D9412GV4/D7412GV4/D7212GV4 | Installation and Operation Guide | Appendix A: System Wiring Diagrams
Figure 37: D7412GV4/D7212GV4 SDI and Zonex Devices System Wiring
1 - Up to 16 supervised D1255 (all versions),
D1255RB, D1256, D1256RB Keypads, or
D1257RB or D1257 Fire Annunciators, or up to 8
supervised D1260 Keypads (all versions)
2 - Up to 2 D9210C Access Control Interface
Modules (not available on the D7212GV4)
3 - Up to 1 supervised 9131A Parallel Printer
Interface Module
4 - Power limited, supervised
The number of D8129 OctoRelays that can be connected to each zonex terminal on the control panel is limited by the
*
number of D8128D OctoPOPITs connected to the same terminal. Refer to the D8128D Installation Guide (P/N: F01U070537)
or the D8129 Operation and Installation Guide (P/N: F01U036302) for specific information.
Terminals 24 through 36 are power limited, supervised.
Fire and Intrusion devices must be on separate circuits. Refer to ICP-SDI-9114 Installation
Instructions (P/N: F01U030068).
Bosch Security Systems, Inc. | 3/12 | F01U266054-01
5 - Up to two DX4020, ITS-DX4020-G, or B420
Ethernet Communication Modules
6 - Power limited
7 - D8125 POPEX No. 1
8 - Up to 67 D9127U/T POPITs
9 - Zonex 1: Up to 9 D8128Ds
10 - Zonex 1: Up to 8 D8129s maximum
79