Safety Considerations; Site Preparation; Installing The Outdoor Unit - Nordyne DS5BD User's Information And Installation Instructions Manual

Outdoor air conditioner
Table of Contents

Advertisement

Condensing Unit Section — Each condens-
ing unit is shipped with a refrigerant charge
adequate to operate the outdoor section with
an indoor matching coil or air handler, and 15
feet of refrigeration line.
NOTE: DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK
TESTING.
Matching coils and air handlers are shipped
with a small pressurized holding charge to
pressurize them to keep out contaminants. To
release the pressure, carefully read the instal-
lation instructions provided with the indoor coil
or air handler.
Liquid and Suction Lines — Refrigerant grade
copper tubing should be used when installing the
system. Refrigerant suction line tubing should
be fully insulated.
Field Connections for Electrical Power
Supply — All wiring must comply with current
revisions of the National Electrical Code
(ANSI/NFPA 70) and with applicable local
codes having jurisdiction. The minimum size of
electrical conductors and circuit protection must
be in compliance with information listed on the
outdoor unit data label.

2. SAFETY CONSIDERATIONS

Pressures within the System — Split system
air conditioning equipment contains liquid and
gaseous refrigerant under pressure. Installation
and servicing of this equipment should be per-
formed by qualified, trained personnel thoroughly
familiar with this type of equipment. Under no
circumstances should the Homeowner attempt
to install and/or service the equipment.
Labels, Tags, Precautions — When working
with this equipment, follow all precautions in the
literature, on tags, and on labels provided with
the equipment. Read and thoroughly understand
the instructions provided with the equipment
prior to performing the installation and opera-
tional checkout of the equipment.
Brazing Operations — Installation of equipment
may require brazing operations. Safety codes
must be complied with. Safety equipment (e.g.;
safety glasses, work gloves, fire extinguisher,
etc.) must be used when performing brazing
operations.
WARNING:
Ensure all electrical power to the unit
is off prior to installing or servicing
the equipment. Failure to do so may
cause personal injury or death.

3. SITE PREPARATION

Unpacking Equipment — Remove the card-
board carton and User's Manual from the
equipment. Take care not to damage the tubing
connections when removing the carton.
Inspect for Damage — Inspect the equipment
for damage prior to installing the equipment at
the job site. Ensure coil fins are straight and, if
necessary, comb fins to remove flattened and
bent fins.
Preferred Location of the Outdoor Unit at the
Job Site — Conduct a survey of the job site to
determine the optimum location for mounting
the outdoor unit. Overhead obstructions, poorly
ventilated areas, and areas subject to accumula-
tion of debris should be avoided. The outdoor
unit should be installed no closer than 18 inches
from the outside walls of the facility and in an
area free from overhead obstructions to ensure
unrestricted airflow through the outdoor unit.
Facility Prerequisites — Electrical power
must be supplied to the equipment. Electrical
power supplied must be adequate for proper
operation of the equipment. The system must
be wired and provided with circuit protection in
accordance with local building codes and the
National Electrical Code.
Minimum Circuit Ampacity — Electrical wiring
to the equipment must be compatible and in
compliance with the minimum circuit ampacity
listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size — Circuit
protection for the outdoor unit must be compat-
ible with the maximum fuse/circuit breaker size
listed on the outdoor unit data label.

4. INSTALLING THE OUTDOOR UNIT

Slab Mount — The site selected for a slab mount
installation requires a stable foundation and one
3

Advertisement

Table of Contents
loading

Table of Contents