    Contents Safety precautions ...........................................3 Mesures de sécurité ..........................................5 Preparing the installation ........................................7 Space requirements ..........................................9 Installing the unit ..........................................11 Refrigerant piping works ........................................15 Wiring works ............................................19 Commisioning ............................................24...
  • Page 3: Safety Precautions

    Safety precautions The safety information and precautions below must be kept for the safety of users and installers. Before installing an air conditioner, please read this manual thoroughly to ensure that you know how to safely and efficiently install a new appliance. DVM S air conditioner uses R-410A refrigerant.
  • Page 4 Safety precautions FOR INSTALLATION WARNING Make sure to connect wires thoroughly and fix them firmly so that no outer pressure of the wires would put on the terminal block. If the terminal is loose, it may generate heat and cause a fire. Supplied power should be more or less than 2% of the rated power.
  • Page 5: Mesures De Sécurité

    Mesures de sécurité Les renseignements sur la sécurité et les précautions ci-dessous doivent être conservés pour garantir la sécurité des utilisateurs et des installateurs. Avant d'installer un climatiseur, veuillez lire attentivement ce manuel pour vous assurer que vous savez comment installer efficacement et en toute sécurité...
  • Page 6 Mesures de sécurité MONTAGE AVERTISSEMENT Veillez à bien serrer les fils et à les fixer fermement afin qu'aucune pression extérieure sur les câbles ne puisse provoquer une traction sur le bornier. Si une cosse est mal serrée, cela peut générer de la chaleur et provoquer un incendie. L'alimentation électrique fournie peut être supérieure ou inférieure de 2 % par rapport à...
  • Page 7: Preparing The Installation

    Preparing the installation Accessories Please check if items below are included in installation accessories. Insulation Insulation Installation Pattern Pipe Name Cable tie (for pipe) (for base) manual sheet socket Shape Please purchase Y-connector separately. (Not included) Y-connector Name [ Ø 9.52 mm (3/8"): DB96-23143A ], [ Ø 15.88 mm (5/8"): DB96-23144A ] Shape Selecting the refrigerant pipe for installation The design pressure of MCU for R-410A is about 4.1 MPa.
  • Page 8 Preparing the installation MCU indoor/outdoor unit compatible table Before installing MCU, refer to the compatible table below and find the model before installation. Outdoor Unit Indoor Unit MCU-S6NEK2N MCU-S4NEK3N AM✴✴✴✴X✴✴✴✴ AM✴✴✴✴N✴✴✴✴ MCU-S2NEK2N MCU-S1NEK1N Model Description below 61.6 kW (216MBH) MCU-S6NEK2N MCU Kit below 61.6 kW (216MBH) MCU-S4NEK3N...
  • Page 9: Space Requirements

    Liquid pipe connected to indoor unit Gas pipe connected to indoor unit ø 9.52 (ø 3/8) WELDING ø 15.88 (ø 5/8) WELDING <MCU-S1NEK1N> Space requirements 1. Since refrigerant noise can be generated during the MCU operation, do not install the unit on the ceiling of the places that requires silence such as bedrooms, libraries, hospitals and offices etc.
  • Page 10 Space requirements 3. It is normally recommended to install MCU in a hallway but a bulkhead should be installed to minimize the noise from being transferred to living area. (Refer to the below figure) Bulkhead Living area Hallway Living area Living area Hallway Living area...
  • Page 11: Installing The Unit

    2 3 4 2 3 4 2 3 4 Combination of A+B port Combination of C+D port Combination of E+F port Default In case of MCU connection in series, the maximum capacity of indoor units in MCU series connection is 61.6 kW...
  • Page 12 Installing the unit 3. Preparation before installation. 1) Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. • Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity.
  • Page 13 5. How to connect the pipe line. Protect with wet towel when welding 70 mm Pipe connection from outdoor unit ← Default installing direction. Low pressure gas pipe conection (welding) High pressure gas pipe connection (welding) Liquid pipe connection (welding) Pipe connection to indoor unit Liquid pipe (welding) Gas pipe (welding)
  • Page 14: Refrigerant Piping Works

