4. MR-MT2010 SSCNET III/H HEAD MODULE

4. MR-MT2010 SSCNET III/H HEAD MODULE
4.1 Summary
The MR-MT2010 SSCNET III/H head module is used for SSCNET III/H communications.
This module is necessary to use a sensing module. Connect extension modules to this module. This module
can be used alone because it has digital I/Os.

4.2 Standard specifications

Voltage
Control circuit
Permissible voltage fluctuation
power supply
Current capacity
Communication interface
Number of input points
Insulation method
On voltage/on current
Off voltage/off current
DI
Input response time
Timing latch input
Input form
Number of output points
Maximum load current
Insulation method
DO
Output response time
(Note 3)
Output form
Interface power supply
Compliance to global standards
Structure (IP rating)
Environment
Mass
Note 1. This is the maximum value of when four extension modules are connected to a head module. The current capacity can be
decreased by reducing the number of connected extension modules.
2. The number of the points will be four points when extension modules are connected.
3. This value is applicable when the output current is 50 mA or more.

4.3 Function list

The following table lists the functions of the MR-MT2010 SSCNET III/H head module. For details and usage
of the functions, refer to the manuals for controllers.
Function
Digital input function
Digital output function
Timing-latch input function
Level output function
Output CLEAR/HOLD function
Item
Off → On
On → Off
Number of
simultaneously
used points
Off → On
On → Off
This function sends the status of digital input signals to the controller.
This function turns on/off digital output signals using commands issued from the controller.
This function sends the timing to input digital input signals to the controller.
This function digitally outputs values depending on the level of each monitor value of the pulse
I/O module, analog I/O module, and encoder I/F module. Values can be digitally output
without the controller.
This function sets whether to hold or clear the preceding outputs when communications with
the controller are interrupted.
MR-MT2010 SSCNET III/H head module
21 V DC or more/3 mA or more
3 V DC or less/1 mA or less
[kg]
Description
4 - 1
24 V DC
24 V DC ± 10%
1.0 A (Note 1)
SSCNET III/H
12
Photocoupler insulation
Within 1 μs
Within 1 μs
Max. 12 (Note 2)
Sink input/source input
2
0.1 A/1 point
Photocoupler insulation
Within 1 µs
Within 1 µs
Sink output
24 V DC ± 10%
Refer to section 1.3.
Refer to section 1.3.
Refer to section 1.3.
0.2