MULTIQUIP LT6k Operation Manual page 64

Light tower/generator
Table of Contents

Advertisement

Lamp TROuBLesHOOTIng guIde
Use the following procedure and wiring diagrams on the
next pages to determine which of the four lights is not
functioning:
Connections
1. Make sure that lamp #1 power cable is plugged into
the J1 connector on the T-Bar assembly.
2. Make sure that lamp #2 power cable is plugged into
the J2 connector on the T-Bar assembly.
3. Make sure that lamp #3 power cable is plugged into
the J3 connector on the T-Bar assembly.
4. Make sure that lamp #4 power cable is plugged into
the J4 connector on the T-Bar assembly.
Starting
1. Start the generator and verify that there are no
abnormal sounds.
2. Turn lamp circuit breakers (CB2 and CB3) to the On
position.
3. Wait a few minutes and determine which lamp is not
igniting.
4. If one of the lights is OFF, disconnect its power cable
and plug it into a receptacle that is known to be working.
dO nOT unplug a power cable from the T-Bar while
power is being supplied by the generator. Always turn
the circuit breaker OFF before unplugging a power
cable.
page 64 — LT6K LIgHT TOWeR • OpeRaTIOn manuaL — Rev. #2 (09/11/14)
troublesHooting (lamps)
5. If the lamp still does not ignite after plugging it into a
working receptacle (460 VAC present), then the lamp
is defective and has to be replaced.
6. If the lamp ignites after plugging it into a working
receptacle, continue with step 7.
7. With the voltmeter set to the AC position, connect the
negative lead of the AC voltmeter to any (neutral) white
wire on the junction terminal block. This block connects
all the neutral wires (white) in the system.
8. Connect the positive lead of the voltmeter to the output
side of the circuit breaker where the lamp was originally
OFF and observe that 460 VAC is present. Make sure
circuit breaker is On.
9. If no output voltage is present, the circuit breaker is
defective and needs to be replaced.
10. If the correct output voltage is present then it can be
assumed that the generator is working correctly and
the correct voltage (460 VAC) is being supplied to the
ballast. Then it can be assumed that the ballast for that
lamp is defective. Replace ballast.
Ballast Removal
1. Place the main (CB1) and lamp circuit breakers (CB2
and CB3) in the OFF position. Make sure that no
voltage is being supplied to the ballast compartment.
2. Remove the panel from the generator frame that
encloses the ballasts. There are two such panels
located at the front of the generator just to the left and
right of the mast.
3. Make sure to discharge the ballast capacitor.
4. Remove the defective ballast, taking care to guard
against electrical shock when coming in contact with
the ballast and capacitor. The capacitor is known to
store an electrical charge, that when discharged could
result in a harmful shock. Make sure to discharge
capacitor.

Advertisement

Table of Contents
loading

Table of Contents