter of high
temperature chimney listed to UL 103 HT (2100
• M ust use components required by the manufacturer for
installation.
• M ust maintain clearances required by the manufacturer
for installation.
• R efer to manufacturers instructions for installation
•This insert is listed to UL 1482 Standard and is approved
for installation into listed factory-built zero clearance fire-
406
places listed to UL 127 conforming to the following speci-
305
fications and instructions:
121
•The original factory-built clearance fireplace chimney
cap must be re-installed after installing the approved
254
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
•If the chimney is not listed as meeting HT requirements,
or if the factory built fireplace was tested prior to 1998, a
full height listed chimney liner must be installed from the
appliance flue collar to the chimney top.
•The liner must be securely attached to the insert flue collar
and the chimney top.
•The air flow of the factory-built zero-clearance fireplace
system must not be altered. The flue liner top support
attachment must not reduce the air flow for the existing
air-cooled chimney system.
•No dilution air is allowed to enter the chimney.
1. Secure the fireplace damper in the open position. If
this cannot be accomplished, it will be necessary to
remove the damper.t
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the fireplace.
3. Both methods must be removable and replaceable
for cleaning and re-installation.
7069-101B
Castile & Santa Fe CE Insert
Inches
6
6
Millimeters
152
152
o
F).
Page 21