    Refrigerant piping works Method and cautions on brazing the pipe Keeping refrigerant pipe clean and dry To prevent foreign materials or water from entering the pipe, it is important to keep the refrigerant pipe clean, dry and sealed during installation. Exposure place Exposure time Sealing type...
  • Page 15 5. Select the insulation of the refrigerant pipe. Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size. Indoor temperature of 30°C(86°F) and humidity of 85% is the standard condition. If install in a high humidity condition, use one grade thicker insulator by referring to the table below.
  • Page 16 Refrigerant piping works Installing the circuit breaker and wires Power supply MCCB Power cable Earth cable Communication cable Max : 242V XA, 30mmA 0.0039inch 0.0039inch 0.0012~0.0023inch (2.5mm (2.5mm (0.75~1.5mm Min : 198V 0.1 sec Installing the wire Supply the 220-240V/208-230V power to L1, L2 (L, N) of MCU separately Connect the communication cable from the outdoor unit to F1, F2 of MCU.
  • Page 17 Choose the compressed socket based on the cross-section of the connecting wire. Silver solder Nominal dimensions for cable [mm (inch2)] 1.5 (0.002) 2.5 (0.003) 4 (0.006) Nominal dimensions for screw [mm (inch)] 4 (0.157) 4 (0.157) 4 (0.157) 4 (0.157) 4 (0.157) Standard dimension [mm (inch)] 6.6 (0.259)
  • Page 18: Wiring Works

    Wiring works Setting MCU address and port Process 1. MCU address Set MCU address by rotary switch. setting Example> If you want to set MCU address to 21, set upside rotary switch to 2 and set bottom rotary switch to 1 MCU Address MCU Address Default...
  • Page 19 4. MCU address and Auto setting : refer to 'auto pipe pairing' port setting for Manual setting : indoor unit 1. Wireless remote controller 1) Enter mode to set option 2) Assign an indoor unit MCU port address by wireless remote controller - The initial setting status of indoor unit ADDRESS(MAIN/RMC/MCU port) is “0A0000- 100000-200000-300000”...
  • Page 20 Wiring works 4. MCU address and 2. Wireled remote controller port setting for - Setting for MWR-WE11N indoor unit 1) Press the Delete and Set buttons at the same time for more than three seconds. Then you will enter the additional function settings, and the [main menu] will be displayed. 2) Assign an indoor unit MCU port address with main menu 4, sub menu 7 (MCU address is assingned to SEG 12, Port address is assinged to SEG 4) If you want to know the detailed operation of MWR-WE11N , refer to installation manual for MWR-WE11N...
  • Page 21 • The Direct-connected indoor unit without MCU like below picture, be sure to set their options to "Cooling only unit setting“ and then connect them to a low pressure gas pipe and a liquid pipe. This indoor unit only operate to cooling mode. Direct-connected indoor unit without MCU (Connecting Only Low Pressure Gas Pipe / Liquid Pipe) Set to Cooling Only Unit...
  • Page 22 Wiring works Option SEG7 SEG8 SEG9 SEG10 (When setting SEG3) (When setting SEG3) Standard for mode Compensation option for Long pipe or height Explanation PAGE Time required for changing Cooling → diffference between indoor units mode change Heating mode Remote Controller Display Indication Details Indication Details Indication...
  • Page 23 Display segment Display Contents Remarks (Pushed time) On/Off for solenoid valve A_C, A_H • ✴_C : Cooling solenid valve of port ✴ On/Off for solenoid valve B_C, B_H • ✴_H : Heating solenid valve of port ✴ On/Off for solenoid valve C_C, C_H •...
  • Page 24: Commisioning

    Commisioning ❈ After installing MCU, check those items below. If you find something unfulfilled, refer to the manual to complete it. Item Check 1. If the gas leaking test has been completed or not. 2. If MCU has been fixed securely enough to avoid the danger of vibration and falling or not. 3.