Preparing the installation

Accessories
Please check if items below are included in installation accessories.
Insulation
Name
(for pipe)
Shape
Soundproof and soundproofing materials
Name
Shape
Selecting the refrigerant pipe for installation
The design pressure of MCU for R-410A is about 4.1 MPa (594.6psi). For safe use of the product, please refer to the table below in
selecting the installation pipe.
Outer diameter
mm
6.35
9.52
12.70
15.88
19.05
22.22
25.40
28.58
31.75
34.92
38.10
41.28
44.45
50.80
53.98
• For pipes larger than Ø 19.05mm(3/4"), drawn type (C1220T-1/2H or C1220T-H) type copper pipe must be used. If an
annealed type (C1220T-O) copper pipe is used, pipe may break due to its low pressure resistance and cause personal injury.
CAUTION
• Pour les tuyaux de diamètre supérieur à Ø 19,05 mm (3/4"), du cuivre étiré (C1220T-1/2H ou C1220T-H) doit
être utilisé. Si du tuyau en cuivre recuit (C1220T-O) est utilisé, une rupture est possible compte tenu de sa faible
MISE EN GARDE
résistance à la pression, ce qui peut provoquer des blessures.
Insulation
Installation
(for base)
manual
MXJ-YM1509M
inch
1/4
3/8
1/2
5/8
3/4
7/8
1
1 1/8
1 1/4
1 3/8
1 1/2
1 5/8
1 3/4
2
2 1/8
Pattern
Cable tie
sheet
Minimum thickness
mm
inch
0.70
0.028
0.70
0.028
0.80
0.031
1.00
0.039
0.90
0.035
0.90
0.035
1.00
0.039
1.10
0.043
1.10
0.043
1.21
0.048
1.35
0.053
1.43
0.056
1.60
0.063
2.00
0.079
2.10
0.083
Pipe socket
MCU-S4*
MCU-S1*
MCU-S6*
MCU-S2*
MCU-S8*
MCU-S12*
-
Temper grade
Annealed
Drawn
7