Aspiration smoke detector LSN improved
5.4

Installing the unit

Notice!
When selecting the installation location, it must be ensured that the unit displays are easily
visible.
Remember when planning that the unit fans generate a noise level of approx. 45 dB(A).
The installation location may not be in any door opening area.
A
Installation of the FAS-420
The air outlet on the unit must not be obstructed. There must be a free area of 10 cm in front
of the air outlet.
The aspiration smoke detector can be installed with the aspiration device pointing upwards or
downwards. Rotate the cover through 180° in the required direction.
Installing on mounting type MT-1
Installation material
FAS-420
Bosch Sicherheitssysteme GmbH
1
2
≥ 10 cm
Aspiration from below
If the air-return pipe is directed upwards, it must be guaranteed that no foreign bodies or
dripping water can penetrate the air return. You should therefore use a short, downward
angled pipe.
Mounting type MT-1
The Aspiration smoke detector is either bolted directly to the wall provided for
installation using the rear panel or installed by means of unit mounting type MT-1, e.g.
onto frames.
1
Installing the Aspiration smoke detector | en
B
≥ 10 cm
2
Cylinder or flat head screws
Thread diameter: max. 6 mm
Head diameter: 10 mm
Operation guide
A
Aspiration device
upwards
B
Aspiration device
downwards with air
outlet opening upwards
1
Smoke aspiration pipe
2
Air-return pipe
1
Horizontal installation
2
Vertical installation
2020.04 | 6.1 | F.01U.029.275