Project Planning With Branch Pipes - Bosch FAS-420-TT Series Operation Manual

Aspiration smoke detector lsn improved
Hide thumbs Also See for FAS-420-TT Series:
Table of Contents

Advertisement

70
en | Planning
Diameter of the air sampling openings
The diameter of the air sampling openings is derived from the number of air sampling
openings. The precise value can be obtained from Simplified pipe planning.
The pipe is closed with an end cap without bore hole.
Arrangement
The air sampling openings must face the airflow.
Note when planning that the air-conditioning ducts are often only accessible from two sides
for installation of the pipe system.
Example
The figure below shows two planning examples of pipe systems in air-conditioning ducts.
a
Ducts with small and large duct cross-sections
Refer to
4.12

Project planning with branch pipes

Project planning with branch pipe are suitable for sampling points which are located distantly
from the main run of the pipe system.
2020.04 | 6.1 | F.01U.029.275
FAS / FCS
150
200
1/2 b
b
A > 0,5 m
2
Simplified pipe planning, page 53
FAS / FCS
100
a
100
1/2 b
b
A ≤ 0,5 m
2
Operation guide
Aspiration smoke detector LSN improved
A
Cross-sectional area of
duct (with A = a x b)
a
Height of air-conditioning
duct
b
Width of air-conditioning
duct
Bosch Sicherheitssysteme GmbH

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents