Lsn Configuration; Parameter Settings Via Rps (Remote Programming Software) - Bosch FAS-420-TT Series Operation Manual

Aspiration smoke detector lsn improved
Hide thumbs Also See for FAS-420-TT Series:
Table of Contents

Advertisement

82
en | Installing the Aspiration smoke detector
Designation
Shield
X8 LSN
X7 24 VDC
X6 ext.
Display
* Digital parallel displays for the FAS-420 series are available by separate order.
5.5.2

LSN Configuration

Once the aspiration smoke detector has been connected to the LSN, the detector and
detector module, or the two detector modules (FAS-420-TP2 and FAS-420-TT2), are
configured using the FSP‑5000‑RPS programming software via a laptop connected to the Fire
Panel.
Information on the LSN configuration can also be found in the Online Help feature of the RPS
programming software. Notes on diagnostics data for the fire panel are contained in the
operation guide for the FPA‑5000.
Notice!
Both a dual-detector dependency and a dual-zone dependency can be established when
connecting the FAS-420-TP2 and the FAS-420-TT2 to the Modular Fire Panel.
5.5.3

Parameter settings via RPS (Remote Programming Software)

The parameters for each detector module are specified in the relevant "Sensor" dialog window
via drop-down fields.
The default settings in RPS are in bold in each case.
Detector
module
DM‑TT‑01(05)
DM‑TT‑10(25)
DM‑TT‑50(80)
2020.04 | 6.1 | F.01U.029.275
Cable
-
b1+
Yellow
a1-
White
b2+
Yellow
a2-
White
V+
Red
V-
Black
V+
Red
V-
Black
V+
Red
V-
Black
D+
-
D-
-
Enter the used detector module.
Select all other parameters (see tables).
Sensitivity
DM‑TT‑01(05)
0.015%/m (0.05%/
m)
0.03%/m (0.1%/m)
Function
Shield wire
LSN b, incoming
LSN a, incoming
LSN b, outgoing
LSN a, outgoing
Additional power supply, incoming
Additional power supply, outgoing
Supply voltage for digital parallel display *
Data line connection for digital parallel display *
DM‑TT‑10(25)
0.1%/m (0.25%/
m)
0.2%/m (0.5%/m) 1.0%/m (1.6%/m)
Operation guide
Aspiration smoke detector LSN improved
Further
sensitivity
DM‑TT‑50(80)
Second
sensitivity can
0.5%/m (0.8%/
be set, e.g. for
m)
day/night
mode. (Left:
Bosch Sicherheitssysteme GmbH